70
[If installed a single Combi Boiler]
4. Open a hot water fixture and confirm that the
Flame symbol comes on, and that hot water is
being produced.
NOTE
If an error code “11” appears on the
Operation Display, air may be trapped
in the gas line.
1) Close a hot water fixture.
2) Turn the Combi Boiler off and then
back on.
3) Reopen a hot water fixture.
4) If necessary, repeat until the air is
completely purged from the gas
line.
5. Make sure the proper installation and proper
operation according with on page 52.
NOTE
If step 4 and 5 cannot be done, the
Quick Connect Cord may not be
properly connected.
Check that the cord is connected
according with on page 51 and 52.
Proceed to Steps 6 and 7
NOTE
If an error code “11” or “F11” appears
on the Operation Display, air may be
trapped in the gas line.
1) Close a hot water fixture.
2) Turn the Combi Boiler off and then
back on.
3) Reopen a hot water fixture.
4) If necessary, repeat until the air is
completely purged from the gas
line.
[If installed with a Quick Connect Multi-System]
4. Slowly open a hot water fixture and check that
a unit ignites independently. Check to see that
the hot water temperature is the same as the
temperature displayed on the Operation Display.
5. Check that the hot water temperature changes
by changing the temperature setting.
Proceed to Steps 6 and 7
[Procedure to follow after step 5 for both
installation of a single Combi Boiler and
installation with a Quick Connect Multi-System]
6. • Make sure that there are no obstructions
blocking the condensate drain line from
discharging condensate.
• Be sure to check that condensate is freely
flowing from the condensate drain piping.
Condensate will begin flowing out of the
Combi Boiler
within 15 minutes after
operation has started
.
error code 64 will continue to be displayed on
the Operation Display. This warning indicator
will allow the Combi Boiler to operate. To
completely clear error code 64, refer to the
“How to reset error code 64” section on this
page.
•
DO NOT ignore this condition (Error Code 20
and 64).
Without purging air from the Combi boiler,
heating system and internal pump, the error
code 20 or 64 will continuously appear and
potentially damage the Heat Exchanger.
[How to reset error code 64]
Before resetting the error code 64, purge air
from the internal pump in the Combi Boiler
completely according with pages 68 - 69. Failure
to properly remove air from the internal pump
will cause this error to continuously appear and
potentially damage the Heat Exchanger. To reset
the error code 64, turn off the Maintenance
Writer (MW) “3E”*.
* Maintenance Writer (MW)
1. Disconnect the electrical power and wait for
10 seconds (Leave the Operation Display off).
2. Reconnect the electrical power.
3. Hold the
button
until the display blinks
“99”. Now in the MW mode.
4. Scroll to MW “3E” by using the or
button
. The display blinks “3E”.
5. Press and hold the
ENTER button
for
approximately 1 second. “DHW Icon” will be
OFF if the procedure is done correctly.
6. Once complete, hold and press both the
/
buttons
together for 5 seconds until the
the Operation Display starts beeping.
2) With a bucket ready, remove the water drain
valves.
NOTE
Approximately 0.13 gallon (0.5 L) of
water will drain out.
1) Close the hot water valve and the water
supply valve.
Inlet
O-Ring
Water drain valve
(with water filter)
7. After the trial operation, clean the filters in the
cold water inlet according to the procedure as
follows.