Nordyne M1GB 056 Скачать руководство пользователя страница 5

5

5. UNIT LOCATION

The furnace shall be appropriately located to the supply and
return air distribution system. (See “AIR DISTRIBUTION”,
Page 7) Sides and back of the furnace may be enclosed by
wall framing. (See “Minimum Clearances,” Table 4, and
Figures 2 through 5.)

The furnace installation is only intended for free air return
through the furnace door louvers. DO NOT connect a ducted
return air system directly to the furnace. Improper installation
may create a hazard and damage equipment, as well as void
all warranties.

Furnace may be installed on combustible flooring when using
NORDYNE Duct Connectors (see Table 7 and Figures 9-16).

6. MINIMUM CLEARANCES

This heating appliance must be installed with clearances not
less than the minimums shown in Table 4. This heating
appliance must be installed with ample clearance for easy
access to the air filter, blower assembly, burner assembly,
controls, and vent connections.

a. Alcove installations (see Figure 2): minimum 18"

clearance at front of furnace shall be provided for future
servicing. A removable access panel should be installed
between top of the furnace door frame and the ceiling.

b. Closet installations must use a louvered door having a

minimum free area of 235 sq. in. when located 6" from
furnace (See Figure 3). For special clearance between
1" and 6", requirements are a louvered door with a
minimum of 250 sq. in. free area, with the openings in
the closet door directly in line with the louvered openings
in the furnace door . A fully louvered closet door may
be used  (See Figure 4).

Figure 1. Overall Dimensions

“A”- 56"

23 3/4"

“B”- 76"

19 3/4"

“A” Model- 
w/o Coil Cabinet

“B” Model- 
w/Coil Cabinet

Table 4. Minimum Clearances

7. RETURN AIR PROVISIONS

U.S.A. home manufacturers shall comply with all of the
following conditions to have  acceptable return air systems for
closet installed forced air heating appliances:

a. Regardless of the location, the return air opening into

the closet shall not be less than specified in the
appliance’s listing.

b. Means shall be provided to prevent inadvertent closure

by a flat object placed over the return air opening
when it is located in the floor of the closet (versus the
vertical front or side wall).

c. The cross-sectional area of the return duct system

leading into the closet, when located in the floor or
ceiling shall not be less than 235 square inches (or
390 square inches for 5 ton ready M1 Furnaces).

d. The total free area of openings in the floor or ceiling

registers serving the return air duct system must be
at least 352 sq. in. At least one register should be
located where it is not likely to be covered by carpeting,
boxes and other objects.

e. Materials located in the return duct system must have

a flame spread classification of 200 or less. This
includes a closet door if the furnace is in a closet.

f.

Noncombustible pans having 1" upturned flanges are
located beneath openings in a floor duct system.

g. Wiring materials located in the return duct system

shall conform to Articles 300-22 of the National
Electrical Code (ANSI C1/NFPA-70).

h. Gas piping is not run in or through the return duct

system.

i.

Test the negative pressure in the closet with the air-
circulating fan operating at high speed and the closet
closed. The negative pressure is to be no more
negative than minus 0.05 inch water column.

CAUTION:

HAZARD OF ASPHYXIATION: Negative
pressure inside the closet, with closet door
closed and the furnace blower operating on
high speed, shall be no more negative than
minus 0.05 inch water column.

!

ALL MODELS

CLOSET

ALCOVE

Front

6"

18"

Back

0"

0"

Sides

0"

0"

Roof Jack

0"

0"

Top

6"

6"

Top and Sides of Duct

0"

0"

Bottom of Duct

B Cabinet

0"

0"

A Cabinet (w/ coil box)

0"

0"

A Cabinet (w/o coil box)

1/4"

1/4"

Содержание M1GB 056

Страница 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Iftheinformationinthismanualisnotfollowedexactly afireorexplosionmayresu...

Страница 2: ...E GUIDE 18 18 MAINTENANCE 22 19 OPTIONAL ACCESSORIES 23 20 WIRING DIAGRAMS 24 26 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 27 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Страница 3: ...nstallation Blower Assemblies A C Capacity Blower Wheel Motor Hp Ton 903412 10 x 8 1 3 2 2 3 903413 11 x 8 1 2 2 2 3 4 903414 10 x 8 3 4 2 2 3 4 5 Part No Blower Motor Assembly Furnace Input Output Or...

Страница 4: ...ion furnace adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which cannot be included in warranty payments are 1 Converting the furnace to u...

Страница 5: ...followingconditionstohave acceptablereturnairsystemsfor closet installed forced air heating appliances a Regardless of the location the return air opening into the closet shall not be less than specif...

Страница 6: ...ertiduct program to determine proper duct size for A C 8 AIR DISTRIBUTION SYSTEMS For proper air distribution the supply duct system must be designed so that the static pressure measured external to t...

Страница 7: ...2 ROOF SLOPE 2 SLANT DECK 12 1 2 ROOF JACK WITH 2 FLASHING 12 SLANT 1 2 S S AW T 20 32 2 AW ALL WEATHER FLASHING PITCH 12 RISE 0 FLAT 2 2 5 12 4 4 12 MIN ADJ LENGTH F S FLAT FLASHING SLANT FLASHING TY...

Страница 8: ...flooropening SeeFigure13 b Cut ceiling and roof holes as follows Ceiling Hole 8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE THIS COULD CAUSE UNSA...

Страница 9: ...8 CUT DUCT OPENING a Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct b Center duct connector and push back against rear edge of floor opening c Ma...

Страница 10: ...r opening c Slide onto mounting plate Bottom rear slots on furnace should engage with mounting plate tabs d Secure front with one 1 fastener at each corner See Figure 19 or 20 NOTE Additional fastener...

Страница 11: ...ion door Gas or Oil To furnace wall thermostat MANUFACTURED HOME SITE a Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 24 b Place upper Roof Jack crown on to the...

Страница 12: ...ircuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems Once the furnace is installed check the thermostat anticipator against the nominal setting of 0 4 1 Connect t...

Страница 13: ...ttom of the fuel tank to the fuel pump must not exceed ten feet Keep the tank filled especially in the summer to reduce the accumulation of condensation CAUTION The furnace must be converted by a qual...

Страница 14: ...n the oil supply line and all plugs nuts and fittingsonthepumpmustbeairtight Thisincludesthenutthat covers the pressure adjustment It is important that the hook up be done carefully and with a good fl...

Страница 15: ...old the control lever for about one 1 minute after the pilot is lit Release the lever and it will spring back to the PILOT position Pilot should remain lit If it goes out repeat steps d through h abov...

Страница 16: ...appliancebeforeservicing unit c Set the ON OFF switch to OFF d Honeywell pushinthegascontrolknobandturnclockwise to OFF Robertshaw push the gas control lever to OFF e Replace the furnace door SEQUENCE...

Страница 17: ...ust be reset e When call for heat is satisfied the thermostat contacts open and the burner will stop Gas Gun Models M1 gas gun furnaces may be converted to oil gun in the field by using the proper con...

Страница 18: ...hrough the observation door The same pilot orifice is used with both natural and L P gas b After this sequence the control module tests to see if flame is sensed If it has the furnace continues to hea...

Страница 19: ...wn in Figure 32 Do not permit any electrodes to be grounded to any surface GAS CONVERSION This gas fired heating appliance was shipped from the factory for use with natural gas However the appliance c...

Страница 20: ...o put the furnace into operation NOTE Thepilotflameisadjustablebyturningtheadjustment screw located on the gas valve with a small screwdriver See Figure 29 TROUBLESHOOTING STANDING PILOT MODELS Main B...

Страница 21: ...s Closed a Check for polarity b Check ground c Check flue d Check combustion air e Check gas pressure f Check orifice g Check the position of ignitor a normal reading should be 40 75 ohms 24 Volts Sup...

Страница 22: ...filters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During extremely col...

Страница 23: ...thasbeendesignedspecifically for manufactured housing applications and can best handle your home comfort needs Listed and ARI Certified all models are protected by the NORDYNE Air Conditioner Limited...

Страница 24: ...ied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent BLACK BLACK SUPPLIED BY INSTALLER BLUE WHITE MANUAL RESET VENT SWITCH 1 5 2 3 6 4 GAS VALVE FAN SWITCH HI LI...

Страница 25: ...ce orange wire with red wire low speed NOTE To run at same speed in both heating and cooling mode remove wire from either terminal 4 or 6 on the relay then attach jumper to terminals 4 and 6 6 5 4 3 2...

Страница 26: ...original wires as supplied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent SUPPLIED BY INSTALLER C W G R COM BLUE 1 5 2 A C BLOWER RELAY 3 6 4 FAN SWITCH HI LIM...

Страница 27: ...2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28 28 29 M1M 077 ORIFICE SIZE LP 40 41 42 42 42 43 43 44 44 45 OUTPUT MBTUH 61 7 56 9 54 6 52 4 50 3 48 3 46 4 44 5 42 7 41 0...

Страница 28: ...MO 707776C Replaces 707776B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 04 99 INSTALLER Please leave these installation instruc...

Отзывы: