29
Example
given
φ
1= 30 %rh,
φ
2= 70 %rh
absorption distance B
N
:
1,4 m
(0.36 m for steam distribution system MultiPipe)
Note: If the absorption distance has to be reduced for technical reasons, the amount of steam per unit
must be divided between several steam distribution pipes or the steam distribution system MultiPipe
must be used. If this is the case, contact your Nordmann representative.
Minimum distances to be observed
To prevent the steam, that is emitting from the steam distributor, from condensing on downstream system
components, a minimum distance to the steam distributor must be observed (depends on the absorp-
tion distance "B
N
").
before/after constriction
after expansion
0.5 x B
N
(1.97")
50 mm
0.5 x B
N
before bend
before branch
1 x B
N
1 x B
N
Содержание Omega Pro 10
Страница 1: ...INSTALLATION MANUAL Steam humidifier Nordmann Omega Pro 2588794 A EN 1807...
Страница 63: ......