Nordyne P6SD Series /installation Скачать руководство пользователя страница 8

8

Rooftop

Rooftop installations must be located according to local 
building codes or ordinances and these requirements:
•  The roof must be capable of handling the weight of the 

unit. For unit weights, see Table 4 (page 14). Reinforce 
the roof if necessary.

•  The appropriate accessory roof curb (Figure 4) must 

be installed prior to unit installation. The roof curb 
must be square and level to ensure proper condensate 
drainage. 

Please follow all instructions provided 

with the kit

.

•  Secure roof curb or frame to roof using acceptable

mechanical methods per local codes. 

NOTE:

 

Make sure 

the two supports beneath the unit have been removed. 

Roof
Curb

Figure 4. Roof Top Installation

2”

Figure 3. Ground Level Installation

Removal of Internal Filter Rack (3 Phase Only)

1.  Remove the return air panel from the unit.
2.  Remove the height adjustment screw from the inside 

of the rack.

3.  Remove (1) screw securing the assembly to the 

coil located on the left leg of the rack. 

NOTE:

 The 

assembly can now be easily collapsed and removed 
from the unit. See Figure 5 for fi lter rack securing 
screw locations.

Installing Filters in the Filter Rack (3 Phase Only)

1.  Remove access panel screws from return air panel. 

(

Hint:

 Loosen the unit’s top panel screws near the 

top edge of the access panel. The access panel was 
designed to be captured underneath the top panel.)

2.  Slide the fi rst fi lter between both guide channels of 

fi lter rack and

 

allow the fi lter to drop easily into place.

3.  Verify the bottom of the fi lter is within the channels 

of the rack.

4.  Slide the 2nd fi lter between both guide channels of 

fi lter rack.

5.  Verify the bottom of the fi lter is within the channels 

of the rack.

6.  Replace access cover by sliding the top edge of panel 

under the lip of the unit’s Top Panel. Secure access 
panel by replacing the screws.

Removing Filters from Filter Rack (3 Phase Only)

1.  Remove access panel screws from return air panel. 

(

Hint:

 Loosen the unit’s top panel screws near the 

top edge of the access panel. The access panel was 
designed to be captured underneath the top panel.)

2.  Remove  upper  fi lter  by  gently  pulling  fi lter  through 

the access panel opening.

3.  Remove lower fi lter by lifting media to top of fi lter 

rack. Remove in the same manner as described in 
step 2.

4.  Install new fi lter in the fi lter rack as described in the 

previous section.

Condensate Drain

Condensate is removed from the unit through the 3/4” 
female pipe fi tting located on the front side of the unit. 
Install a 2 inch condensate trap in the drain line of the 

Securing

Screws

Figure 5. Internal Filter Rack Location

Horizontal to Downfl ow Conversion

The unit is shipped ready for horizontal duct connections. 
If down fl ow ducts are required, the unit must be converted 
following the steps below for the supply and return ducts.
1.  Locate the duct cap inside the duct openings and 

remove the screw holding it in place.

2  Lift the cap out of the unit. (

Hint: 

The cap can be 

pushed up from the bottom by reaching through the 
fork slot).

3.  Cover the horizontal duct opening with the horizontal 

duct cap. The insulation will be on the indoor side.

4.  Fasten the cover with screws to seal.

Содержание P6SD Series /installation

Страница 1: ...tions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experi...

Страница 2: ...2...

Страница 3: ...rves 16 Figure 12 Wiring Diagram PSC Motor Three Phase 208 230V 17 Figure 13 Wiring Diagram Fixed Torque Motor Three Phase 208 230V 18 Figure 14 Wiring Diagram PSC Motor Single Phase 208 230V 19 Figur...

Страница 4: ...arnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designateadegreeorlevelof seriousnessandshouldnot be ignored WARNING indicat...

Страница 5: ...refrigerant underhighpressure Installationorservicingshouldonly beperformedbyqualifiedtrainedpersonnelthoroughly familiar with this type equipment All electrical wiring must be completed in accordance...

Страница 6: ...lated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Acoustical Duct Work Certain installations m...

Страница 7: ...ter Size Requirements AIR CONDITIONER INSTALLATION Packaging Removal Remove the shipping carton and User s Manual from the equipment Take care not to damage the tubing connections when removing the ca...

Страница 8: ...the bottom of the filter is within the channels of the rack 4 Slide the 2nd filter between both guide channels of filter rack 5 Verify the bottom of the filter is within the channels of the rack 6 Rep...

Страница 9: ...08V operation remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V Internally mounted circuit breakers are available as field installed options These ci...

Страница 10: ...age imbalance by using the results from steps 2 3 in the following equation max voltage deviation from average voltage 100 x average voltage Voltage Imbalance 6 454 100 x 1 32 Example 1 M e a s u r e...

Страница 11: ...blue wire Motor leads are code Q in Figure 8 High speed Connect the black wire to terminal 3 on the relay Tie off the orange red and blue wires They are not connected for high speed Fixed Torque ECM...

Страница 12: ...and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to ON Refrigerant Charging WARNING Single Packaged Air Conditioners are shipped fully charged with...

Страница 13: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginningofeachheatingandcoolingseason Service as necessary Inspect and...

Страница 14: ...IZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Table 4 Center of Gravity Unit Shipping Weights Model Number P6SD Unit Weight Center of Gravity Height C in inches A B with base rails withou...

Страница 15: ...pplied for 1 Stage Cool 1 Stage Heat R Y1 Y2 C G 1 2 3 4 5 6 7 8 9 Gray Yellow Blue ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE Red Black Green FROM TRANSFORMER FROM CONTACTOR FROM BLOWER RELAY Optiona...

Страница 16: ...80 1260 1230 Tap T3 1740 1690 1650 1600 1360 1500 1460 1390 Tap T4 1960 1910 1840 1820 1540 1740 1700 1600 Tap T5 2090 2050 2010 1975 1780 1900 1850 1790 NOTES Airflow performance is with a dry coil D...

Страница 17: ...des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V la terre 5 For supply wire ampacities and overcurrent protection see unit rating plate 711011S 1 2 3 4 5 6 7 8 9 R C S 1...

Страница 18: ...0 V la terre 7110100 1109 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 711010M 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 R C S 1 5 2 6 3 4 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8...

Страница 19: ...NG LEGEND LOW VOLTAGE HIGH VOLTAGE L C M H 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 BLOWER PLUG BLOWER MOTOR 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6...

Страница 20: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 21: ...BLACK YELLOW BLACK BLUE BLACK WHITE RED YELLOW YELLOW BK BK BK WHITE WHITE NOTES FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 460 Volt z H 0 6 e s a h P e e r h T r e n o i t i d n o C r i A d e g a k...

Страница 22: ...RED RED RED RED ORANGE ORANGE ORANGE ORANGE BLACK BLACK BLACK BLACK BLACK BLACK BLUE RED BLACK BLUE BROWN YELLOW YELLOW BLACK BK BK HEATER PLUG z H 0 6 e s a h P e e r h T t l o V 0 6 4 NOTES 1 Discon...

Страница 23: ...5 130 135 Add refrigerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F 200 220 240 260 280 300 320 340 360 38...

Страница 24: ...TALLATION INSTRUCTIONS WITH THE HOMEOWNER COOLING CHARGING CHARTS 13 SEER A C CONTINUED 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 75 80 85 90 95 100 105 110 115 1...

Отзывы: