11. INSTALLATION

Required floor, ceiling, and roof cut-out openings must be
carefully located to avoid misalignment of the furnace and
Roof Jack (see Figures 12 & 13). Installation procedures are
suggested for typical furnace installations and need not be
followed in the exact listed sequence.

CUT OUT FLOOR OPENING & FUEL LINE HOLE

a. Determine center of closet or alcove (Figure 13).
b. Locate center of the floor opening, measured 10" from

the rear wall, and mark cut-out measuring
approximately 14-1/2" by 14-1/2" (± 1”) for model duct
connector used (refer to Figures 10 & 11).

c. Locate center of fuel line hole, measured 23-1/4" from

the rear wall and 6-5/8" to the left of center of the floor
cut-out (See Figure 12) or 5-1/4" to the left of center of
the floor cut-out, or for entry through right-side of
furnace measured 9" to the right of center of the floor
cut-out.

d. Cut out floor opening and one fuel line hole.

CUT OUT CEILING AND ROOF OPENINGS

a. Locate center of Roof Jack opening, measured

13 1/2" from the rear wall of closet or alcove along the
center line of furnace and floor opening. (See Figure 13)

b. Cut ceiling and roof holes as follows:

Ceiling Hole = 8-3/4" (222 mm) diameter
Roof Hole = 9-3/8" (238 mm) diameter

c. DO NOT ALLOW DEBRIS TO FALL INTO THE

FURNACE. THIS COULD CAUSE UNSAFE
OPERATION AND VOIDS THE FURNACE
WARRANTY. Use the top cap that comes with the
furnace packaging (or alternate protector) to prevent
debris from falling into the furnace before the final roof
jack connection is made.

IMPORTANT:

Refer to the installation instructions provided
with optional air conditioning packages when
installing furnaces with optional cooling coil
cabinet or with optional C***-series indoor coils.

!

X

SEE 

TABLE 7

REDUCER

FELT-SEAL

SPACERS

C

OPENING TO DUCT

WITH PLATE (C) REMOVED
OPENING BECOMES
13-1/4” x 13-1/4”

13 1/4"

10 1/4"

19”  

19"

T

Top View

of Duct

Connector

x

SUPPLY AIR DUCT

FLOOR CAVITY
(depth equal to "X" in Figure 11 and Table 7)

If "X"

  (Floor cavity) is:

7/8" (22mm)

901987

2" (51mm)

901988

4 1/4" (108mm)

901989

6 1/4" (159mm)

901990

8 1/4" (210mm)

901991

10 1/4" (260mm)

901992

12 1/4" (311mm)

901993

Use Duct 

Connector Model

IF PITCH IS:

FLASHING NO.

"X" FACTOR IS:

2" in 12"

901942

2 1/8" (54MM)

(51mm/304mm)

2 1/2" in 12"

901941

2 1/2" (64MM)

(64mm/304mm)

3" in 12"

901940

2 7/8" (73MM)

(76mm/304mm)

3 1/2" in 12"

901939

3 1/4" (83MM)

(89mm/304mm)

4" in 12"

901938

3 5/8" (92MM)

(102mm/304mm)

5" in 12"

Use 901941

2 1/2" (64MM)

(127mm/304mm)

 with flue having 

slant flashing.

 See Fig. 8

Содержание M1GB 056

Страница 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Iftheinformationinthismanualisnotfollowedexactly afireorexplosionmayresu...

Страница 2: ...E GUIDE 18 18 MAINTENANCE 22 19 OPTIONAL ACCESSORIES 23 20 WIRING DIAGRAMS 24 26 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 27 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Страница 3: ...nstallation Blower Assemblies A C Capacity Blower Wheel Motor Hp Ton 903412 10 x 8 1 3 2 2 3 903413 11 x 8 1 2 2 2 3 4 903414 10 x 8 3 4 2 2 3 4 5 Part No Blower Motor Assembly Furnace Input Output Or...

Страница 4: ...ion furnace adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which cannot be included in warranty payments are 1 Converting the furnace to u...

Страница 5: ...followingconditionstohave acceptablereturnairsystemsfor closet installed forced air heating appliances a Regardless of the location the return air opening into the closet shall not be less than specif...

Страница 6: ...ertiduct program to determine proper duct size for A C 8 AIR DISTRIBUTION SYSTEMS For proper air distribution the supply duct system must be designed so that the static pressure measured external to t...

Страница 7: ...2 ROOF SLOPE 2 SLANT DECK 12 1 2 ROOF JACK WITH 2 FLASHING 12 SLANT 1 2 S S AW T 20 32 2 AW ALL WEATHER FLASHING PITCH 12 RISE 0 FLAT 2 2 5 12 4 4 12 MIN ADJ LENGTH F S FLAT FLASHING SLANT FLASHING TY...

Страница 8: ...flooropening SeeFigure13 b Cut ceiling and roof holes as follows Ceiling Hole 8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE THIS COULD CAUSE UNSA...

Страница 9: ...8 CUT DUCT OPENING a Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct b Center duct connector and push back against rear edge of floor opening c Ma...

Страница 10: ...r opening c Slide onto mounting plate Bottom rear slots on furnace should engage with mounting plate tabs d Secure front with one 1 fastener at each corner See Figure 19 or 20 NOTE Additional fastener...

Страница 11: ...ion door Gas or Oil To furnace wall thermostat MANUFACTURED HOME SITE a Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 24 b Place upper Roof Jack crown on to the...

Страница 12: ...ircuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems Once the furnace is installed check the thermostat anticipator against the nominal setting of 0 4 1 Connect t...

Страница 13: ...ttom of the fuel tank to the fuel pump must not exceed ten feet Keep the tank filled especially in the summer to reduce the accumulation of condensation CAUTION The furnace must be converted by a qual...

Страница 14: ...n the oil supply line and all plugs nuts and fittingsonthepumpmustbeairtight Thisincludesthenutthat covers the pressure adjustment It is important that the hook up be done carefully and with a good fl...

Страница 15: ...old the control lever for about one 1 minute after the pilot is lit Release the lever and it will spring back to the PILOT position Pilot should remain lit If it goes out repeat steps d through h abov...

Страница 16: ...appliancebeforeservicing unit c Set the ON OFF switch to OFF d Honeywell pushinthegascontrolknobandturnclockwise to OFF Robertshaw push the gas control lever to OFF e Replace the furnace door SEQUENCE...

Страница 17: ...ust be reset e When call for heat is satisfied the thermostat contacts open and the burner will stop Gas Gun Models M1 gas gun furnaces may be converted to oil gun in the field by using the proper con...

Страница 18: ...hrough the observation door The same pilot orifice is used with both natural and L P gas b After this sequence the control module tests to see if flame is sensed If it has the furnace continues to hea...

Страница 19: ...wn in Figure 32 Do not permit any electrodes to be grounded to any surface GAS CONVERSION This gas fired heating appliance was shipped from the factory for use with natural gas However the appliance c...

Страница 20: ...o put the furnace into operation NOTE Thepilotflameisadjustablebyturningtheadjustment screw located on the gas valve with a small screwdriver See Figure 29 TROUBLESHOOTING STANDING PILOT MODELS Main B...

Страница 21: ...s Closed a Check for polarity b Check ground c Check flue d Check combustion air e Check gas pressure f Check orifice g Check the position of ignitor a normal reading should be 40 75 ohms 24 Volts Sup...

Страница 22: ...filters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During extremely col...

Страница 23: ...thasbeendesignedspecifically for manufactured housing applications and can best handle your home comfort needs Listed and ARI Certified all models are protected by the NORDYNE Air Conditioner Limited...

Страница 24: ...ied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent BLACK BLACK SUPPLIED BY INSTALLER BLUE WHITE MANUAL RESET VENT SWITCH 1 5 2 3 6 4 GAS VALVE FAN SWITCH HI LI...

Страница 25: ...ce orange wire with red wire low speed NOTE To run at same speed in both heating and cooling mode remove wire from either terminal 4 or 6 on the relay then attach jumper to terminals 4 and 6 6 5 4 3 2...

Страница 26: ...original wires as supplied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent SUPPLIED BY INSTALLER C W G R COM BLUE 1 5 2 A C BLOWER RELAY 3 6 4 FAN SWITCH HI LIM...

Страница 27: ...2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28 28 29 M1M 077 ORIFICE SIZE LP 40 41 42 42 42 43 43 44 44 45 OUTPUT MBTUH 61 7 56 9 54 6 52 4 50 3 48 3 46 4 44 5 42 7 41 0...

Страница 28: ...MO 707776C Replaces 707776B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 04 99 INSTALLER Please leave these installation instruc...

Отзывы: