Nordyne MB7BM Series Скачать руководство пользователя страница 8

8

4. Place the horizontal drain pan on the opposite side of 

the coil. On units with 2 sets of knockouts, remove the 
other set of knockouts in the coil spacing plates and 
insert support rod.

5. Slide the coil and the horizontal drain pan assembly 

back into the unit. Re-attach the tube close off plate.

  note: For A-size cabinet applications, it may be 

preferrable to remove the blower assembly prior 
to installing the coil & drainpan. In this case follow 
instructions 1-4 as listed above but also remove the 
blower access door and blower assembly. The blower 
assembly is secured with two screws on either side 
near the front. With these removed the blower assembly 
can slide out of the front of the unit. Install the coil and 
drain pan as described in step 5 and then replace the 
blower assembly. Take care to ensure that the flanges 
on the sides of the blower assembly are captured by 
the pockets in the blower deck. It may be necessary 
to lift the blower assembly during insertion to allow the 
lower blower leg to clear the side of the drain pan. The 
blower will stop against the back of the blower deck. 
Replace the two screws and the blower access door 
and procede with steps 6-9.

6. Remove the plug from one of the threaded holes 

in the horizontal drain pan. Completely remove the 
webbing located in the threaded holes of the drain 
pan. iMPortant: If the webbing is not removed, the 
condensate will not drain properly and ceiling damage 
may occur.

7. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom 
of the unit to block bypass air.

8. Remove the corresponding drain line knockout from 

the coil access door to allow access to the horizontal 
drain.

9. Replace the door and attach the drain line.

Horizontal installation
MB7 air handlers are shipped from the factory ready 
for horizontal left applications and horizontal right 
applications. The blowers can be installed horizontally 
in an attic, basement, crawl space or alcove. They can 
also be suspended from a ceiling in a basement or utility 
room in either a right to left airflow or left to right airflow. 
A typical installation of the unit in a suspended horizontal 
application is shown in Figure 5.

When mating the blower and coil for horizontal left or 
right applications, reference the upflow instructions on 
page 6. Make sure to account for the coil orientation by 
configuring the coil drain pan assembly properly. Multi-
position procedures are also available in the cased coil 
Installation Instructions supplied with the unit.

noteS:

•  In  many  applications  when  joined  with  a  C6  cased 

coil, the shorter horizontal drain pan extension which 
is included with the MB7 must be used. This is to avoid 
any interference with the extension included with the 
C6 and the blower.

•  The 

air handler may or may not be shipped from the 

factory with all the parts required for horizontal left 
applications and horizontal right applications. If your 
unit does not have parts for a horizontal application, a 
kit may be available.

If suspending the air handler from the ceiling, assemble 
a support frame (Figure 5) using slotted iron channel and 
full threaded rod. Fasten the frame together with nuts, 
washers, and lockwashers. Secure the support frame 
to the rafters with lag bolts. The air handler can also be 
suspended using steel straps around each end of the 
unit. The straps should be attached to the air handler with 
sheet metal screws and to the rafters with bolts.

Horizontal Left Installations
1. Remove the coil access door.
2. Remove the plug from one of the threaded holes in the 

horizontal drain pan. Completely remove the webbing 
in the threaded holes of the horizontal drain pan. if the 
webbing is not removed, the condensate will not 
drain properly and ceiling damage may occur.

3. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom 
of the unit to block bypass air.

4. Remove the corresponding drain line knockout from 

the coil access door to allow access to the horizontal 
drain.

5. Replace the door and attach the drain line.

Horizontal Right Installations
1. Remove the coil access door. Unscrew the line-set tube 

close-off plate from the front left cabinet rail.

2. Slide the coil and drain pan assembly out of the unit.
3. Remove the sheet metal hairpin covers (if supplied) 

from the back of the coil and discard.

Figure 5. unit Horizontally Suspended

Threaded 

Rod

Lag
Bolt

Nuts (x2)

Washer 

and 

Lockwasher

Nuts (x2)

Содержание MB7BM Series

Страница 1: ...nt role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in ser...

Страница 2: ...ing 11 Turning the Blower Off 11 Blower Configurations 11 Selecting minimum Electric Heat Airflow 11 Determining Nominal System Capacity 11 3 speed Units 11 High Efficiency Units 12 Selecting Basic He...

Страница 3: ...ment Do not store any of the following on or in contact with the unit Rags brooms vacuum cleaners or other cleaning tools spray or aerosol cans soap powders bleaches waxes cleaning compounds plastics...

Страница 4: ...dbesetintopositionbeforerouting the refrigerant tubing Operation of an Air Handler During Construction CAUTION Failure to follow these instructions will void the factory warranty and may significantly...

Страница 5: ...tments must be constructed and installed in accordance with NFPA and SMACNA construction standards Consult with local codes for special requirements For best sound performance be sure to install all t...

Страница 6: ...nts air handler INSTALLATION The MB7 Series air handler is shipped ready for vertical upflow installation and is approved for attic basement alcove closetorcrawlspaceinstallationwithzeroclearance to c...

Страница 7: ...ne gasket tape to the top of the air handler NOTE The blowers flanged surface is now beneath the air handler and will connect with the supply air duct 4 Carefully place the cased coil on top of the mo...

Страница 8: ...ion of the unit in a suspended horizontal application is shown in Figure 5 When mating the blower and coil for horizontal left or right applications reference the upflow instructions on page 6 Make su...

Страница 9: ...gures 14 16 Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Aluminum suppl...

Страница 10: ...erkitforyour unit by referring to the list below or the units rating label A Size Cabinet 15Kw max B Size Cabinet 20Kw max C Size Cabinet 20Kw max 1 Connect the 2 wire plug of the air handler to the m...

Страница 11: ...Disconnect all electrical power to the unit and remove the upper door 2 Remove the black and red wires from the blower motor jumping terminal Discard the blower motor jumping terminal Startup Adjustme...

Страница 12: ...ch nominal system capacity When operating in the heat pump mode a higher basic airflow setting will increase the energy efficiency and capacitybutwillalsodecreasethesupplyairtemperature For maximum ca...

Страница 13: ...eate excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life It is recommended that the blower compartment be cleaned of dirt or lint that may ha...

Страница 14: ...mension B Dimension C A 12 3 4 24 3 4 14 1 4 B 12 3 4 24 3 4 17 1 2 C 18 1 4 27 1 2 21 B A 12 7 8 3 4 TYP 1 3 4 1 7 8 K O 3 1 4 1 1 4 C 22 1 1 7 8 3 1 2 5 1 2 2 5 8 1 1 8 K O TYP 1 1 4 2 7 8 TOP VIEW...

Страница 15: ...ount Kit Blower Motor Blower Wheel Blower Housing Transformer Control Board Coil Assembly Outlet Heater Box Lower Front Bracket Blower Door Motor Control Board Rear Bracket Front Joining Bracket Figur...

Страница 16: ...0 845 780 705 610 530 Corrected ESP1 0 08 0 19 0 31 0 42 0 54 0 65 0 76 Med 1335 1290 1235 1175 1100 1015 925 805 Corrected ESP1 0 10 0 22 0 34 0 46 0 59 0 71 High 1470 1425 1360 1300 1225 1135 1050 9...

Страница 17: ...685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0 1 1330 12...

Страница 18: ...0 1 0 650 0 0 1 1 2 TON 1300 0 0 1 1 4 TON 700 0 1 0 0 1350 0 1 0 0 750 0 1 0 1 1400 0 1 0 1 800 0 1 1 0 2 5 TON 1450 0 1 1 0 850 0 1 1 1 1500 0 1 1 1 875 1 0 0 0 1550 1 0 0 0 950 1 0 0 1 1600 1 0 0 1...

Страница 19: ...0 1 0 0 700 1 15 1300 1 0 1 0 1 750 1 20 1500 1 0 1 1 0 800 1 25 N A 1 0 1 1 1 850 1 30 N A 1 1 0 0 0 875 1 1 0 0 1 950 1 1 0 1 0 1050 1 1 0 1 1 1150 1 1 1 0 0 1250 1 1 1 0 1 1350 1 1 1 1 0 1400 1 1 1...

Страница 20: ...1 7 68 1 50 25 70 020H XX 53 1 103 1 60 110 46 5 43 3 89 8 50 45 90 C 2000CFM None 5 5 15 15 5 5 15 15 005H XX 30 30 35 35 26 7 26 7 30 30 008H XX 44 6 44 6 45 45 39 3 39 3 40 40 010H XX 55 55 60 60 4...

Страница 21: ...Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with Variable Speed Air Handler Typical 2 Stage Heat Pump with Variable Speed Air Handler Y2 Y2 Y2 Y2 OUT W E R Air Conditioner Air Handler Air C...

Страница 22: ...age Control Board MB7BM Models Figure 11 Two Stage Control Board MB7EM VM Models LED 1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2...

Страница 23: ...W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTPUTS STATUS LIGHTS 2 3 4 5 6 7 8 OFF ON A B GREEN RED STATUS NOT USED TEST PORT BLOWER MOTOR R C Y1 TWIN DEHUM...

Страница 24: ...PLUG HOUSING WHEN HEATER KIT NOT INSTALLED BLACK RED WHITE BROWN BROWN BLACK WHITE RED GRAY YELLOW WHITE GREEN GRAY RED NOTES 1 The blower motor speed tap connection may not be as shown See the Insta...

Страница 25: ...2 3 4 5 6 9 PIN HOUSING 9 PIN PLUG 6 PIN PLUG HARNESS BLACK WHITE GRAY RED BLACK RED WHITE BLACK MOTOR 6 PIN PLUG HARNESS WHITE BLACK BLUE GREEN YELLOW ORANGE RED BROWN BLUE GREEN ORANGE RED BROWN YE...

Страница 26: ...R BLACK WHITE 6 PIN PLUG 6 PIN PLUG BLACK WHITE BLACK WHITE GRAY RED BLACK HARNESS HARNESS GREEN BROWN RED ORANGE YELLOW GREEN BLUE BROWN RED ORANGE YELLOW GREEN BLUE RED CUT WIRES TO REMOVE PLUG HOU...

Страница 27: ...delay W Y AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Страница 28: ...ly Blower off after 15 second delay W1 W2 EHEAT On 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat o...

Страница 29: ...off instantly Heat blower turns off after 40 second delay W1 W2 Y Y2 AUX HEAT On 5 KW Stage 1 Heat on instantly Cool blower on after 3 second delay 10 KW Stage 1 Heat on instantly Cool blower on afte...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...Replaces 7091750 ATTENTION INSTALLERS It is your responsibility to know this product better than your customer This includes being able to install the product according to strict safety guidelines and...

Отзывы: