1000 PSI Pressure Transducer and Amplifier
6
Part
1602989-02
E
2021
Nordson Corporation
Troubleshooting
WARNING:
Allow only qualified personnel to perform the following tasks. Follow
the safety instructions in this document and all other related documentation.
Armored Cable Pinouts
To check the transducer function, unplug the armored cable from the amplifier and
check for continuity across pins A and D and pins E and F. If you find an open
circuit on either pair, the transducer has failed. Since the transducer and amplifier
are a calibrated set, you must replace the entire assembly.
Pin
Function
A
E
XC +
B
Not Used
C
Not Used
D
EXC -
E
SIG -
F
SIG +
Cordset Pinouts
To check the operation of the amplifier, measure the Vdc across the black and
white wires (Pins B and D). If the voltage is less than 0.995 Vdc at 0 psi or more
than 4 Vdc, replace the entire assembly.
Pin
Wire Color
Function
A
Red
EXC +
(+14 to +28 Vdc)
B
Black
SIG -
C
Green
EXC -
D
White
SIG +
(1 to 4 Vdc)