NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters
92
BU 0135 en-4118
5.2.5 Additional parameters
P523
Factory setting
RM
Setting range
0 … 1
Other applicable parameter(s):
P550
Factory setting
{ 0 }
Description
Reset all motor start parameters to the factory settings.
Note
The setting is not permanent until the values from the RAM have been transferred to
the Flash memory (see
P550
).
Setting values
Value
Meaning
0
No change
This function is not implemented.
1
Load factory setting
All parameters are reset to the factory settings. The display then
jumps back to a value of "0".
P535
I²t motor
FL
Setting range
0 … 2
Other applicable parameter(s):
P108, P203, P427
Factory setting
{ 1 }
Description
I²t motor shut
-
off class
– This determines how quickly the motor starter shuts off in the
event of overcurrent. The rated current upon which the I²t monitoring is based is
determined by
P203
. The shut-off takes place almost immediately as of 7.2 times the
rated current. (Error
E3.0
)
Note
The three selectable motor shut-off classes are based on curves that are defined in
EN 60947-4-2.
Setting values
Value
Meaning
0
Class 10A
1.5 times overcurrent for 120 s
1
Class 10
1.5 times overcurrent for 240 s
2
Class 20
1.5 times overcurrent for 360 s
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...