82
19.2 Procedure for Flushing the Plate Heat Exchanger
NOTE
This procedure is only intended for use by a qualified service professional or authorized Service
Representative. Any unauthorized use of this procedure may result in voiding the Noritz America
Limited Warranty. Contact Noritz America at 1-866-766-7489 for additional support.
To prevent damage to the Plate Heat Exchanger from Scale Build-up, the Plate Heat Exchanger needs to be
flushed* to remove the Scale Build-up.
Damage to the Combi Boiler due to Scale Build-up is not covered by the Combi Boiler’s warranty.
* Connect the blue connector marked “FLUSH” for flushing near the Circuit Board when flushing the Plate Heat Exchanger.
NOTE
The Combi Boiler must remain connected to the electrical power when flushing the Plate Heat
Exchanger.
The preparation of the flushing system
1. Close the gas supply valve.
2. Close the Domestic Water Inlet valve (V1) and the Domestic Water Outlet valve (V2).
3. Connect the one drain hose (H1) to the drain valve (V3), and then the other to the circulating pump.
4. Connect the drain hose (H2) to the circulating pump.
5. Connect the drain hose (H3) to the drain valve (V4).
6. Pour 1 gallon of “Calcium, Lime and Rust Removal Product” and 1 gallon water into the bucket.
It is recommended “Calcium, Lime and Rust Removal Product” for flushing.
7. Place the both drain hoses (H2 and H3) into the bucket filled with the flushing solution.
8. Open the both drain valves (V3 and V4).
Gas Supply
Valve
Bucket
Flushing
Solution
Circulating
Pump
** Isolation Valves may be purchased as an accessory from an authorized manufacturer’s wholesaler.
This allows for full diagnostic testing and easy flushing of the system.
Contact Noritz America for more information. (1-866-766-7489)
䚷
Gas
Supply
Combi Boiler
Continue to connect
V3
V4
H2
H3
H1
V1
Domestic
Water
Inlet
V2
Domestic
Water
Outlet
If a submersible pump is used,
then only 2 hoses will be
needed (H1 and H3).
Isolation Valves** are necessary for
flushing the Plate Heat Exchanger.
V4
Domestic Water Inlet
Domestic Water Outlet
V2
V3
V1
Maintenance