Wiring the Hold switch:

 

An optional Hold switch can be 
used to allow the load to remain 
energized after the hand switches 
are released. This feature is 
useful for applications that have 
long machine cycles. 
 
The Hold switch is normally open 
and must not be closed until the operator can no longer reach into the point of 
operation. Once the Hold switch is closed, it should remain closed for the rest 
of the machine cycle. The Hold switch circuit does not become functional until 
the machine cycle has begun. 
 
The Hold switch is connected to terminals marked "HOLD". The terminal to the 
right is also used by the Reset circuit. Do not remove the reset jumper wire 
unless you are installing the optional Reset switch as described below. 

 
 

Warning! 

The Hold switch must be mounted on the machine so that it 
cannot close until the point of operation is no longer 
hazardous.  

 

 

Wiring the Reset switch:

 

An optional switch can be used to reset the Start Bar when a machine cycle is 
completed. 
 
Remove the jumper wire from 
the terminals marked "RESET" 
prior to installing the wires 
connected to the reset switch. 
The left terminal also shared 
with the optional Hold switch (if 
installed). 

 

The Reset switch is normally closed and will reset the control when it is 
opened. This switch must be closed before a machine cycle can be started. 

 

Содержание TB-2 Series

Страница 1: ...t Bar is an ergonomic starting system The internal anti tiedown control monitors both start sensors for concurrent operation The output utilizes redundant positive guided relays which are monitored to...

Страница 2: ......

Страница 3: ...ent operation of the trip controls or levers by the operator s hands to initiate the machine cycle Each Nolatron hand control is protected against unintended operation and arranged by design construct...

Страница 4: ...y other control device unless it is of a control reliable design General purpose programmable controllers PLCs are not intended for such an application Please call Nolatron at 717 564 3398 for technic...

Страница 5: ...the anti tie down control Metal shavings caused by drilling may cause an internal electrical short circuit This chamber is sealed to keep out contaminants such as oil drilling additional holes may all...

Страница 6: ...er machine cycle can be started An optional load timer can be used to limit how long the load will receive power The TB 2 is reset after the time cycle is completed See parts list Wiring the Start Bar...

Страница 7: ...tact To configure the output this way do not install the jumper wire from the terminal marked 115 VAC and the output contact as indicated above Warning Do not connect the output of the Start Bar to th...

Страница 8: ...d HOLD The terminal to the right is also used by the Reset circuit Do not remove the reset jumper wire unless you are installing the optional Reset switch as described below Warning The Hold switch mu...

Страница 9: ...ght is on and that the Output light is off 4 Activate the left start switch Verify that the Ready light is off 5 Wait for at least a second then activate the right start switch 6 Verify that the Ready...

Страница 10: ...millisecond response time Model TB 2M Mechanical switches with polyurethane cover 8oz actuation force Warranty Nolatron LLC warrants the Start Bar against defects in material and workmanship under nor...

Страница 11: ...uminum housing 055026 front access plate with gasket 055028 3 8 6 32 black Phillips head screws 8pcs 055031 5 8 6 32 socket head screws 3pcs 055040 mechanical hand switch assembly model TB 2M Optional...

Страница 12: ...5198 Richmond Rd Bedford Heights OH 44146 Phone 717 564 33 Fax 216 274 9262 www nolatron com sales nolatron com 2018 Nolatron LLC P N APPTB 2 Rev Date 15 Feb 18...

Отзывы: