NIVELCO UNICONT PDF-401-A EX Скачать руководство пользователя страница 7

BKI15ATEX0013X/1 

 pdf4012a0600p_06 

 7 / 20 

 

4.1

 

W

IRING

 

 

2-wire indicators are used in 4–20 mA current loops. They do not require external power supply. 

 

3-wire devices are powered with 10 V…36 V DC (Ex type devices: 10 V...30 V DC) through the output. 

 

Make sure, that current values on the internal terminals should not exceed overload capability limits. 

 

Wiring should be done with shielded cable, specified under ‘Technical Data’ table. 

 

Devices should be grounded by using their grounding screws. 

 

The screw terminals can be accessed after removal of the housing cover and the display module. 

 

After wiring and programming the cover should be screwed to tightness of the sealing. 

 

!

 

The types with stainless steel housing are not allowed to be set up and installed until,  

the „Ex d” certified cable gland is not fixed to the place of the red plastic closing cap with proper sealing! 

The metal plug may only be removed if 2 cable glands are used. 

!

 

The housing cover of the flameproof device is allowed to remove only when the unit is de-energized! 

The housing cover can be removed after unscrew the M2 size hex socket set screw 

or after dismounting the safety locking bolt by unscrew the M4 size hex socket set screws. 

!

 

The instrument may be damaged by electrostatic discharge (ESD) via its terminal, thus apply the precautions commonly used to avoid 

electrostatic discharge e.g. by touching a properly grounded point before removing the cover of the enclosure. 

A possible electrostatic discharge can cause damage for the instrument. Do not touch the internal terminals! 

!

 

After wiring and programming the housing cover should be closed properly and the hex socket set screw or the safety locking bolt should be 

tightened! The sealing ring must be replaced if damaged, otherwise the IP class of the device can be jeopardized. 

 

 

4-20mA

4-20mA

PDF- 401-6/A/C Ex

Us

6

1

Ex Ex

 

Figure 2.  Wiring of a 2-wire Unicont in the current loop of a transmitter 

R 250 

≥ Ω

HART

Us

4-20mA

P   F-401-8/B/D Ex

  

Ex Ex

6

1

 

Figure 3.  Wiring of a HART capable (3-wire) Unicont  

in the current loop of a transmitter 

Shielding should be grounded at one point.

Содержание UNICONT PDF-401-A EX

Страница 1: ...df4012a0600p_06 1 20 Manufacturer H 1043 Budapest Dugonics u 11 Phone 36 1 889 0100 Fax 36 1 889 0200 sales NIVELCO Process Control Co E mail nivelco com www nivelco com UNICONT PDF loop indicator and...

Страница 2: ...G INTO OPERATION PROGRAMMING 10 5 1 DEFAULT 11 5 2 DISPLAY OF THE SAP 202 AND KEYS OF THE UNIT 11 5 3 PROGRAMMING 12 5 3 1 STEPS OF PROGRAMMING 12 5 3 2 PARAMETERS DESCRIPTION AND PROGRAMMING 14 5 4 E...

Страница 3: ...o HART signals and so enable devices that have analogue outputs only to be integrated into HART multidrop systems The ratio between the input and output current can be programmed The intelligent elect...

Страница 4: ...r displayed values over 10000 Temperature coefficient 0 05 10 K Output 4 20 mA and or HART for 4 20mA current limit values 3 9 20 5 mA terminal resistor for HART Rtmin 250 Error indication on the curr...

Страница 5: ...tic M20x1 5 for cable diameter 6 12 mm Metal M20x1 5 for cable diameter 7 13 mm Metal M20x1 5 for cable diameter 8 12 mm Ambient temperature 25 C 70 C TYPE P F 501 8 EX P F 401 8 EX P F 601 8 EX P F 4...

Страница 6: ...ts Installation and programming manual Warranty Card Declaration of Conformity Sticker set of engineering units HART os k sz l kn l CDROM az EView2 programmal 4 INSTALLATION AND ELECTRIC CONNECTION Th...

Страница 7: ...the flameproof device is allowed to remove only when the unit is de energized The housing cover can be removed after unscrew the M2 size hex socket set screw or after dismounting the safety locking bo...

Страница 8: ...Wiring of a HART capable 3 wire Unicont in the current loop of a 4 wire transmitter HART L L SH Us 4 20mA 4 20mA Transmitter Ex 1 P F 01 8 B D Ex Ex Ex HART 6 1 6 1 Transmitter Ex 2 R 250 P F 01 8 B D...

Страница 9: ...0 20mA 4 20mA 0 20mA HART 6 6 1 1 P F 01 4 Transmitter 1 Transmitter 15 R 250 Figure 6 Wiring of 3 wire Uniconts with Multicont controller and 4 wire transmitters 1 6 R 5 Figure 7 Internal wiring of...

Страница 10: ...dow of intrinsical safe equipment with metallic enclosure exceeds the limit thus the devices must be protected against electrostatic charges Equipment with plastic housing are susceptible to electrost...

Страница 11: ...put current appears on the display of the 2 wire models While pressing the key the output current appears on the display of the 3 wire models 5 2 DISPLAY OF THE SAP 202 AND KEYS OF THE UNIT Symbols on...

Страница 12: ...of PROGRAMMING mode It is also used in programming mode This is represented in the manual with the symbols of the two keys and the sign in between them That is E getting into PROGRAMMING mode This pro...

Страница 13: ...er values to default LOAD is be displayed for warning Reset default value of the relevant parameter LOAD will be displayed for warning GET VALUE function for automatic setting of P0 and P1 Actual meas...

Страница 14: ...current value is to be entered in P0 or P1 it can automatically be set by the GET VALUE function To do so the above described procedure should be performed but pressing instead of step 4 Successful se...

Страница 15: ...e set for 0 20 mA P9 a Current generator test for 3 wire models only In this parameter the actual current output is displayed Going to the parameter value the output current of 3 6 22 mA can be set by...

Страница 16: ...ut current to be the error indication of the Unicont For 3 wire models only Attention character a is at the right end this is the first to blink a Range selection d Error indication on the current out...

Страница 17: ...S 3 cm in VOL C 4 l gal FLOW 5 t 6 F P13 00ba HART short address for 3 wire models only FACTORY DEFAULT 00 The short address of the unit for the multidrop system HART network is to be given here Pleas...

Страница 18: ...cm2 35 Kelvin 61 kg 87 LTon h 126 152 ft3 lb 10 kg cm2 36 mV 62 MetTon 88 LTon d 127 kW 153 pF 11 Pa 37 ohm 63 lb 89 128 kWh 154 mL L 12 kPa 38 Hz 64 STon 90 129 hp 155 uL L 13 torr 39 mA 65 LTon 91...

Страница 19: ...ess E to go to the address and E again to return to value Enter the new secret code or 0000 If there is no secret code or it is not active the PROG symbol is blinking 5 4 ERROR INDICATIONS 5 4 1 VALID...

Страница 20: ...ned All repairs will be carried out only on the premises of the Manufacturer 7 STORAGE Ambient temperature 25 C 60 C Relative humidity max 98 8 WARRANTY NIVELCO provides warranty of 3 three years in c...

Отзывы: