Nordyne 060C-12 Скачать руководство пользователя страница 21

21

Table 5.  Capacity of Black Iron Gas Pipe

 (cu. ft. per hour) for Natural Gas (specific gravity = .60)

LEAK CHECK

!

 WARNING:

Fire or Explosion Hazard

Failure to follow the safety warnings exactly
could result in serious injury, death or property
damage.

Never test for gas leaks with an open flame. Use
a commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result
causing property damage, personal injury or
loss of life.

After the gas piping to the furnace is complete, all connections
must be tested for gas leaks.  To check for leaks in gas
piping systems, use only a soap and water solution or other
approved method.

!

 CAUTION:

Do not use matches, lighters, candles, or other
sources of open flame to check for gas leaks.

IMPORTANT NOTE:
When pressure testing the gas supply lines at pressures
greater than 1/2 psig  (14 inch W.C.), the furnace must be
disconnected from the gas supply piping system to
prevent damage to the gas control valve. If the test
pressure is less than or equal to 1/2 psig (14 inch W.C.),
the  furnace  must be isolated from the gas supply line by
closing the manual shut-off valve.

Conversion

Conversion of this furnace to use LP/propane gas must
be made by qualified service personnel, using 

only

approved parts.

!

 WARNING:

This furnace was equipped at the factory for use
with natural gas only.  A special kit, supplied by
the manufacturer, is required to convert the
furnace to operate on LP/propane  gas.  Failure to
use the proper conversion kit can cause fire,
explosion, property damage, carbon monoxide
poisoning, personal injury, or death.

NOMINAL 

               LENGTH OF PIPE RUN

BLACK IRON

               (feet)

PIPE DIAMETER

(in.)

10

20

30

40

50

60

70

80

1/2

130

90

75

65

55

50

45

40

3/4

280

190

150

130

115

105

95

90

1

520

350

285

245

215

195

180

170

1 1/4

1050

730

590

500

440

400

370

350

1 1/2

1600 1100

890

760

670

610

560

530

The cubic feet per hour listed in the table above must be greater than the cubic feet

per hour of gas  flow required by the furnace.

To determine the cubic feet per hour of gas flow required by the furnace, divide the 

input rate of the furnace by the heating value of the gas:

     Cubic Feet Per Hour Required    =          Input To Furnace (Btu/hr)

Heating Value of Gas (Btu/Cu. Ft.)

CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)

FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)

High Altitude Application

High altitude application with this furnace can be field
performed by a simple adjustment of manifold pressure,
and if necessary changing the orifices. The changes
required depend on the installation altitude and the heating
value of the gas. The gas heating value based on sea level
can be obtained from your  local gas utility. The heating
value of gas at high altitude is always lower than the sea
level heating value. The heating values used in Tables 6
& 7 are based on sea level values.

Natural Gas High Altitude Conversion

All factory shipped furnaces are ready to operate between
zero and 4999 ft. above sea level.  For higher altitudes
(between 5000 and 10,000 ft. above sea level), conversion
can be achieved simply by adjusting the furnace manifold
pressure as shown in Table 6.

LP/Propane Gas Sea Level and High Altitude
Conversion

IMPORTANT NOTE: 

When converting a low NOx furnace

from natural gas to LP/Propane, it is necessary to remove
the NOx baffles from the furnace.

Conversion of this furnace to utilize LP/propane gas must
be made by qualified service personnel, using factory
authorized or approved parts. Conversion to LP/propane
gas can be accomplished by first replacing the natural gas
orifices with the appropriate LP/propane orifices shown in
Table 8 or 9.  Note: for installations between zero and 5000
ft. above sea level, a #54 or #55 drill size orifice should be
used depending upon the rated firing rate of the unit (see

Содержание 060C-12

Страница 1: ...assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment Read all instructions...

Страница 2: ......

Страница 3: ...er Venting 17 Location of Outdoor Terminations 17 Horizontal Installation 17 Flexible Vent Systems 19 Circulating Air Supply 19 20 General 19 Return Air 19 Gas Supply and Piping 20 22 General 20 Leak...

Страница 4: ...Air Opening Bottom 7 8 FURNACE SPECIFICATIONS Upflow Horizontal Models Figure 1a Upflow Unit Dimensions Table 1a Upflow Furnace Dimensions and Shipping Weights Furnace Dimensions Shipping Model Input...

Страница 5: ...Bottom Opening Bottom Opening 10 1 4 24 1 2 19 3 4 Table 1B Downflow Furnace Dimensions and Shipping Weights Model Furnace Shipping Number Input A B C Weights RK Btuh inches inches inches lbs 060C 12...

Страница 6: ...880 0 0 1 0 650 945 1 0 0 1 720 1050 1 0 0 0 800 1155 1 0 1 0 900 1305 0 1 0 1 1000 1450 0 1 0 0 1060 1530 1 1 0 1 1100 1595 0 1 1 0 1170 1700 1 1 0 0 1290 1870 1 1 1 0 CFM SWITCH NUMBER 2 TON 3 5 TON...

Страница 7: ...publications are available from National Fire Protection Association Inc Batterymarch Park Quincy Massachusetts 02269 WARNING This furnace is not approved for installation in mobile homes Installation...

Страница 8: ...Aconfinedspaceisanareawithvolumelessthan50cubic feet per 1 000 Btuh of the combined input rates of all WARNING Do not place combustible material on or against the furnace cabinet or within 6 inches of...

Страница 9: ...protected to avoid physical damage by vehicles WARNING Donotplacecombustiblematerialonoragainst the furnace cabinet or within 6 inches of the vent pipe Do not place combustible materials including gas...

Страница 10: ...or Type Standard Single Wall Metal Vent Type B 1 Double Wall Metal Vent LEFT SIDE 0 0 RIGHT SIDE 5 0 VENT 6 1 BACK 0 0 BOTTOM 0 0 TOP 1 1 FRONT 4 4 UPFLOW DOWNFLOW INSTALLATION CLEARANCES LEFT SIDE RI...

Страница 11: ...alled directly on combustible wood flooring or supports if type B 1 vent pipe is used See Figure 4 It is recommended for further reduction of fire hazardthatcementboardorsheetmetalbeplacedbetween the...

Страница 12: ...0 000 100 000 120 000 140 000 160 000 Minimum Free Area Each Opening 10 sq in 15 sq in 20 sq in 25 sq in 30 sq in 35 sq in 40 sq in Round Duct Diameter 4 5 5 6 6 7 8 Furnace Water Heater Vent or Chimn...

Страница 13: ...a chimney serving a fireplace the fireplace must be sealed off from the chimney For Category I furnace installations the furnace shall be connectedtoafactorybuiltchimneyorventcomplyingwith a recognize...

Страница 14: ...burner operation Use the flame of a match or candle 8 If improper venting is observed during any of the above tests the venting system must be corrected in accordance with the NationalFuelGasCode ANSI...

Страница 15: ...thends of the bleed tube Do not cover the hole in the bleed tube Place the assembly back on the pressure switch sensor tube and the collector pan sensor tube See Figure 12 2 Remove the nut and restric...

Страница 16: ...pipes and fittings or using support straps All jointsmustbesealedwithhightemperaturesiliconebefore locking bands are installed If the lengths of pipe must be cut the joint must still be sealed with si...

Страница 17: ...nsareprovidedwiththekit Installation must conform to those instructions and applicable requirements of local codes WARNING The entire vent system must be sealed with a high temperature sealant which w...

Страница 18: ...100 00 Btuh 30 kW 36 inches 91 cm for appliances 100 00 Btuh 30 kW 4 feet 1 2 m below or to side of opening 1 foot 300 mm above opening C Clearance to permanently closed window D Vertical clearance t...

Страница 19: ...alf Inner Shield 41 2 Dia Wall Thimble Outer Half Outer Overlapping Shield 61 2 Dia 3 Termination Tee Protective Screen Inside Combustible Wall Inside Combustible Wall 3 Vent Pipe Outside Combustible...

Страница 20: ...e casing to avoid unwanted noise and or damage to the furnace All gas piping must be installed in compliance with local codes and utility regulations Some local regulations requiretheinstallationofama...

Страница 21: ...80 170 1 1 4 1050 730 590 500 440 400 370 350 1 1 2 1600 1100 890 760 670 610 560 530 The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas flow require...

Страница 22: ...ane sea level and high altitude is detailed in the installation instructions provided with the conversion kit Approved conversion kits are listed below UnitedStatesLP PropaneGasSeaLevelandHighAltitude...

Страница 23: ...ors can cause improper and dangerous operation Verify proper operation after servicing Thefurnacecabinetmusthaveanuninterrupted unbroken groundtominimizeinjuryshouldanelectricalfaultcondition occur Th...

Страница 24: ...rounded 2 The thermostat wires R W Y and G are securely connected to the correct leads on the terminal strip of the circuit board 3 The gas line service pressure does not exceed 10 0 in watercolumn 0...

Страница 25: ...the manifold pressure remove the regulator cap and turn the adjusting screw clockwise to increase pressure or counter clockwise to reduce pressure Replace the regulator cap after adjustments are compl...

Страница 26: ...airflows for other modes of operation exceptgasheat aredeterminedbythissetting Table1showstheairflowvaluesversustheairflowselector switch settings and the range of airflow settings recom mended for e...

Страница 27: ...furnace door is in place and that there is power to the furnace Set the thermostat to a temperature above room temperatureandobservetheignitionsequence Theburner flame should carry over immediately b...

Страница 28: ...ame Sensor The flame sensor acts to prove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds of ignition Flame Ro...

Страница 29: ...season Newornewly renovatedhomesmayrequiremorefrequentchanginguntil the construction dust has been removed Filters for side return and bottom return applications are available from your local distribu...

Страница 30: ...WHITE STRIPES WHITE NEUTRAL BLACK 120V GROUND BLACK BLUE FLAME ROLL OUT SWITCH ALL MODELS PRESSURE SWITCH C 180 120 90 60 THERMOSTAT R Y G W YELLOW GREEN BLUE GREY RED YELLOW BLACK WHITE BLACK W W RED...

Страница 31: ...FF position 5 Disconnect the wires from the gas valve igniter flame sensor combustion air motor flame roll out switch blocked vent switch over temperature limit switch pressure switch CAUTION Label al...

Страница 32: ...ctions leak tested ________ Gas Line Pressure _________ in water column with furnace operating Manifold Pressure _________ in water column with furnace operating Is there adequate fresh air supply for...

Отзывы: