NOJA-7343-03
11
Ground Mount Kiosk (GMK-1000 Series)
User Manual
E
ARTH
B
AR
The GMK enclosure, recloser and RC10 components are connected to earth through the earth bar located at the
bottom of the recloser.
A cable entry has to be prepared on the HV gland plate to suit the incoming main earth cable which will be then
connected to the earth bar.
The earth bar comes with M12 nut and bolt that can be used in connecting the main earth cable.