P24: - - - a Target tracking speed
With this parameter the evaluation can be sped up at the expense of the accuracy.
a
Tracking speed
Remark
0
Standard For
most
applications
1
Fast
For fast changing level
2
Special
For very special cases only, as this reduces the maximum measuring range to 50% of the nominal value! The
measuring window (P25 and P33) is inactive and the EasyTREK will respond practically instantly to any target.
FACTORY DEFAULT: 0
P25: - - - a
Selection of Echo within the measuring window
A so-called measuring window is formed around the echo signal. The position of this measuring window determines the flight time for calculation of the
distance of the target. (the picture below can be seen on the test oscilloscope)
Received
signal
amplitude
Echo 1.
t
"t" ultrasound flight time
Echo 2.
Some applications involve multiple ( disturbing) echoes even within the measuring window. Basic echo selection will be done by the Quest +
software automatically. This parameter only influences the echo selection within the measuring window.
a
Echo in the window to be selected
Remarks
0
With the highest amplitude
For most applications (both liquids and solids)
1
First one
For applications with multiple echoes within the Measuring Window
2
Largest one
Recommended for applications with floating material in the air
FACTORY DEFAULT: 0
P26: - - - - Level elevation rate (filling speed) [m/h]
FACTORY DEFAULT: 500