5.3.2.
P
ARAMETERS
–
DESCRIPTION AND PROGRAMMING
Attention! Before programming it is suggested to read the description of parameter
P10
carefully!
P0: - - - a
Setting input current (Ia) that is to be assigned to displayed value (Da) See Figure 9, 10 and 11
FACTORY DEFAULT: 4 mA
P1: - - - a
Setting input current (Ib) to be assigned to displayed value (Db)
FACTORY DEFAULT: 20 mA
The current value can be entered in P0 and P1 manually
For instance, entering 5.6 mA in P0 should be performed as shown below:
1. Press
E
+
to get into PROGRAMMING mode
2. Press
to go to P0
3. Press
E
to go to the parameter value
4. Press
/
/ to adjust the display to 5.6
5. Press
E
+
to return to MEASUREMENT mode
If the actual current value is to be entered in P0 or P1 it can automatically be set by the GET VALUE function. To do so the above described
procedure should be performed, but pressing
+
(instead of
/
/ ) (step 4.). Successful setting is indicated by the message ‘SET’
displayed.
Remarks:
If the input current range is set for 4 … 20 mA, than the value of P11 can not be set below 4 mA in P0 and the value of P1 can not exceed 20 mA.
An input current value outside of this range would make VALID LED and current value display blinking.
P2:
Setting displayed value (Da) to be assigned to input current Ia See Figure 9, 10 and 11
FACTORY DEFAULT: 0.0
P3:
Setting displayed value (Db) to be assigned to input current Ib
FACTORY DEFAULT: 100.0
P4:
Setting output current pertaining to the input current Ia (for 3-wire models only)
FACTORY DEFAULT: 4 mA
P5:
Setting output current pertaining to the input current Ib (for 3-wire models only)
FACTORY DEFAULT: 20 mA