Page 13
5.6 U1000-HM Interface Cables
The U1000-HM interface cable supplied is a 6-core cable for power and pulse output connections and
a separate 4 core plug-in cable for the Modbus connections.
The un-insulated wire is the connection to the screen of the cable and should be earthed for full
immunity to electrical noise.
Figure 8 instrument connections
5.7 Connecting The U1000-HM To The Supply
The U1000-HM will operate within the voltage range 12 - 24V ac/dc. The supply must have a minimum
rating of 7VA. Connect the external power supply to the Brown and Blue wires of the six core cable.
Ensure that the supply wires are NOT earthed / grounded.
This equipment is designed to work with a non-earth referenced power supply. If a power supply with
a connection to ground is used in conjunction with a communications link an earth loop may be formed
that can damage the instrument. See the notes below:
Power
Figure 8. U1000-HM Interface Cable