Nordyne C6DA-T Скачать руководство пользователя страница 6

6

Figure 7. Downflow Furnace with Coil 

Cabinet

SMALL
PLATE

LARGE
PLATE

TABS

MOUNTING
HOLE

OFFSET

Figure 8. Close-Off Plates (Supplied with 

appropriate blower conversion package)

5. REFRIGERANT lINE  

 

    CONNECTIONS

WARNING:

This coil is pressurized with Nitrogen.  
Avoid direct face exposure or contact 
with valve when gas is escaping. Al-
ways ensure adequate ventilation is 
present during the depressurization 
process.  Any uncertainties should be 
addressed before proceeding.

Note:

 For coils with factory installed TXV valve 

proceed to step #8.

Note

: Before proceeding with the connection of 

the refrigerant lines, confirm that the orifice size 
meets the requirements outlined in the outdoor 

unit installation manual. Factory installed orifice 
sizes are listed in the Specifications section. If 
the  restrictor  orifice  must  be  replaced,  follow 
the steps below:

1.  Remove the valve cap from the end of the 

liquid line. Relieve all pressure from the coil 
by depressing the valve. Remove the valve 

core. Properly dispose of all removed parts.

2.  Loosen the orifice body halves by applying 

two wrenches and squeezing them together 
as shown in 

Figure 9

, to turn the assembly 

nut counter-clockwise.

3.  Continue  to  unscrew  the  assembly  nut  to 

separate it from the distributor body.

4.  Insert a light-gauge wire hook between the 

distributor body and the restrictor orifice to lift 
the orifice out of the body. 

(See Figure 10) 

Carefully remove the restrictor orifice being 

careful not to scratch either part.

5.  Check the actual size of the new orifice. The 

size is stamped on its side. Do not use pin 

gauges to measure the orifice diameter.

6.  Insert the new orifice in the distributor body, 

rounded end down. 

(See Figure 11)

7.  After  installing  the  orifice  in  the  distributor 

body, realign the assembly nut to the 
distributor body. Mark a line along both 
bodies after hand tightening and then 

tighten  an  additional  1/4  turn.  Caution:  Do 
not overtighten! The misalignment of the two 
lines will show how much the nut is tightened. 
If a torque wrench is used, tighten to 10-12 
ft. lbs. or 14-16 Nm.

8.  Remove the valve cap from the end of the 

liquid line. Relieve all pressure from the coil 
by depressing the valve. Remove the valve 
core.

 Note:

  On  models  which  use  a  TXV,  it  is 

recommended to wrap a wet rag around the 
suction line between the sensing bulb and 

the line set braze joint before applying any 
heat.

9.  Unbraze and remove the cap on the suction 

line.  Unbraze  and  remove  the  valve  core 

holder on the liquid line.

10. Properly dispose of all removed parts.

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

Содержание C6DA-T

Страница 1: ...licensed installation service personnel for this type of equipment Read all instructions carefully before starting the installation CAUTION Read the installation instructions supplied with the furnac...

Страница 2: ...Downflow Electric Furnace Downflow Electric Furnace Air Handler with Integral Coil Cabinet or Optional Coil Cabinet 4 Verify Pressurization 5 5 Refrigerant Line Connections 6 6 Completing the Install...

Страница 3: ...nnections are ready to be made NOTE Optionalcooling heatingequipmentmust be properly sized and installed in accordance with the furnace manufacturer s specifications and approved recommendations Heati...

Страница 4: ...l it as needed to ensure proper condensate drainage 6 Secure the coil hold down bracket with screws 7 Add air filters to the sides of the coil 8 Cut the floor opening for the refrigerant lines and dra...

Страница 5: ...caping Al ways ensure adequate ventilation is present during the depressurization process Any uncertainties should be addressed before proceeding VERIFY PRESSURIZATION TestbydepressingSchradervalveand...

Страница 6: ...the assembly nut to separate it from the distributor body 4 Insert a light gauge wire hook between the distributor body and the restrictor orifice to lift the orifice out of the body See Figure 10 Car...

Страница 7: ...ng structural damage premature equipment failure or pos sible personal injury Condensate Drain 1 Thread the 3 4 drain fitting included into the lowest tapped hole on the condensate pan Hand tighten th...

Страница 8: ...setpriortocharging Refertotheoutdoor unit installation manual for detailed charging instructions 7 MAINTENANCE AND SERVICE To ensure optimum system performance and to minimize the possibility of equip...

Отзывы: