background image

5

CLEARANCES TO COMBUSTIBLE MATERIALS

This furnace is Designed Certified by CSA International  for the minimum clearances to combustible
material listed in Table 6. See the furnace name plate, located inside the furnace cabinet, for specific
model number and clearance information.

Table 2. Minimum Clearances to Combustible Materials

  ‡

 24 inches is the minimum clearance for servicing.

   36 inches is the recommended clearance for service.

IMPORTANT NOTE

The Commonwealth of Massachusetts re-
quires compliance with regulation 248 CMR
4.00 and 5.00 for installation of through – the –
wall vented gas appliances as follows:

(a) For direct-vent appliances, mechanical-

vent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake is installed
below four feet above grade the following
requirements must be satisfied:

1. If there is not one already present, on

each floor level where there are
bedroom(s), a carbon monoxide de-
tector and alarm shall be placed in the
living area outside the bedroom(s). The
carbon monoxide detector shall com-
ply with NFPA 720 (2005 Edition).

2. A carbon monoxide detector shall be

located in the room that houses the
appliance or equipment and shall:

a. Be powered by the same electrical

circuit as the appliance or equipment
such that only one service switch
services both the appliance and the
carbon monoxide detector;

b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and

comply with NFPA 720 (2005 Edi-
tion); and

d. Have been approved and listed by a

Nationally Recognized Testing Lab-
oratory as recognized under 527
CMR.

3. A Product-approved vent terminal must

be used, and if applicable, a Product-
approved air intake must be used. In-
stallation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.

4. A metal or plastic identification plate

shall be mounted at the exterior of the
building, four feet directly above the
location of vent terminal. The plate shall
be of sufficient size to be easily read
from a distance of eight feet away, and
read “Gas Vent Directly Below”.

(b) For direct-vent appliances, mechanical-

vent heating appliances or domestic hot
water equipment where the bottom of the
vent terminal and the air intake is installed
above four feet above grade the following
requirements must be satisfied:

1. If there is not one already present, on

each floor level where there are
bedroom(s), a carbon monoxide de-
tector and alarm shall be placed in the
living area outside the bedroom(s). The

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIAL

High Fire

Cabinet

Minimum Clearances (Inches)

Rated Input

Width

(Btuh)

 (Inches)

Side

Vent

Back

Top

Front

60,000

19 3/4

0

0

0

1

1

80,000

19 3/4

0

0

0

1

1

100,000

19 3/4

0

0

0

1

1

120,000

22 1/2

0

0

0

1

1

Содержание *TE Series

Страница 1: ...ervice or maintenance can cause injury or property damage Re fer to this manual for assistance For additionalinformationconsultaquali fied installer service agency or the gas supplier FOR YOUR SAFETY...

Страница 2: ...upport 15 Location of Outdoor Terminations 18 HorizontalVenting 18 Vertical Venting 19 Vent Freezing Protection 20 ConcentricVentTermination 20 DrainageofCondensateFromFurnace 20 GasSupplyandPiping 21...

Страница 3: ...ts A B Combustion Air Vent 3 See Fig 15 for sizes 1 1 2 x 3 1 2 Dia Opening for Gas Connection 3 4 3 4 3 4 22 1 2 Exhaust Vent Combustion Air Inlet 1 1 2 x 3 1 2 Dia Opening for Gas Connection C 2 PVC...

Страница 4: ...d furnace for installation in a residential garage must be installed as specified on Page 7 of these instructions 10 The furnace is not to be used for temporary heating of buildings or structures unde...

Страница 5: ...ices both the appliance and the carbon monoxide detector b Have battery back up power c Meet ANSI UL 2034 Standards and comply with NFPA 720 2005 Edi tion and d Have been approved and listed by a Nati...

Страница 6: ...erage The 90 upflow furnace can be installed hori zontally in an attic basement crawl space or alcove This furnace can be installed horizon tally to the clearances listed in Table 6 on a platform or o...

Страница 7: ...itch Grey Tubing Soft Tubing 1 4 Vinyl Cap Grey Tubing Drain Trap Soft Tubing PVC Tee Soft Tubing Looped to Provide a Drain Trap 3 to 2 Reducer Optional Drainage Port is Downard Reducer Bushing Altern...

Страница 8: ...ice such as a fireplace insert stove etc CIRCULATINGAIRSUPPLY Plenums and air ducts must be installed in accordance with the Standard for the Installa tion of Air Conditioning and Ventilating Systems...

Страница 9: ...mes contaminated with various household chemicals which can cause severe corrosion in the furnace combus tion system NOTE If the furnace is operated without ad equate air for combustion and ventilatio...

Страница 10: ...WARNING Furnacesinstalledwithcombustionair drawn from a heated space which in cludes exhaust fans fireplaces or otherdevicesthatmayproduceanega tive pressure should be considered confined space insta...

Страница 11: ...90 degree elbow 3 Do not include termination elbows in calculation of vent length 4 This table is applicable for elevations from sea level to 2000 ft For higher elevations decrease vent pipe lengths b...

Страница 12: ...ir Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ducts must extend above attic insulation Air Duct must be at least 1 sq in per 4 000 Btuh of total input rating Ventilation Louver...

Страница 13: ...roper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 or the CAN CGA B149 Instal lation Codes and these instructions Determine that there is no blockage or restriction...

Страница 14: ...installation requires breakable connections in the piping Note that a maximum of two couplings per pipe are allowed UpflowFurnaces Combustion Air Pipe Exhaust Vent Cabinet 5 Support System on Vertica...

Страница 15: ...eter of the piping can be chosen for which the equivalent vent length is less than the maximum allowable vent length Returning to our example we consult Table 3 and deter mine that for a 120 000 Btu h...

Страница 16: ...cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW 12 inches 30 cm for appliances 50 000 Btuh 15 kW C Clearance to permanently closed window D Ver...

Страница 17: ...0 000 Btuh 3 kW and 100 00 Btuh 30 kW 36 inches 91 cm for appliances 100 00 Btuh 30 kW 4 feet 1 2 m below or to side of opening 1 foot 300 mm above opening C Clearance to permanently closed window D V...

Страница 18: ...ence in installation and service Location of Outdoor Terminations Horizontal Venting Vent and combustion air intake terminations must be as shown in Figures13 and 14 Vent termination clearances shall...

Страница 19: ...e by closely fitting standard couplings The face plates are retained on both sides of the wall by the couplings and the gasket is retained against the wall by the outer face plate Face plates must be...

Страница 20: ...GEOFCONDENSATE FROMFURNACE The condensate drainage system is internal to the furnace It is not recommended to connect additional traps to the exterior of the furnace Doing so will have adverse effects...

Страница 21: ...required as NORDYNE cannot be held responsible for water leakage which occurs due to loose hose connections or improperly sealed drain line pipes GAS SUPPLY AND PIPING This furnace is equipped for eit...

Страница 22: ...olutionmadespecificallyforthe detection of leaks to check all connec tions A fire or explosion may result causing property damage personal injury or loss of life IMPORTANT NOTE When pressure testing g...

Страница 23: ...LP Gas Sea Level Heating Value of 2 500 Btu hr Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 6000 to 7999 8000 to 10000 Manifold Pressure Setting in WC Full Input 10 8 5 10 9...

Страница 24: ...bles 6 and 7 WARNING This furnace was equipped at the fac tory for use with natural gas only A special kit supplied by the manufac turer is required to convert the fur nace to operate on LP propane ga...

Страница 25: ...e done in accor dancewiththecurrentCanadianElectricalCode CSA C22 1 Part 1 and or local codes If any of the original wire as supplied with the furnace must be replaced it must be replaced with wire ha...

Страница 26: ...ower will operate at high speed b Low fire only operation To set low fire only operation program the second stage temperature higher than the de sired room temperature refer to Ther mostat controller...

Страница 27: ...ing fixtures and convective load ing from warm air registers or electrical appli ances START UPANDADJUSTMENTS Prior to start up verify that 1 The line voltage power leads are securely connected that t...

Страница 28: ...rating plate At alti tudes above 2000 feet it must not exceed that on the rating plate less 4 for each 1000 feet Follow the procedure below to determine the firing rate 1 Shut off all other gas fired...

Страница 29: ...at the optimum airflow rate for the capacity Detailed operation is described in the cooling unit instal lation instructions and control manual Verifying and Adjusting TemperatureRise Verify that the...

Страница 30: ...mit switch makesurethattheblowerdoorisinplaceandthat there is power to the furnace Completely block the return airflow to the furnace by installing a close off plate in place of or upstream of the fil...

Страница 31: ...WHITE WHITE GRAY BLACK WHITE GREEN BLACK BLACK RED BLACK YELLOW ORANGE WHITE GREEN GREEN GREEN GREEN BLACK RED RED PLUG CONNECTOR BLACK BROWN BROWN BLACK C W2 RH R W1 H 0 Y2 Y1 G L V A B GD OD ID GD T...

Страница 32: ...is recommended that the furnace be checked yearly At a minimum this check should include the following items WARNING Toavoidelectricshock personalinjury ordeath disconnecttheelectricpower before perfo...

Страница 33: ...9 BlowerDoor Switch 10 VentSafetySwitch 11 LowVoltage Transformer 12 Supply Air Limit Switch 3 4 12 18 14 7 9 11 23 5 6 22 10 16 13 15 21 8 17 20 2 1 13 CirculatingAir BlowerAssembly 14 InducedDraft...

Страница 34: ...for the heating cool ing and fan modes are described below Refer to the field and furnace wiring diagrams Figures 22 and 25 Heating Mode 1 On a call for heat the thermostat sends signal to the interfa...

Страница 35: ...n blower stages to lower speed Low fire is satisfied the low fire will be de energized 10 The inducer is de energized after a 30 second postpurge 11 The circulating air blower remains on for 120 secon...

Страница 36: ...d ______ Gas Line Pressure ____________________ in water column with furnace operating Manifold Pressure ____________________ in water column with furnace operating Is there adequate fresh air supply...

Отзывы: