Maximum Vent Lengths

•  This appliance has been designed to be vented 

with either 3" (75mm) or 4" (100mm) PVC or 
CPVC pipe. 

   Do not exceed the following maximum vent lengths:

   * Not including the termination

      

Refer to page 16 for max. vent lengths

      when using termination VK3-H-PVC.

•  Maintain the same vent pipe diameter from the 

heater fl ue to the vent termination. The exhaust 
and intake pipes must be the same vent pipe 
diameter.

8.

 

Vent Pipe Installation

(Indoor Installation Only)

WARNING

Be sure to do

CARBON MONOXIDE POISONING
Follow all vent system requirements in accordance with relevant local or state regulation, 
or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI 
Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with NSCNGPI.

  No. of Elbows 

Max. Straight Vent Length*

 

N/A 

39' (11.7m)

 

16' (4.8m) 

45' (13.5m)

 

22' (6.6m) 

51' (15.3m)

 

28' (8.4m) 

57' (17.1m)

  Pipe diameter 

3" (75mm)  4" (100mm)

• Under normal conditions, this appliance will 

not produce an exhaust flue temperature 
in excess of 149°F (65°C) and schedule 40 
PVC pipe may be used as the vent material.  
If required by local code, schedule 40 or 80 
CPVC may also be used on this appliance.

  Refer to page 14 for additional requirements.

• Make sure the vent system is gas tight and 

will not  leak.

•  Support the vent pipe with hangers at regular 

intervals as specifi ed by these instructions or 
the instructions of the vent manufacturer.

• Do not common vent or connect more than 

one appliance to this venting system.

•  The total vent length including horizontal & vertical 

vent runs should be no less than 3' (0.9m).

•  Do not store hazardous or flammable sub-

stances near the vent termination and check 
that the termination is not blocked in any way.

•  Steam or condensed water may come out 

from the vent termination.  Select the location 
for the termination so as to prevent injury or 
property damage.

•  If snow is expected to accumulate, take care 

the end of the pipe is not covered with snow 
or hit by falling lumps of snow.

General Requirements

Clearances

PVC or CPVC has been approved for use on this 
appliance with zero clearance to combustibles.

Содержание ecOTOUGH NRC1111-DV-LP

Страница 1: ...work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion After completing instal...

Страница 2: ...Shape Q ty Remote Controller Cord 26ft 8m Quick Connect Cord QC 2 1 1 1 each Isolation Valves includes pressure relief valve Owner s Guide Warranty Installation Manual this document Bird Screen for 4...

Страница 3: ...ater temperature will become unstable as the pipe length increases Distance at center 20 3 36 3 in 515 922mm Quick Connect Cord Union Gas Valve Union Shutoff Valve Shutoff Valve Hot Water Shutoff Valv...

Страница 4: ...ith a Solar Pre Heater Using this unit with a solar pre heater can lead to unpredictable output temperatures and possibly scalding If absolutely necessary use mixing valves to ensure output temperatur...

Страница 5: ...s a result Avoid installation in places where special chemical agents e g hair spray or spray detergent are used Ignition failures and malfunction may occur as a result Carbon Monoxide Poisoning Hazar...

Страница 6: ...nal noises while it is running Before installing make sure that the exhaust flue termination will have the proper clearances according to the National Fuel Gas Code ANSI Z223 1 State of California The...

Страница 7: ...f the unit to facilitate maintenance and service if necessary If possible leave 3 75mm or more above and below the vent pipe to facilitate inspection and repair if necessary Securing of space for repa...

Страница 8: ...k Illustration Outdoor Clearances to Opening into Any Building 12 300mm or more 12 300mm or more There must be no building opening within this area Flue terminal 12 300mm or more 12 300mm or more Vent...

Страница 9: ...aintain clearances in accordance with local installation codes and the requirements of the gas supplier A vent shall not terminate directly above a sidewalk or paved driveway that is located between t...

Страница 10: ...parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take cauti...

Страница 11: ...haust accessory on the top of the appliance as illustrated below Or if the vent pipe has already been installed 2 After installing the drain pipe make sure that the area around the appliance is well v...

Страница 12: ...ill not produce an exhaust flue temperature in excess of 149 F 65 C and schedule 40 PVC pipe may be used as the vent material If required by local code schedule 40 or 80 CPVC may also be used on this...

Страница 13: ...18 00 18 90 m 1 0 2 3 4 ft Vent length Elbows 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Number of pieces 3 3 0 3 3 5 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 3 3 0 3 3 5 3 3 3 3 3 3 3 4...

Страница 14: ...arely cut all pieces of pipe o Remove all burs and debris from joints and fittings o All joints must be properly cleaned primed and cemented Use only cement and primer approved for use with the pipe m...

Страница 15: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 Slope the horizontal vent 1 4 upwards for every 12 300mm toward the termination Use a condensation drain if necessary In the Commonwealth of Massachusetts a...

Страница 16: ...public walkway 6 1 8m from the combustion air intake of any appliance and 3 0 9m from any other building opening gas utility meter service regulator etc T erminate at least 3 0 9m above any forced ai...

Страница 17: ...r must be supplied from the outdoors as shown on pages 15 16 Terminate at least 6 1 8m from the combustion air intake of any appliance and 3 0 9m from any other building opening gas utility meter serv...

Страница 18: ...ance in front of the unit to the door If combustion air will be provided through a duct size the duct to provide 60 cubic feet of fresh air per minute Supply combustion air to the units as per the Nat...

Страница 19: ...1 Natural Gas Meter See next page for the pipe capacity charts Noritz Condensing Tankless Gas Water Heater 199 900 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 10 3...

Страница 20: ...496 55 112 213 440 675 1260 Maximum Capacity of Flex TracPipe in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 206 383 614...

Страница 21: ...ater may not be connected to any heating system or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in...

Страница 22: ...eans to ensure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demanded Also install a pressure meter on the inlet If thi...

Страница 23: ...Required Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install Noritz Isolation Valves...

Страница 24: ...Long runs or applications where the nearest drain is above the water heater will require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the water...

Страница 25: ...PVC pipe DO NOT ADD ANY VALVES NORITZ Condensing Tankless Gas Water Heater DO NOT ADD ANY VALVES NORITZ Condensing Tankless Gas Water Heater Note If the drain line becomes clogged or frozen condensate...

Страница 26: ...0 F 5 C below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and service valve with unions and a pressure re...

Страница 27: ...eater will not activate resulting in possible freezing damage Do not let the power cord contact the gas piping Tie the redundant power cord outside the water heater Putting the redundant length of cor...

Страница 28: ...o operation press the Power On Off Button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display This unit can be programmed so that it wil...

Страница 29: ...the end of the remote controller cord to the terminal block 5 Replace the terminal block cover and install the screw previously removed in step 3 6 Reconnect electrical power to the water heater Exter...

Страница 30: ...m a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Connect Multi System feature Relay connection with larger pumps 85 W 1 Locate and...

Страница 31: ...pling Cord Clamp Ground wire Connector Connector Connecting Quick Connect Cord 2 Caution For Quick Connect Multi System Installation use part QC 2 only sold separately Quick Connect Cord 2 Quick Conne...

Страница 32: ...r a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do...

Страница 33: ...ower to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop a...

Страница 34: ...S INLET COLD WATER INLET HOT WATER OUTLET CONDENSATE DRAIN FROM BOTTOM OF CASE HEIGHT OF EACH FITTING 6 7 170mm 5 5 140mm 3 9 100mm 2 8 70mm 1 4 36mm 0 4 10mm 4 0 5 13mm 6 0 24 x 0 4 6 x 10mm OBLONG H...

Страница 35: ...on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locations...

Страница 36: ...ord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the rem...

Страница 37: ...ual provided with the water heater In order to use this product safely read this installation manual carefully and follow the installation instructions Potential dangers from accidents during installa...

Страница 38: ...t The value in indicates the quantity Remote Controller Mounting bracket Raised countersunk head wood screw Wall anchor Raised countersunk head screw For junction box installation Machine screw When a...

Страница 39: ...mounting bracket Insert the bottom of the remote contoller into the groove at the bottom of the bracket and push in the 2 hooks on top of the remote controller completely If it is difficult to attach...

Страница 40: ...tons 3 Press the ENTER Button the Misc settings screen appears on the display 4 Select Max set Temp using the Buttons 5 Press the ENTER Button 120 F 50 C appears on the display 6 Set the upper limit o...

Страница 41: ...e controller 2 Disconnect then reconnect electrical power to the water heater 3 Press the MENU Button inside the cover select Initial settings using the Buttons 4 Press the ENTER button the Initial se...

Отзывы: