Troubleshooting - Quick Reference

Quick Reference Troubleshooting Steps

Check for supply voltage at the rear of the refrigerator. 

1. 

Turn the temperature control to the "On" position.

2. 

The operating voltage should be between 10.5V and 

32V DC. There will be some variation in these readings 

depending on the supply voltage.
Check the compressor voltage between points A and B. 

3. 

Voltage should be between 15V - 25V AC. Refer to Figure 

10.
If voltage is not within range, refer to Procedure C.
With the refrigerator power on, take an Ohm reading (1.4 

4. 

- 3.5Ω) at the compressor between points A and B. Refer 

to Figure 11. 
If the Ohm reading is not within range, refer to Procedure 

B.
With the refrigerator power off, and the lead removed 

5. 

from point "A", take an Amp reading (1.6 - 3.3 Amps) at 

the black wire with the rubber boot. Refer to Figure 12. If 

amperage is not within range, refer to Procedure D.

A

B

AR

T01949

Figure 10. Checking Compressor Voltage

AR

T01958

B A

Figure 11. Taking an Ohm Reading

A

AR

T01953

Figure 12. Measuring the Amp Draw

Содержание DC-0040

Страница 1: ...T DC0740 X DE0740 X DC0751 X DE0751 X DC0040 K DC0051 K MODELS Part No 631842A 08 08 07 2007 NORCOLD INC All rights reserved Please note that the X at the end of certain model numbers indicates the eq...

Страница 2: ...Measuring Compressor Amp Draw 6 Troubleshooting Procedure E Verifying Thermistor Operation 7 Troubleshooting Procedure F Insufficient Cooling 8 Troubleshooting Procedures G Refrigerator is Too Cold 8...

Страница 3: ...everse Polarity Check Operation Red Black OK Replace 10A Fuse See Figure 2 OK Check DC Polarity INCORRECT OK Compressor Runs YES NO Check Both DC Fuses BLOWN OK Compressor Runs YES NO DC 0V DC 12 to 3...

Страница 4: ...3 5 Normal Internal Compressor Failure See Procedure C Change Cooling Unit Note Perform procedure at room temperature ART01947 Measuring the Compressor Resistance Turn the temperature control to the O...

Страница 5: ...Failure DC Power Supply Failure Check AC Power Supply 37 45V DC See Figure 5 Check AC Power Supply 37 45V DC See Figure 5 Power Source Less than 15V AC 15 25V AC Measure Voltage Between A B At the Com...

Страница 6: ...sure Amperage at A on the Compressor See Figure 6 Normal 40Watt 1 6 2 0Amps 60Watt 2 7 3 3Amps 40Watt 1 6Amps 60Watt 2 7Amps 40Watt 2 0Amps 60Watt 3 3Amps Compressor Failure Compressor Failure Change...

Страница 7: ...ce of the thermistor Refer to Table 1 for a listing of acceptable resistance ranges NOTE In general 1 6K 29K good thermistor defective thermistor An open thermistor will stop normal compressor operati...

Страница 8: ...ting The compressor vibrates but there is no cooling Troubleshooting Procedure G Refrigerator is Too Cold If the refrigerator is too cold do the following Adjust the temperature control to a lower set...

Страница 9: ...the vents by closet or cabinet doors Reducing the vent area can cause the following Shortened life of the refrigeration cooling unit Poor cooling performance of the refrigerator Continuous operation...

Страница 10: ...between points A and B 3 Voltage should be between 15V 25V AC Refer to Figure 10 If voltage is not within range refer to Procedure C With the refrigerator power on take an Ohm reading 1 4 4 3 5 at the...

Страница 11: ...This Page Intentionally Left Blank...

Страница 12: ...XX DEXXXX Compressor Refrigerator Service Manual Part No 631842A 08 08 07 NORCOLD Inc Customer Support Dept Telephone 800 543 1219 Fax 937 497 3183 www norcold com NORCOLD Inc P O Box 4248 Sidney OH 4...

Отзывы: