7

Damper Installation
An automatic shut-off damper is available (see
replacement parts list).  An automated shut off
damper is required when the home is air con-
ditioned by a self-contained unit.  This damper
is designed to fit in the feeder duct cavity,
directly under the furnace.  A damper is required
to prevent chilled air from flowing over the
furnace heat exchanger.  For proper installa-
tion, refer to the instructions provided with the
damper.

Installation of Furnace onto the MA-200
Base
Lift the furnace over the base so that the flange
at the back comes to rest on the inside rails of
the base.

Raise the front of the furnace to clear the gasket
on the bottom of the furnace and slide the back
until the rear flange drops into the channel at the
rear of the base.  Be careful not to damage the
combustion air adapter, if present,  while posi-
tioning the unit.

Be sure that the furnace is all the way back so
as to engage the tabs on the rear flange on the
base.

Open the access door.  Fasten the front of the
furnace and the base to the floor with #8 x 1/2"
long sheet metal screws.

Using the provided hose clamp, secure the
flexible combustion air tubing from the burner to
the combustion air adapter.

Installation of Furnace onto the MA-100
Base
Tilt the furnace forward and carefully work the
furnace back over the MA-100 Universal base.

Lift the furnace as necessary when positioning
the unit over the base assembly to prevent any
damage to the feeder duct assembly and com-
bustion air adapter, if present.

Be sure the furnace is positioned all the way to
the back of the base assembly.

Open the furnace door and fasten the furnace
to the base using #8 x 1/2" long sheet metal
screws.

Install the feeder duct by bending the tabs inside
the heat duct and using the metal tape to insure
an airtight connection.

Set the bottom base panel over the feeder duct.
Slit the corners of the feeder duct down to the
top of the base.  While the top of the distribution
duct is pulled up with one hand, bend down each
side of the feeder duct tightly to the base with the
other hand.  Trim the metal to allow one inch
flange over the top of the base and seal that
flange with the metal tape.

Secure the top panel to the floor with two (2)
screws through the front flange.

If a “V” or “U”-box crossover system is to be
used, see the instructions provided with the
crossover system.

Combustion Air Duct/Pipe Installation
The CMF furnace must draw the combustion air
from outside, except for special installations
(See Table 1).  This can be accomplished either
by using the 2”X7” rectangular combustion air
duct provided in the MA series base kits or using
the direct vent kit.

When the rectangular combustion air duct is to
be used, install the combustion air duct through
the selected knockout in the base.  For direct
vent  applications, the rear knock-out in the
furnace base cannot be used.  After the
combustion air duct has been positioned, install
the combustion air adapter.  This adapter will
transition the 2”X7” opening of the combustion
air duct to the 2” diameter of the burner flexible
tubing.  This adapter is included in the MA series
base kits.  For retrofit applications in which the
MA series base is already installed, the
combustion air adapter can be ordered as a kit.
Refer to the Replacement Parts List for more
details on ordering this kit.
Secure the adapter with either wood or metal
fasteners (field provided), depending upon the
particular installation.  Ensure that the gasket
for the adapter is positioned properly before
installing the adapter. Attach the flexible hose
from the burner to the combustion air adapter
using the provided metal hose clamp.

When the direct vent  kit is used, follow the
instructions provided with the kit.  Note: The
direct vent kit should be installed before
positioning the furnace on the base.

Содержание CMF 100-PG

Страница 1: ...ty direct vent furnaces used for manufactured housing rec reational vehicle and residential applications These furnaces are offered in either power gas designated by PG or power oil designated by PO models The power gas models are de signed for operation with either natural or pro pane LP gas The CMF series is convertible from power oil to power gas and vice versa Furthermore the firing rate of th...

Страница 2: ...stallationofOil BurningEquipment ANSI NFPA70 National Electrical Code and NFPA 211 Chimneys Fireplaces Vents and Solid Fuel Burning Appliances The National Fuel Gas Code is available by writing American National Standards Institute Inc 1430 Broadway New York NY 10018 NFPA publications are available by writing National Fire Protection Association Batterymarch Park Quincy ME 02269 Combustion Air and...

Страница 3: ...enting Requirements Manufactured Housing Installations For all manufactured housing applications the CMF furnace must be vented using the SRJ series roofjack The instructions for selecting the proper roofjack for your installation are detailed later in these instructions Venting Requirements Residential Installations WARNING This furnace is not to be connected to a chimney flue serving a separate ...

