Nordyne P6SD Series /installation Скачать руководство пользователя страница 12

12

START UP & SYSTEM CHECK

Pre-Start Check List

  Verify the unit is level and allows condensate to drain.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/
control panels are in place.

  Verify that the duct work is sealed to prevent air leakage. 

  Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

    Verify that the low voltage wires are securely connected 

to the correct leads on the low voltage terminal strip.

  Verify that the outdoor fan turns freely.

  Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  Verify that the thermostat is wired correctly. The 

thermostat system mode should be set to OFF and 
the thermostat fan mode should be set to AUTO.

Start-Up Procedure

Close all electrical disconnects to energize the system.

Air Circulation
Leave the thermostat system mode on OFF, and set the 
fan mode to ON. Blower should run continuously. Check 
the air delivery at the supply registers and adjust register 
openings for balanced air distribution. Examine ductwork 
for leaks or obstruction if insuffi cient air is detected. Set 
the thermostat fan mode to AUTO. The blower should 
stop running.

 WARNING:

If the unit is equipped with a crankcase heater, 
allow 24 hours prior to continuing the start up 
procedures to allow for heating of the refrigerant 
compressor crankcase. Failure to comply may 
result in damage and could cause premature 
failure of the system. This warning should be 
followed at initial start up and any time the power 
has been removed for 12 hours or longer.

System Cooling
1.  Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostats 
setpoint below room temperature and verify the outdoor 
unit and indoor blower energize.

2. Feel the air being circulated by the indoor blower 

and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds 
occur, determine the source of the noise and correct 
as necessary.

3.  Allow the cooling system to operate for several minutes 

and then set the temperature selector above room 
temperature. Verify the fan and compressor cycle off 
with the thermostat. 

NOTE: 

The blower should also 

stop unless fan mode is set to ON.

Refrigerant Charging

 WARNING:

Single Packaged Air Conditioners are shipped 
fully charged with R-410A refrigerant and ready 
for installation. When a system is installed 
according to these instructions, no refrigerant 
charging is required. If repairs make it necessary 
for evacuation and charging, it should only be 
done by qualifi ed, trained personnel thoroughly 
familiar with this equipment. Some local codes 
require licensed installation/service personnel 
to service this type of equipment. Under no 
circumstances should the owner attempt to 
install and/or service this equipment. Failure to 
comply with this warning could result in property 
damage, personal injury, or death.

The system refrigerant charge can be checked and 
adjusted through the service ports provided at the front 
panel. Use only gauge lines which have a Schrader 
depression device present to actuate the valve.

NOTES:

•  To achieve rated capacity and effi ciency the compressor 

must be exposed to refrigerant for at least 24 hours 
prior to running and then must be run for a minimum 
of 12 hours.

•  The refrigerant charging charts (Figures 18 - 20, 

pages 23 & 24) are applicable to listed assemblies 
of equipment and at listed airfl ows for the indoor coil. 
Assemblies of indoor coils and outdoor units not listed 
are not recommended.

Charging an R-410A Unit in AC Mode at Outdoor 
Temperatures Above 65F.

1.  With the system operating at steady-state, measure 

the liquid refrigerant pressure in psig at the service 
valve.

2.  Measure the liquid refrigerant temperature in 

Fahrenheit at the service valve.

3.  For the temperature measured, determine the required 

liquid refrigerant pressure from the appropriate 
charging charts in Figures 18 - 20.

4.  If the pressure measured in step 1 is greater than 

the required liquid refrigerant pressure determined in 

System Heating
If the unit has been equipped with optional electric heater 
kits, set the thermostat's system mode to HEAT and the 
fan mode to AUTO. Verify the compressor and outdoor 
fan are not energized but that the blower and heaters are. 
Feel the air being circulated by the indoor blower and verify 
that it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.

Содержание P6SD Series /installation

Страница 1: ...tions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experi...

Страница 2: ...2...

Страница 3: ...rves 16 Figure 12 Wiring Diagram PSC Motor Three Phase 208 230V 17 Figure 13 Wiring Diagram Fixed Torque Motor Three Phase 208 230V 18 Figure 14 Wiring Diagram PSC Motor Single Phase 208 230V 19 Figur...

Страница 4: ...arnings and any other special notes highlighted in the manual Safety markings are used frequently throughout this manual to designateadegreeorlevelof seriousnessandshouldnot be ignored WARNING indicat...

Страница 5: ...refrigerant underhighpressure Installationorservicingshouldonly beperformedbyqualifiedtrainedpersonnelthoroughly familiar with this type equipment All electrical wiring must be completed in accordance...

Страница 6: ...lated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements Acoustical Duct Work Certain installations m...

Страница 7: ...ter Size Requirements AIR CONDITIONER INSTALLATION Packaging Removal Remove the shipping carton and User s Manual from the equipment Take care not to damage the tubing connections when removing the ca...

Страница 8: ...the bottom of the filter is within the channels of the rack 4 Slide the 2nd filter between both guide channels of filter rack 5 Verify the bottom of the filter is within the channels of the rack 6 Rep...

Страница 9: ...08V operation remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V Internally mounted circuit breakers are available as field installed options These ci...

Страница 10: ...age imbalance by using the results from steps 2 3 in the following equation max voltage deviation from average voltage 100 x average voltage Voltage Imbalance 6 454 100 x 1 32 Example 1 M e a s u r e...

Страница 11: ...blue wire Motor leads are code Q in Figure 8 High speed Connect the black wire to terminal 3 on the relay Tie off the orange red and blue wires They are not connected for high speed Fixed Torque ECM...

Страница 12: ...and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to ON Refrigerant Charging WARNING Single Packaged Air Conditioners are shipped fully charged with...

Страница 13: ...s necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginningofeachheatingandcoolingseason Service as necessary Inspect and...

Страница 14: ...IZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Table 4 Center of Gravity Unit Shipping Weights Model Number P6SD Unit Weight Center of Gravity Height C in inches A B with base rails withou...

Страница 15: ...pplied for 1 Stage Cool 1 Stage Heat R Y1 Y2 C G 1 2 3 4 5 6 7 8 9 Gray Yellow Blue ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE Red Black Green FROM TRANSFORMER FROM CONTACTOR FROM BLOWER RELAY Optiona...

Страница 16: ...80 1260 1230 Tap T3 1740 1690 1650 1600 1360 1500 1460 1390 Tap T4 1960 1910 1840 1820 1540 1740 1700 1600 Tap T5 2090 2050 2010 1975 1780 1900 1850 1790 NOTES Airflow performance is with a dry coil D...

Страница 17: ...des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V la terre 5 For supply wire ampacities and overcurrent protection see unit rating plate 711011S 1 2 3 4 5 6 7 8 9 R C S 1...

Страница 18: ...0 V la terre 7110100 1109 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 711010M 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 R C S 1 5 2 6 3 4 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 9 8...

Страница 19: ...NG LEGEND LOW VOLTAGE HIGH VOLTAGE L C M H 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 BLOWER PLUG BLOWER MOTOR 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6...

Страница 20: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 21: ...BLACK YELLOW BLACK BLUE BLACK WHITE RED YELLOW YELLOW BK BK BK WHITE WHITE NOTES FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 460 Volt z H 0 6 e s a h P e e r h T r e n o i t i d n o C r i A d e g a k...

Страница 22: ...RED RED RED RED ORANGE ORANGE ORANGE ORANGE BLACK BLACK BLACK BLACK BLACK BLACK BLUE RED BLACK BLUE BROWN YELLOW YELLOW BLACK BK BK HEATER PLUG z H 0 6 e s a h P e e r h T t l o V 0 6 4 NOTES 1 Discon...

Страница 23: ...5 130 135 Add refrigerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F 200 220 240 260 280 300 320 340 360 38...

Страница 24: ...TALLATION INSTRUCTIONS WITH THE HOMEOWNER COOLING CHARGING CHARTS 13 SEER A C CONTINUED 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 75 80 85 90 95 100 105 110 115 1...

Отзывы: