5.4.4.
M
EASUREMENT OPTIMALIZATION
P20: - - - a Damping
This parameter can be used for reduction of unwanted fluctuation of the displayed value and the output.
a
Damping time [s]
Granules
particle size >2-3 mm
D
UST
particle size < 1-2 mm
0
None
For test only
1
3 Not
recommended
Not recommended
2
6
Not recommended
Not recommended
3
10
Not recommended
Not recommended
4
30 Applicable
Not
recommended
5
60 Recommended
Applicable
6
100 Recommended
Recommended
7
300 Recommended
Recommended
8
600 Recommended
Recommended
9
1000 Applicable Applicable
FACTORY DEFAULT: 7 ( 300 s )
P23: - - - a Angle of repose (repose formation)
This parameter is important for the optimalisation of the of the QUEST+ software echo evaluation.
a
Estimated angle of repose
0
No angle of repose
α
≅
0
1
α<
15
°
2
α
> 15
°
The optimal setting of this parameter can be done with the help of checking the echo strength in
the read out parameter P72 indicating the echo amplitude in dB.
The ideal setting of P23 is at which the parameter value in P72 becomes the best (nearest “0”).
FACTORY DEFAULT: 0