does not exceed 3450W (but not more than 1150W on
any one channel)
or:
loads of up to 1150W may be connected to all eight
channels provided that the unit is operated so that the total
load that is switched on at any one time does not exceed
3450W.
If connected to a lower capacity supply, or by a standard
British 13Amp BS1363 plug and socket, the output must be
reduced as follows:
•
For a 13A supply
, the maximum total load is 2990W
which can be made up of:
either:
375W watts on each of the eight channels
or:
different loads on each channel so that the total does
not exceed 2990W (but not more than 1150W on any one
channel)
or:
loads of up to 1150W may be connected to all eight
channels provided that the unit is operated so that the total
load that is switched on at any one time does not exceed
2990W.
Inductive loads:
If connecting inductive loads such as motors or
discharge lighting (metal halide, fluorescent or neon) to the
Euro 8s, make sure that the VA rating of the load does not
exceed the figures above (1150VA per channel, 3450VA
total). The VA rating should be labelled on the apparatus
being connected. If the VA rating is not known, reduce the
maximum handling capacity to 800W per channel, and
2400W total.
High-inrush loads.
If connecting high inrush loads, such as halogen lamps
or apparatus incorporating a transformer, reduce the
handling capacity to 800W per channel, and 2400W total.
User Guide
Euro 8s
© N.J.D. Electronics 2001
-Page 3-