06:
Bypass enable/disable when UPS is off
Parameter 3:
Enable or disable
Bypass function. You may choose
the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07:
Bypass voltage range settings
Parameter 2&3:
Set the acceptable
high voltage point and acceptable
low voltage point for Bypass mode
by pressing the Down key or Up
key.
HLS:
Bypass high voltage point
-> 230-264: setting the high
voltage point in parameter 3
from 230Vac to 264Vac. (Default:
264Vac)
LLS:
Bypass low voltage point
-> 170-220: setting the low voltage
point in parameter 3 from 170Vac
to 220Vac. (Default: 170Vac)
08:
Autonomy limitation settings
Parameter 3:
Set up backup time
on battery mode for general
outlets.
0-999:
setting the backup time in
minutes from 0-999 for general
outlets on battery mode.
0:
When setting as “0”, the backup
time will be only 10 seconds.
999:
When setting as “999”,
the backup time setting will be
disabled. (Default)