rES7 Sensor
Fixture Embedded Smart Sensor
360° COVERAGE
•
LOW VOLTAGE
•
WIRELESS
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/29/2021
IS-RES7-002
TYPICAL INSTALLATION INSTRUCTIONS (may vary by luminaire)
• Attach foam pads to surface of rES7 as shown.
Adjust thickness of pad as needed to fill gap
between sensor body and end cap.
• Attach wires to sensor according to the
diagram below. Wire locations are also shown
on product label.
• Ensure thin wire antenna points toward the
center of the fixture, between the LEDs and
diffuser.
• Place the rES7 in the fixture, with the rES7
cylinder aligned to the clearance hole.
• Insert rES7 lens assembly through the hole,
securing it to the sensor body.
• Install diffuser.
• Attach wires to sensor according to the wiring diagram below. Wire
locations are also shown on product label.
• Route the coax cable through the inside of the fixture to the
antenna hole.
• Affix the o-ring, washers, and nut as indicated on the drawing (2) to
the external surface of the fixture.
• Attach external antenna (1) to the brass SMA connector. Torque
spec for proper installation is 5in-lbs.
• Place the rES7 in the fixture, with the rES7 cylinder aligned to the
clearance hole.
• Secure the lens assembly to the rES7 body.
For further troubleshooting guidance, please contact the Controls Technical Support Team
1(800)-535-2465
TYPICAL INSTALLATION FOR EXTERNAL ANTENNA (optional)
SENSOR BODY
FOAM PADS
LENS ASSEMBLY
HOLE
ANTENNA
• The rES7 is a wireless sensor that can be interconnected with the nLight® AIR network of wireless sensors and switches.
• The rES7 is compatible for use in fixtures with eldoLED drivers, or other analog (0-10VDC) third party aux drivers.
• The rES7 with EM option provides UL924 emergency operation when paired with an EldoLED driver that supports power loss detection. Emer-
gency transfer switches must be break-before-make, delayed transition type, and set to ensure at least 200 msec interruption of load power
when transferring from normal to emergency sources. All testing must be performed in a manner which ensures this interruption of the power
supplied to the egress lighting.
rES7 BASIC OVERVIEW
1
2
2
2
2
2
SECTION VIEW OF EXPLODED DUALBAND ANTENNA IN
CASTING DETAIL
LOCK WASHER
O-RING
NUT
FLAT WASHER
0.250
0.390
0.056
0.044
0.150
0.85
PROVIDE CLEARANCE FOR
ASSEMBLY TOOL
MOUNTING HOLE DETAIL
• Occupancy Control:
Enabled
• Microphonics (with -PDT):
Enabled
• Occupied Dim Level:
100%
• Unoccupied Time Until Dim:
2.5 Minutes
• Unoccupied Dim Level:
1%
• Dim to Off Time Delay:
7.5 Minutes
• Daylighting Control:
Enabled
• Daylighting Set Point:
10 fc
• Daylighting Transition On Time:
45 Seconds
• Daylighting Transition Off Time:
10 Minutes