Страница 4: ...in operation a Seal any unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required in the ANSIZ223 1 NFPA54 NationalFuelGas Code and ANSI NFPA 31 Installation of Oil Burning Equipment and these instruc tions Determine that there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condition c In s...

Страница 5: ...e used Then mark the 2 1 4 x 7 1 4 opening for the combustion air duct Cut the opening for the feeder duct 14 1 8 x 14 1 8 in flooring cutting opening 1 larger all the waywillallowtheflangesontheundersideofthe base pan to fit in the opening If using the combustion air duct cut the opening for the duct about 1 8 larger than the marking on the floor Be sure to cut through all insulation and the bott...

Страница 6: ...uct sys tem may be small and restrictive to proper air flow The MA 100 base provides approxi mately four 4 inches of additional plenum space before the discharge air enters the manu factured home duct system See Figures 4 and 5 Use the bottom panel of the base assembly to mark the 12 1 8 x 12 1 8 center opening for the feeder duct If using the combustion air duct select and knock out the combustio...

Страница 7: ...ction Set the bottom base panel over the feeder duct Slit the corners of the feeder duct down to the top of the base While the top of the distribution duct is pulled up with one hand bend down each side of the feeder duct tightly to the base with the other hand Trim the metal to allow one inch flange over the top of the base and seal that flange with the metal tape Secure the top panel to the floo...

Страница 8: ...t its inadvertent clo sure by a flat object placed over the open ing C The cross sectional area of the return duct system when located in the floor or ceiling of the manufactured home leading into the closet is to be not less than 200 square inches D The total free area of the openings in the floor or the ceiling registers serving the return air duct system is to be not less than 300 square inches...

Страница 9: ...RJ Roof Jack Installation Refer to Figure 7 to determine SRJ roof jack and appropriate accessories required for your installation Furnace Base Package for O E M and replacement installations Model No MA 200 See Replacement Parts List for types of Base Packages offered Furnace Base Package for replacement installations Model No MA 100 See Replacement Parts List for types of Base Packages offered RA...

Страница 10: ...ion at the top of the furnace Ease the roof jack assembly through the open ings The lower portion of the outer barrel must extend through the finished ceiling as indicated on the barrel Use sealant or caulking on the roof or adaptor to seal under the flashing of the roof jack assembly Extendtheventpipedowntoengagethelocking slot with the screw in the top of the furnace flue pipe Turn to lock and t...

Страница 11: ...d all applicable local codes The materials used must be capable of withstanding exposure to temperatures of at least 700 F The CMF power gas units are fan assisted Installation of Ventilaire III or IV Air Quality Package Accessory The Ventilaire air quality packages are available to meet the ventilation requirements as outlined VENT PIPE 3 FEET MIN ROOF JACK ASSY ROOF CAP ASSY FLEX DUCT CEILING TR...

Страница 12: ...off the main fuel supply if desired by the homeowner or required by local codes The proper gas supply line size can be determined using the gas piping chart shown in Table 3 Black pipe is the most practical for naturalgas becauseofthelargersizesrequired Copper tubing with an internal coating of tin is recommended for use with propane LP gas installations Compounds used on the threaded joints must ...

Страница 13: ...sert the return line through the second opening in the duplex bushing If the bottom of the tank is lower than the pump intake the tube should be inserted three or four inches from the tank bottom If the bottom of the tank is higher than the pump intake the return line should extend not more than 8 inside the tank Hook Up Procedure See Figure 12 1 Use 3 8 O D copper tubing for the fuel line Cap the...

Страница 14: ...VALVE IND L1 HSI HSIG L2 W PSI FSI GV PSO FSG C WHITE RED RED GREEN BLUE BLUE BLACK BLACK BLACK BLACK RED TERMINAL BOARD BUSHING LINE CORD BUSHING TO COMBUSTION MOTOR BURNER ELECTRICAL BOX BUSHING BUSHING OPTIONAL 24V COMMON FOR OPTIONAL ACCESSORY KITS C N L1 GROUND SCREW YELLOW CLOSED END CONNECTOR BLUE BLACK BLACK RED RED T T C W Figure 13 Wiring Diagram Model PGB DI Power Gas Burner Direct Igni...

Страница 15: ...ccor dance with local codes or in the absence of local codes with ANSI NFPA 70 National Elec trical Code Use 14 2 Type NM cable with ground or conduit with single wires Secure the cable at the appliance using a code approved connector Line Voltage Connections Before connecting the power supply wiring become familiar with the wiring of this appliance by reviewing the wiring diagram shown in Figure ...

Страница 16: ...the burner compartment 2 Connect R to one of the low voltage terminals on the burner 3 ConnectWtotheotherlowvoltageterminal on the burner FAN AND LIMIT CONTROLS Constant Blower Operation The button protruding through the cover of the fan and limit control provides either automatic operation of the blower through the thermostat or constant blower operation Pull the button out for automatic operatio...

Страница 17: ...cause some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use the phone Leave the building immediately then call your gas supplier If you cannot reach the gas supplier call the fire department C Use only your hand to push in and move the gas control lever Never use tools If the lever will no...

Страница 18: ...essure of 3 5 in WC and a meter dial size of 1 cubic foot There times are based on LP gas at an average of 2 500 BTU per cubic foot a burner manifold pressure of 3 5 in WC and a meter dial size of 1 cubic foot Table 4 Natural and LP Gas Orifices 1 Shut off all other gas fired appliances except for any pilots 2 Startthefurnaceinheatingmodeandallow it to run for at least three minutes 3 Measure the ...

Страница 19: ...the pressure gauge or U tube manometer from the gas valve and replace thetapplug Ensurethatthetapplugistight and not cross threaded Gas Burner Controls The gas valve lever can be set to ON or OFF as shown in Figure 16 When in the ON position gas flow through the gas valve is allowed when the valve is energized electrically When in the OFF position gas flow is completely shut off Combustion Blower ...

Страница 20: ...erating Instructions as outlined previously in this manual to put the furnace into operation Adjusting the Burner The air shutter is factory pre set for installation in a given furnace as shown in Table 5 You should not need to adjust the air shutter setting of the gas gun burner except when converting thefiringrateofthefurnace Foryourinstallation check to ensure that the air shutter setting is co...

Страница 21: ...er wire on the primary control Oil Burner Shutdown Procedure Set the room thermostat to OFF or its lowest setting Flame Adjustment 1 Turn the thermostat to a setting below room temperature to start the furnace 2 Allow the furnace to operate for about ten 10 minutes 3 Adjust the air shutter setting until 11 CO2 with a number zero smoke or less is achieved Furthermore the draft over the fire must be...

Страница 22: ...er detected The control will attempt to re ignite the gas twice before locking out Once in lock out the control can be reset by interrupting the 24 volt power This can be easily accomplished by setting the thermostat below room temperature for at least forty five 45 seconds and then returning it to the desired setting If adjusting the thermostat does not reset the ignitioncontrol turnoffthepowerto...

Страница 23: ...t switch in open mode d Check for clean air filter and proper airflow e Loose wire connections f Check for tripped manual reset aux iliary limit 3 120 volts is available to burner Test lamp does not light Remove junction box cover on burner check for a Loose wires b Defective transformer c Defective motor B Burner motor does not run no main flame 1 Defective centrifugal switch a Check the operatio...

Страница 24: ...ts thermal load 5 Check thermostat anticipator 0 9 amps H Burner does not shut off Note Burner willstopwhenthedoorswitchisopen With the door open secure the door switch in the closed position by depressing the switch The means for securing the door switch must be removed once this testing has been completed 1 Disconnect the thermostat wires from TT connections on the burner junction box If the bur...

Страница 25: ...u become familiar with the R7184 oil primary control For further service information please refer to Honeywell R7184 Installation Instruc tions 69 1233 and Beckett Technician s Quick Reference Guide RWB 61351 A Burner does not start with a call for heat 1 Check the electrical supply to the furnace 2 Be sure the furnace door switch is in the on position 3 Check for line voltage at the oil primary c...

Страница 26: ...f not in restricted mode replace R7184 d If indicator light stays off while the flame is on check cad cell sighting for view of flame e If burner locks out check cad cell resistance f If burner keeps running system is Okay g If indicator light is off check cad cell assembly after disconnecting line voltage power C Burner will not start and indicator light is flashing at 2 second on 2 second off Ho...

Страница 27: ......

Страница 28: ...A Replaces7080620 Specificationsandillustrationssubject tochange withoutnoticeandwithoutincurringobligations PrintedinU S A 8 01 INSTALLER Please leave these installation instructions with the homeowner EFFICIENCY RATING CERTIFIED ama ...