NORDAC PRO – Migration guideline SK 5xxE to SK 5xxP
46
MI 0500 en-2922
Pos : 89 /Migrati onsl eitf aden/N ORDAC PR O/ SK 5xxE - SK 5xxP/Migration/Z ubehör- Komponenten/U nt erbau-Netz filter @ 83\ mod_1639475647604_388.doc x @ 2850579 @ 45 @ 1
2.9.2.2
Footprint line filter
In the table below, the different SK LF2-… footprint line filters are assigned to the individual power
ranges for the SK 5xxE. Footprint line filters are only available for a 3-phase mains connection.
Depending on the space available and the respective depth in the control cabinet, the footprint line
filters can be mounted flat or vertically (book size) next to the frequency inverter.
Information
Optional footprint line filters for the entire SK 5xxP power range are available via the Getriebebau
NORD sales department
only on request
.
Illustration 10: NORDAC PRO SK 5xxE footprint line filter
The SK LF2-… footprint line filters are UL certified and can only be installed in the control cabinet due
to their IP00 protection class version. The connection cable for the mains connection must be provided
and should be as short as possible. The mains cable is connected using screw terminals. The footprint
line filters must be connected to the frequency inverter’s mains connection on the outgoing circuit side
using the pre-assembled connection cables.
Information
Compliance with the wiring guidelines must be ensured when connecting. In the additional
parameters, the pulse frequency should be set to the factory setting (6 kHz). For detailed information,
please refer to the technical information
Chapter 5.1.2 "Technical information/Data sheets".