rES7 Sensor

 

Fixture Embedded Smart Sensor

360° COVERAGE 

• 

LOW VOLTAGE

 • 

WIRELESS

Acuity Brands | One Lithonia Way Conyers, GA 30012  Phone: 800.535.2465   www.acuitybrands.com   © 2021 Acuity Brands Lighting, Inc.   All rights reserved.   Rev. 04/29/2021

IS-RES7-002         

TYPICAL INSTALLATION INSTRUCTIONS (may vary by luminaire)

• Attach foam pads to surface of rES7 as shown. 

Adjust thickness of pad as needed to fill gap 

between sensor body and end cap.

• Attach wires to sensor according to the 

diagram below. Wire locations are also shown 

on product label.

• Ensure thin wire antenna points toward the 

center of the fixture, between the LEDs and 

diffuser.

• Place the rES7 in the fixture, with the rES7 

cylinder aligned to the clearance hole.

• Insert rES7 lens assembly through the hole, 

securing it to the sensor body.

• Install diffuser.

• Attach wires to sensor according to the wiring diagram below. Wire 

locations are also shown on product label.

• Route the coax cable through the inside of the fixture to the 

antenna hole.

• Affix the o-ring, washers, and nut as indicated on the drawing (2) to 

the external surface of the fixture.

• Attach external antenna (1) to the brass SMA connector. Torque 

spec for proper installation is 5in-lbs. 

• Place the rES7 in the fixture, with the rES7 cylinder aligned to the 

clearance hole.

• Secure the lens assembly to the rES7 body.

For further troubleshooting guidance, please contact the Controls Technical Support Team 

1(800)-535-2465

TYPICAL INSTALLATION FOR EXTERNAL ANTENNA (optional)

SENSOR BODY

FOAM PADS

LENS ASSEMBLY

HOLE

ANTENNA

• The rES7 is a wireless sensor that can be interconnected with the nLight® AIR network of wireless sensors and switches.

• The rES7 is compatible for use in fixtures with eldoLED drivers, or other analog (0-10VDC) third party aux drivers.

• The rES7 with EM option provides UL924 emergency operation when paired with an EldoLED driver that supports power loss detection.  Emer-

gency transfer switches must be break-before-make, delayed transition type, and set to ensure at least 200 msec interruption of load power 

when transferring from normal to emergency sources.  All testing must be performed in a manner which ensures this interruption of the power 

supplied to the egress lighting.

rES7 BASIC OVERVIEW

1

2

2

2

2

2

SECTION VIEW OF EXPLODED DUALBAND ANTENNA IN 

CASTING DETAIL

LOCK WASHER

O-RING

NUT

FLAT WASHER

  0.250 

  0.390 

 0.056 

 0.044 

 0.150 

0.85

PROVIDE CLEARANCE FOR

ASSEMBLY TOOL

MOUNTING HOLE DETAIL

• Occupancy Control: 

Enabled

• Microphonics (with -PDT): 

Enabled

• Occupied Dim Level: 

100%

• Unoccupied Time Until Dim: 

2.5 Minutes

• Unoccupied Dim Level: 

1%

• Dim to Off Time Delay: 

7.5 Minutes

• Daylighting Control: 

Enabled

• Daylighting Set Point:

 10 fc

• Daylighting Transition On Time: 

45 Seconds

• Daylighting Transition Off Time: 

10 Minutes