T5BP CHARGING CHARTS - COOLING ONLY

Application Notes on the Use of Charging Charts

• 

This equipment’s cooling system contains refrigerant under high pressure. Always use safe and 
environmentally sound methods when handling refrigerant handling or servicing the unit. Review the 
factory literature and safety warnings prior to servicing.

•  When repairing system leakages, always use a nitrogen (inert) gas to protect the refrigerant system and pressure 

check the repair before re-charging. Always replace the fi lter-dryers when performing any repair to the refrigeration 
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns 
and weigh in the refrigerant to the amount specifi ed on the unit rating label.

•  All T5BP-090/120 units are shipped from the factory with a 90 oz. holding charge refrigerant. Inspect the unit 

rating label to determine the units information prior to working on the system. DO NOT mix different refrigerants 
or charge the unit with a refrigerant not listed on the unit rating label.

•  Charging charts are valid for a variety of indoor, return air conditions and are most infl uenced by the outdoor 

ambient temperature, outdoor fan operation and the unit operating voltage. Before using these charts, make 
sure the unit is in a stable operating mode. As shown in the charging charts (Figures 8 or 9, page 19), the ideal 
system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of 
sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit effi ciency 
(EER) or rated Coeffi cient of Performance (COP) in heating mode.

•  To inspect a systems operation, using quality instruments, match the measured liquid temperature to the units 

chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.

•  For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase 

balance and the refrigeration system for leaks.

•  Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more 

signifi cant deviation than the amount stated above.

• 

DO NOT

 use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient 

kit instructions for more information. (If applicable)

Содержание T5BP 090C

Страница 1: ...nate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes req...

Страница 2: ...2...

Страница 3: ...enance 13 Replacement Parts 13 Component Functions 14 Figures Tables 14 Figure 5 T5BP Heat Pump Dimensions 14 Table 3 Unit Dimensions Shipping Weights 14 Electrical Information 15 Table 4 Electrical S...

Страница 4: ...de to COOL or AUTO and change the fan mode to AUTO See Figure 1 2 Set the temperature selector to the desired temperature level The outdoor fan compressor and blower motor will all cycle on and off to...

Страница 5: ...al power to the unit is turned on WARRANTY INFORMATION A warranty certificate with full details is included with the heat pump Carefully review these responsibilities with your dealer or service compa...

Страница 6: ...refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified in...

Страница 7: ...econsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the job site to determine th...

Страница 8: ...required a copper tubing bender is recommended Avoid sharp bends and contact of the refrigerant lines with metal surfaces A filter dryer is provided with the unit and must be installedintheliquidlineo...

Страница 9: ...sk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Label all wir...

Страница 10: ...mostats can be used withthisequipmentdependingonoptionalaccessories i e economizer installed with the unit Select a thermostatthatoperatesinconjunctionwiththeinstalled accessories A typical commercial...

Страница 11: ...ch from delay to no delay remove the pin from the delay pin location and move it to the no delay pin location Scroll compressors that have noise issues while going into or coming out of defrost should...

Страница 12: ...outdoor unit remains de energized 3 After approximately 5 minutes verify the compressor andfanenergizeandthetemperatureofthedischarge air is cooler than the room temperature System Cooling 1 Set the...

Страница 13: ...d in Step 1 is greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is corr...

Страница 14: ...low 6 Minimum Clearance FIGURES TABLES Model Number T5BP Unit Weights Lbs Height H Width W Depth D Shipping Height Without Packaging Shipping Weight All dimensions in inches 090C 390 424 44 1 4 37 1 2...

Страница 15: ...1 7 Fan Blade Diameter Pitch Blades 30 22 3 30 22 3 30 26 3 30 26 3 RPM CFM Max Total 850 7 200 850 7 200 850 8 000 850 8 000 PHYSICAL DATA REFRIGERANT SPECS Outdoor Coil Assembly 1 ea 1 ea 1 ea 1 ea...

Страница 16: ...r run time is accumulated Opening of DFT during defrost or interval period resets the interval to 0 5 Ground on location provided inside compressor terminal box CC Contactor Coil CCH Crankcase Heat DF...

Страница 17: ...ED RED WHITE BLUE VIO 14 GRN 18 GRN 18 RED 12 GRY 12 BLK 12 BLU 12 BLK 12 BLACK BLACK GREEN BROWN SINGLE STAGE HEAT PUMP THERMOSTAT SEE NOTE 1 SEE NOTE 2 SEE NOTE 4 SEE NOTE 5 SEE NOTE 3 G Y E R O B W...

Страница 18: ...or a variety of indoor return air conditions and are most influenced by the outdoor ambient temperature outdoor fan operation and the unit operating voltage Before using these charts make sure the uni...

Страница 19: ...efrigerant when above curve Add refrigerant when below curve Figure 8 Charging Chart for 7 5 Ton Units Figure 9 Charging Chart for 10 Ton Units Liquid Temperature F Liquid Pressure psig 175 200 225 25...

Страница 20: ...n the charge to the amount shown on the rating label However if an inspection with these verification charts does not line up with the values shown and the ambient temperature is above 50 F then a mor...

Страница 21: ...e psig T5BP 120 Heat Mode Verification Chart 80 ID Rtn 70 ID Rtn 60 ID Rtn 62 OD Amb 47 OD Amb 17 OD Amb Figure 10 Verification Chart for 7 1 2 ton units Liquid Temperature F Liquid Pressure psig T5BP...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...___________________________ UnitInstalledMinimumclearancesper Figure 2 page 7 YES NO INSTALLER NAME CITY _______________________ STATE ________________ ELECTRICAL SYSTEM Electrical connections tight Y...

Отзывы: