background image

7

HEAT PUMP INSTALLATION

General Information

The T5BP series heat pump is designed only for outdoor 
rooftop or ground level installations. This unit has been 
tested for capacity and effi ciency in accordance with 
A.R.I. Standards and will provide many years of safe 
and dependable comfort, providing it is properly installed 
and maintained. Abuse, improper use, and/or improper 
maintenance can shorten the life of the appliance and 
create unsafe hazards.

To achieve optimum performance and minimize equipment 
failure, it is recommended that periodic maintenance be 
performed on this unit. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools.

Before You Install the Heat Pump

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 
It is recommended that the area to be conditioned be 
completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. The system must be wired 
and provided with circuit protection in accordance with 
local building codes. If there is any question concerning 
the power supply, contact the local power company.

  The indoor section (air handler, furnace, etc) should be 

installed before routing the refrigerant tubing. Refer to 
the indoor unit's installation instructions for installation 
details.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 
prior to installing the equipment at the job site. Verify 
coil fi ns are straight. If necessary, comb fi ns to remove 
fl attened or bent fi ns. Claims for damage (apparent or 
concealed) should be fi led immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

Locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Overhead obstructions, poorly ventilated areas, and 

areas subject to accumulation of debris should be 
avoided.

• Suffi cient clearance for unobstructed airfl ow through the 

outdoor coil must be maintained in order to achieve rated 
performance. See Figure 2 for minimum clearances to 
obstructions.

•  Consideration should be given to availability of electric 

power, service access, noise, and shade.

18"

18"

18"

18"

TOP OF UNIT

TO BE

UNOBSTRUCTED

Figure 2. Clearance Requirements

Rigging and Hoisting

 WARNING:

To avoid the risk of property damage, personal 
injury, or death, it is the rigger’s responsibility 
to ensure that whatever means are used to hoist 
the unit are safe and adequate:

• 

The lifting equipment must be adequate for the 
load. Refer to Table 3 (page 14) for unit weights.

• 

The unit must be lifted from the holes in the 
base rails using cables or chains.

• 

Spreader bars are required to protect the unit 
and ensure even loading.

• 

Keep the unit in an upright position at all times. 

• 

All panels must be securely in place during 
rigging and hoisting.

Rooftop

Rooftop installations must be located according to local 
building codes or ordinances and these requirements:
•  Units may be installed on Class A, B, or C roof covering 

material. The roof must be capable of handling the 
weight of the unit. For unit weights, see Table 3. 
Reinforce the roof if necessary.

•  Secure optional mounting pad or frame to roof using 

acceptable mechanical methods per local codes.

Packaging Removal

Locate and remove all screws securing the unit to the 
shipping skid. 

NOTE: 

To prevent damage to the tubing 

connections, carefully remove the carton and user’s 
manual from the equipment. Discard the shipping carton.

Содержание T5BP 090C

Страница 1: ...nate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes req...

Страница 2: ...2...

Страница 3: ...enance 13 Replacement Parts 13 Component Functions 14 Figures Tables 14 Figure 5 T5BP Heat Pump Dimensions 14 Table 3 Unit Dimensions Shipping Weights 14 Electrical Information 15 Table 4 Electrical S...

Страница 4: ...de to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Set the temperature selector to the desired temperature level The outdoor fan compressor and blower motor will all cycle on and off to...

Страница 5: ...al power to the unit is turned on WARRANTY INFORMATION A warranty certificate with full details is included with the heat pump Carefully review these responsibilities with your dealer or service compa...

Страница 6: ...refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified in...

Страница 7: ...econsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine th...

Страница 8: ...required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces A filter dryer is provided with the unit and must be installedintheliquidlineo...

Страница 9: ...sk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Label all wir...

Страница 10: ...mostats can be used withthisequipmentdependingonoptionalaccessories i e economizer installed with the unit Select a thermostatthatoperatesinconjunctionwiththeinstalled accessories A typical commercial...

Страница 11: ...ch from delay to no delay remove the pin from the delay pin location and move it to the no delay pin location Scroll compressors that have noise issues while going into or coming out of defrost should...

Страница 12: ...outdoor unit remains de energized 3 After approximately 5 minutes verify the compressor andfanenergizeandthetemperatureofthedischarge air is cooler than the room temperature System Cooling 1 Set the...

Страница 13: ...d in Step 1 is greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is corr...

Страница 14: ...low 6 Minimum Clearance FIGURES TABLES Model Number T5BP Unit Weights Lbs Height H Width W Depth D Shipping Height Without Packaging Shipping Weight All dimensions in inches 090C 390 424 44 1 4 37 1 2...

Страница 15: ...1 7 Fan Blade Diameter Pitch Blades 30 22 3 30 22 3 30 26 3 30 26 3 RPM CFM Max Total 850 7 200 850 7 200 850 8 000 850 8 000 PHYSICAL DATA REFRIGERANT SPECS Outdoor Coil Assembly 1 ea 1 ea 1 ea 1 ea...

Страница 16: ...r run time is accumulated Opening of DFT during defrost or interval period resets the interval to 0 5 Ground on location provided inside compressor terminal box CC Contactor Coil CCH Crankcase Heat DF...

Страница 17: ...ED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT SEE NOTE 1 SEE NOTE 2 SEE NOTE 4 SEE NOTE 5 SEE NOTE 3 G Y E R O B W...

Страница 18: ...or a variety of indoor return air conditions and are most influenced by the outdoor ambient temperature outdoor fan operation and the unit operating voltage Before using these charts make sure the uni...

Страница 19: ...efrigerant when above curve Add refrigerant when below curve Figure 8 Charging Chart for 7 5 Ton Units Figure 9 Charging Chart for 10 Ton Units Liquid Temperature F Liquid Pressure psig 175 200 225 25...

Страница 20: ...n the charge to the amount shown on the rating label However if an inspection with these verification charts does not line up with the values shown and the ambient temperature is above 50 F then a mor...

Страница 21: ...e psig T5BP 120 Heat Mode Verification Chart 80 ID Rtn 70 ID Rtn 60 ID Rtn 62 OD Amb 47 OD Amb 17 OD Amb Figure 10 Verification Chart for 7 1 2 ton units Liquid Temperature F Liquid Pressure psig T5BP...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...___________________________ UnitInstalledMinimumclearancesper Figure 2 page 7 YES NO INSTALLER NAME CITY _______________________ STATE ________________ ELECTRICAL SYSTEM Electrical connections tight Y...

Отзывы: