23
• When installing this water heater outdoors, must be used "Outdoor Vent Cap (VC-6)".
• Disconnect power and then turn ON dip switch #2 if outdoor installation.
• Make sure the clearance of the water heater in accordance with page 9 (Outdoor Installation).
● How to change the dip switches*
*The dip switch bank is placed on the circuit board.
1. Disconnect electrical power to the water heater before changing the dip switches**.
2. Open the front cover of the water heater (4 screws).
3. Adjust the dip switches. (See the illustration.)
4. Close the front cover of the water heater (4 screws).
5. Reconnect the electrical power to the water heater.
**Failure to perform this step will result
a "73" code displayed on the remote
controller and a cease in operation.
If this occurs, disconnect, then
reconnect electrical power to the
water heater to reset the system.
3" (75mm) or more
36" (900mm)
or more
24" (600mm)
or more
Outdoor
Vent Cap
(VC-6)
Exhaust Gas
Intake Flue
Outdoor Vent Cap (VC-6) for
outdoor installation
* Dip switch No.2 is turned on.
Refer to the instructions provided
with Outdoor Vent Cap for additional detail.
Outdoor Installation
The location of Dip Switch Bank
1 2 3 4 5 6 7 8
OFF
ON
The power must be unplugged when adjusting
the DIP switch to switch the airflow amount.
Disconnect power to the water heater before changing the
dip switches. Failure to perform this step will result in a “73”
code displayed on the remote controller and a cease in
operation. If this occurs, disconnect power to the water
heater to reset the system.