background image

38

Storage Tank Circulation pump 

2

Storage Tank Circulation pump 

1

Relief valve

Hot water

 

supply points

Hot water supply line

Hot water return lin

e

Cold water supply pipe *1

When installing 2 pumps in parallel

Set “Yes” for the question 

“Start pump rotation?” in system settings.

(See System controller unit Installation Manual

)

*  Size the cold water supply piping to allow for 

    maximum flow rates of the building.

*  Be sure to connect the cold water supply pipe 

    between the hot water storage tank and intake 

    side of the storage tank circulation pump.

Thermostat

System Controller Unit

Remote 

controller 

cord

Remote Controller

Unit 

1

Unit 

2

Unit 

3

Unit 10

Unit 11

Unit 12

(copper or stainless steel pipe)

Hot water

storage tank

(copper or stainless steel pipe)

Return line  circulation pump

(Size for max. flow

)

(Size for max. flow

)

Storage tank supply line (copper or stainless steel pipe)

Storage tank return line (copper or stainless steel pipe)

B-2. Example of Installation with a Storage Tank and Recirculation System (Using external system controller) 

The pump will push water through the Multi-System to heat up the tank.

When the temperature of the thermostat is high, the system controller will turn off the pump until 

the the temperature cools down.

For the set temperature of the remote controller

, use the temperature (of the thermostat) + about 10°F

.

To achieve the highest recovery

, size the storage tank circulation pump for maximum capacity

  

(12 GPM (each) @ 50 ft. of head (160°F setting or less) + piping losses through the system.) 

 

Verify the supply pressure to the units is at least 30 PSI.

 (Tank recirculation system)

Содержание GQ-C5032WZ US

Страница 1: ...e installation instructions Failures and damage caused by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accor...

Страница 2: ...ty 1 1 Remote Controller Cord 26ft 8m 1 each Isolation Valves includes pressure relief valve Pipe Cover PC 7S 1 1 Owner s Guide Warranty Installation Manual this document 1 System Controller Unit SCU...

Страница 3: ...minal Block Cord Connector Cord Connector 3 Quick Connect Multi System Installation The Quick Connect Multi System allows the installation of two units together utilizing only the Quick Connect Cord T...

Страница 4: ...erature of the water supply as unexpected accidents may occur as a result Check Water Supply Quality If the water supply is in excess of 12 grains per gallon 200 mg L of hardness acidic or otherwise i...

Страница 5: ...m materials Do not locate the vent termination directed towards a window or any other structure which has glass or wired glass facing the termination Install in a location where the exhaust gas flow w...

Страница 6: ...width Provide clearance of 24 600mm or more in front of the unit to facilitate inspection and repair Do install the unit in a location where the unit is out of reach such as the wall of the second flo...

Страница 7: ...149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that...

Страница 8: ...ce when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing...

Страница 9: ...e installer The installer must be professionally trained to do such work and must always follow all local and national codes and regulations Gas line sizing calculations must be performed for every in...

Страница 10: ...ding to total btuh demand of the building and length from the meter or regulator so that the following supply pressures are available even at maximum demand WARNING Natural Gas Supply Pressure Min 5 W...

Страница 11: ...se 50 15m 175 000 Btuh requires 1 Outlet E 25 7 5m Use 30 9m 300 000 Btuh requires 3 4 Section 4 45 13 5m Use 50 15m 475 000 Btuh requires 1 1 4 Natural Gas Meter Noritz Condensing Tankless Gas Water...

Страница 12: ...t each appliance to verify all appliances are receiving a minimum of 5 WC for NG or 8 WC for LP If all appliances are not receiving the minimum inlet pressure the gas piping system may need to be chan...

Страница 13: ...nnected to any heating system or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the s...

Страница 14: ...a pressure meter on the inlet If this is not done local boiling will occur inside the water heater causing abnormal sounds and decreasing the durability of the heat exchanger Freeze Prevention Freezi...

Страница 15: ...m If this water heater will be installed in an application where the supply water is hard the water must be treated with either the Noritz H2Flow or ScaleShield or a water softener Refer to the below...

Страница 16: ...g pump 4 Connect the drain hose H2 to the circulating pump 5 Connect the drain hose H3 to the drain valve V4 6 Pour 2 gallon of and gallon water into the bucket Noritz recommends for flushing 7 Place...

Страница 17: ...lushing solution through the water heater for 1 hour at a rate of 1 5 gallons per minute or more 5 The code C60 is displayed on the Remote Controller when the water heater detects the flow of the flus...

Страница 18: ...t Covers 9 Open the gas supply valves and water outlet valves 10 Check for correct operation of the water heaters is displayed when the Main Water Heater s blue connector is connected is displayed whe...

Страница 19: ...g ON OFF PROG ALARM OFF 120 F Temp CCC Error unit 01 Beep Beep Press ON ON ALARM OFF STOP OFF Display Example In case of Unit 1 s blue connector is connected System down is displayed when the all unit...

Страница 20: ...cedure 3 1 3 5 7 Disconnect the blue connector marked FLUSH for flushing The Code CCC goes out on the Remote Controller 8 Close the Front Covers 9 Open the gas supply valves and water outlet valves 10...

Страница 21: ...as short as possible Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of...

Страница 22: ...CE 1 2 PVC pipe DO NOT ADD ANY VALVES DO NOT ADD ANY VALVES Condensing Tankless Gas Water Heater Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensate will b...

Страница 23: ...eywell Aquastat Model L6006A or L6006C Aquastat Wiring 3 Set the Aquastat to 10 F below the set output temperature An aquastat is the minimum pump control requirement in order to maintain the full rec...

Страница 24: ...ly required by the water heater is 120VAC at 60 Hz The power consumption may be up to 410W or higher if using optional accessories Use an appropriate circuit Do not disconnect the power supply when no...

Страница 25: ...oblems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of slack in order...

Страница 26: ...cover select Initial settings using the Buttons 4 Press the ENTER button the Initial settings screen appears on the display 5 Select F gal C L using the Buttons 6 Press the ENTER Button and select eit...

Страница 27: ...wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with pumps 1 Locate and prepare the pum...

Страница 28: ...Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Connect Cord 2 tag A B 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 Red 2 Bla...

Страница 29: ...ar normal the burner may need to be cleaned by qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure...

Страница 30: ...rol manual valve clockwise to the off position Should overheating occur or the gas supply fail to shut off turn off the manual control valve to the appliance Handling after trial operation If the unit...

Страница 31: ...TING 6 x 0 5 13mm 12 x 0 24 x 0 4 6 x 10mm OBLONG HOLE 6 x 0 5 13mm 12 x 0 24 x 0 4 6 x 10mm OBLONG HOLE 18 7 476mm 18 9 480mm 14 2 360mm 0 7 19mm 0 4 10mm 1 4 36mm 2 8 70mm 3 9 100mm 5 5 140mm 6 7 17...

Страница 32: ...minutes of connecting electrical power before turning on the Power On Off Button press the or button on the remote controller and hold until the display blinks 99 If 99 does not blink on the remote c...

Страница 33: ...s system will make hot water more quickly available to remote fixtures The pump will circulate water through the loop until the entire loop is warm and then the system controller will turn off the pum...

Страница 34: ...trol Wires use external relayV Unit 1 Set Yes for the question Start pump rotation in system settings See System controller unit Installation Manual When installing 2 pumps in parallel Set Yes for the...

Страница 35: ...B Power PCB B5 B5 System Controller No 5 No 4 No 3 No 2 Remote Control terminal block Remote control terminal block Remote Controller Cord PCB Power PCB PCB Power PCB Multi System Wiring Use SC 301 6M...

Страница 36: ...to both the cold water supply piping and the hot water supply piping to prevent freezing during cold weather and to prevent heat loss through the piping Unit 1 Unit 2 Unit 3 Unit 10 Unit 11 Unit 12 S...

Страница 37: ...tem controller This system will make hot water more quickly available to remote fixtures The pump will circulate water through the loop until the entire loop is warm and then the system controller wil...

Страница 38: ...l pipe Hot water storage tank copper or stainless steel pipe Return line circulation pump Size for max flow Size for max flow Storage tank supply line copper or stainless steel pipe Storage tank retur...

Страница 39: ...it 3 CAUTION The below diagram shows the connection of 3 units to the system controller When connecting 4 or more units follow the same procedure Connect the water heaters to the system controller fol...

Страница 40: ...er In order to use this product safely read this installation manual carefully and follow the installation instructions Potential dangers from accidents during installation and use are described below...

Страница 41: ...t The value in indicates the quantity Remote Controller Mounting bracket Raised countersunk head wood screw Wall anchor Raised countersunk head screw For junction box installation Machine screw When a...

Страница 42: ...f the remote controller and the frame pull the entire decorative frame forward while pressing the sections indicated where the fingers are in the figure below If it does not come off insert a flat hea...