1-Nov-2021
Page 13
001200MAN-09
Thermostat Requirements
A three-stage heating and two stage cooling heat pump
configurable thermostat is required for two-stage models. The
stages are S1 = Stage 1 compressor, S2 = Stage 2 compressor
and S3 = electric auxiliary (heating only). One can be pur-
chased with the unit, or other heat pump thermostats with the
same number of stages can be used. The electrical box dia-
gram on the electrical box cover provides a description of the
signal connections, as does the below table. Refer to diagram
on a following page for connections between the thermostat and
the heat pump.
NOTE:
Some models are not available in two-stage. Model
numbers with a T in the Compressor Stages designator are two-
stage; models with an S are single stage (verify the model num-
ber against pages 2 and 3 of this manual, or refer to the
Electri-
cal Specifications
near the end of this manual to determine
if the model is two stage or one stage). The Y2 signal is not
used for these units, and they only require a 2 stage heat 1
stage cool thermostat. The stages are S1 = Compressor and
S2 = electric auxiliary (heating only). If the selected thermostat
has more stages than this, configure it for 2 and 1.
TABLE 7 - Control Signal Description
Signal
Description
C
24VAC Common (Ground)
G
Fan low speed (for air recirculation)
Y
1
Heat Pump Stage 1
R
H
24VAC Hot
L
Fault (24VAC when fault condition)
W
2
Heat Pump Stage 3 (auxiliary heat) /
Emergency Heat
O
Cooling Mode (reversing valve)
Y
2
Heat Pump Stage 2 (not used for single
stage units)
AR
1
Airflow Reduction*
AR
2
Airflow Reduction*
C
P
(I)
Plenum Heater dry contact
(Connect to C or I in plenum heater)
1
Plenum Heater dry contact.
(Connect to 1 and 2 in plenum heater)
*
Connect AR
1
to AR
2
with a dry contact to reduce the air-
flow by 15%. Refer to the
Fan Motor
sub-section for more
information.
Airflow Reduction for Zoning
For zoning purposes, airflow may be reduced by 15%
using a switch or dry contact connected to
AR1-AR2
on the
terminal strip. The dry contact may be from a relay and inter-
connected thermostats, or more commonly a zone controller.
For more zoning advice, see
Ductwork
chapter.
Airflow Adjustment
The unit is equipped with a direct drive ECM fan motor for
maximum efficiency. The motor features a soft start which pro-
vides a smooth, quiet ramp up to operating speed . The motor
will maintain the programmed air flow up to a maximum external
static value.
The air flow can be set to four different levels by changing
the position on the Air Flow board located in the electrical box.
The four levels are indicated in the table. Refer also to the air-
flow tables
in the
Model Specific Information
section.
Units are
shipped with the
MED
position selected for nominal air flow.
It is recommended that airflow reduction (below) only be
used with the
HIGH
or
MAX
air flow setting. Care should be
taken to ensure that the unit does not trip a safety control in
heating or cooling mode if the 15% reduction is used in conjunc-
tion with the
MED
or
LOW
air flow setting.
TABLE 8 - Airflow Selections
Position
Airflow
LOW
-6%
MED
Nominal
HIGH
+6%
MAX
+12%
Содержание R-45
Страница 11: ...1 Nov 2021 Page 11 001200MAN 09...
Страница 15: ...1 Nov 2021 Page 15 001200MAN 09...
Страница 16: ...1 Nov 2021 Page 16 001200MAN 09...
Страница 18: ...1 Nov 2021 Page 18 001200MAN 09...
Страница 19: ...1 Nov 2021 Page 19 001200MAN 09...
Страница 21: ...1 Nov 2021 Page 21 001200MAN 09...
Страница 25: ...1 Nov 2021 Page 25 001200MAN 09...
Страница 26: ...1 Nov 2021 Page 26 001200MAN 09...
Страница 27: ...1 Nov 2021 Page 27 001200MAN 09...
Страница 28: ...1 Nov 2021 Page 28 001200MAN 09...
Страница 29: ...1 Nov 2021 Page 29 001200MAN 09...
Страница 33: ...1 Nov 2021 Page 33 001200MAN 09...
Страница 34: ...1 Nov 2021 Page 34 001200MAN 09...
Страница 35: ...1 Nov 2021 Page 35 001200MAN 09...
Страница 63: ...1 Nov 2021 Page 63 001200MAN 09 Wiring Diagram 208 230 1 60...
Страница 64: ...1 Nov 2021 Page 64 001200MAN 09 Electrical Box Layout R 45 75 208 230 1 60...
Страница 65: ...1 Nov 2021 Page 65 001200MAN 09 Electrical Box Layout R 80 208 230 1 60...
Страница 66: ...1 Nov 2021 Page 66 001200MAN 09 Electrical Box Layout RH 45 75 208 230 1 60...
Страница 67: ...1 Nov 2021 Page 67 001200MAN 09 Wiring Diagram 208 3 60...
Страница 68: ...1 Nov 2021 Page 68 001200MAN 09 Electrical Box Layout R 45 75 208 3 60...
Страница 69: ...1 Nov 2021 Page 69 001200MAN 09 Electrical Box Layout R 80 208 3 60...
Страница 70: ...1 Nov 2021 Page 70 001200MAN 09 Electrical Box Layout RH 45 75 208 3 60...
Страница 71: ...1 Nov 2021 Page 71 001200MAN 09 Wiring Diagram 265 277 1 60...
Страница 72: ...1 Nov 2021 Page 72 001200MAN 09 Electrical Box Layout R 45 75 265 277 1 60...
Страница 73: ...1 Nov 2021 Page 73 001200MAN 09 Electrical Box Layout R 80 265 277 1 60...
Страница 74: ...1 Nov 2021 Page 74 001200MAN 09 Electrical Box Layout RH 45 75 265 277 1 60...
Страница 75: ...1 Nov 2021 Page 75 001200MAN 09 Wiring Diagram 460 3 60...
Страница 76: ...1 Nov 2021 Page 76 001200MAN 09 Electrical Box Layout R 25 75 460 3 60...
Страница 77: ...1 Nov 2021 Page 77 001200MAN 09 Electrical Box Layout R 80 460 3 60...
Страница 78: ...1 Nov 2021 Page 78 001200MAN 09 Electrical Box Layout RH 25 75 460 3 60...
Страница 79: ...1 Nov 2021 Page 79 001200MAN 09...
Страница 80: ...1 Nov 2021 Page 80 001200MAN 09...
Страница 81: ...1 Nov 2021 Page 81 001200MAN 09 Dimensions R 45 Left Return...
Страница 82: ...1 Nov 2021 Page 82 001200MAN 09 Dimensions R 45 Right Return...
Страница 83: ...1 Nov 2021 Page 83 001200MAN 09 Dimensions R 55 65 75 Left Return...
Страница 84: ...1 Nov 2021 Page 84 001200MAN 09 Dimensions R 55 65 75 Right Return...
Страница 85: ...1 Nov 2021 Page 85 001200MAN 09 Dimensions R 80 Left Return...
Страница 86: ...1 Nov 2021 Page 86 001200MAN 09 Dimensions R 80 Right Return...
Страница 87: ...1 Nov 2021 Page 87 001200MAN 09 Dimensions RH 45 Left Return...
Страница 88: ...1 Nov 2021 Page 88 001200MAN 09 Dimensions RH 45 Right Return...
Страница 89: ...1 Nov 2021 Page 89 001200MAN 09 Dimensions RH 55 65 75 Left Return...
Страница 90: ...1 Nov 2021 Page 90 001200MAN 09 Dimensions RH 55 65 75 Right Return...