background image

02

NISM/STPA/02

DATE:

PAGE:

No:

ISSUE:

of

3

7

ST-P-AS

ANALOGUE-ADDRESSABLE

PHOTOELECTRIC SMOKE SENSOR

INSTRUCTION MANUAL

MARCH 2001

Section 2 - ST-P-AS OPERATION

The ST-P-AS utilises the light scatter sensing
principle, using an LED and photodiode in a light proof
chamber.  The LED pulses infrared light into the
smoke chamber, the photodiode being positioned
such that a minimum of light is normally received.  As
the smoke enters the sensor the amount of scattered
light increases.  This change is detected by the
photodiode and is amplified before being processed
and transmitted to the control panel

Section 3 - SENSOR MODELS

The ST-P-AS photoelectric smoke sensor is supplied,
as standard, with three terminals.
The ST-P-AS has the facility to activate a remote LED
indicator or auxiliary function, as standard.
The terminals on the ST-P-AS sensor head are
configured as follows:-
Terminal 3 =  -VE 3 mA aux output
Terminal 1 =  Sig + (+VE) positive in/out
Terminal 6 =  S- (-VE) negative in/out

Section 4 - BASE MODELS

STB-4 Base: 

having 4 terminals, for standard

use with ST-P-AS sensor including the auxiliary
output function.

Section 5 - INSTALLATION

In normal use, the ST-P-AS sensor will be installed at
ceiling level.  Pass the field wiring through the cable
hole in the centre and from the rear of the base.  Offer
up and affix the base to the ceiling or conduit fitting
with screws via the base mounting holes.  Consider
visibility and orientation of the sensor's integral alarm
LED indicator when mounting the base.  Connect the
field wiring to the base terminals, as detailed on page
6 making sure the wiring does not obstruct fitting of
the detector head.  Fit the sensor head by inserting it
into the base and turning clockwise until the notch in
the detector rim aligns with base locking screw.

Fit the plastic dust cover supplied over the sensor to
keep out dust etc, until the system is commissioned.
If the dust cover is not fitted and the environment is
slightly dusty, such as when building work is being
completed, for example, problems of false alarms are
likely to occur after commissioning unless cleaning of
the sensor is undertaken.  At commissioning, the dust
cover should be removed and discarded.

NOTE: THE PLASTIC DUST COVER MUST BE
REMOVED FROM THE SENSOR IN ORDER FOR
THE SENSOR TO FUNCTION CORRECTLY.

Section 6 - MAINTENANCE AND
CLEANING

Maintenance:

The ST-P-AS sensor is a high quality product engi-
neered for reliability.  In order to obtain optimum per-
formance, periodic maintenance is required as a dirty
detector is more likely to cause a false alarm.

Servicing:

Servicing of the system should be carried out in accord-
ance with the requirements of BS 5839 Part 1, Fire
Detection and Alarm Systems for Buildings: Code of
Practice for System Design, Installation and Servicing.

The maintenance procedures described below should be
conducted with the following frequency:

One month after installation:-

Routine Inspection
and every 3 months
after.

Every 6 months:-

Operational Test

Every 12 months:-

Functional Test and
Clean

All above frequencies of maintenance are dependent on
ambient conditions.

Routine Inspection
i) 

Ensure the sensor head is secure and undamaged.

ii)

 Check the smoke entry apertures are in no way

obstructed.

iii)

 Ensure the surface of the sensor’s outer cover is

clean.  If there are deposits due to the presence of oil
vapour, dust etc, then the sensor should be cleaned in
accordance with the cleaning instructions detailed later
in this manual.  It may be advisable to ensure that such
cleaning is conducted regularly in the future.

iv)

 Ensure no equipment which may generate combus-

tion products or fine airborne particles, has been in-
stalled in the vicinity of the detector since the last
routine inspection.  If such equipment has been in-
stalled, then you should notify the Fire Safety Officer or
other competent authority that it’s presence may
cause false alarms.

Operational Test

The purpose of the Operational Test is to confirm the
sensor’s correct operation in response to a smoke
condition.

i) 

Take any necessary precautions at the control panel

to limit the sounding of the alarm sounders/bells and
any fire service summoning device.

Содержание ST-P-AS

Страница 1: ... from Nittan UK Ltd called SENSORTEC ANALOGUE The ST P AS is a low cost elegantly designed low profile sensor which is aesthetically pleasing thus enabling it to blend unobtrusively into modern working environments The ST P AS features the very latest technological advancements increasing reliability and performance The ST P AS is compatible with our existing AS protocol and is compatible with lea...

Страница 2: ...T3 or TT4 electronic tester Available early 1998 ST P AS features Opticaldetector detectingvisibleparticles of combustion Low profile stylish appearance Supplied with protective dust cover remove during commissioning Low monitoring current Integral LED fire alarm indicator Remote indicator output on standard models Easytodisassembleandreassembleforcleaning UsesSTB 4 earlierRB 3 RB 6Bases Manufactu...

Страница 3: ... building work is being completed for example problems of false alarms are likely to occur after commissioning unless cleaning of the sensor is undertaken At commissioning the dust cover should be removed and discarded NOTE THE PLASTIC DUST COVER MUST BE REMOVED FROM THE SENSOR IN ORDER FOR THESENSORTOFUNCTIONCORRECTLY Section 6 MAINTENANCE AND CLEANING Maintenance The ST P AS sensor is a high qua...

Страница 4: ...move the optic chamber by gently twisting in an anticlockwisemovement DO NOT DISMANTLE ANY FURTHER iv Examine the optic chamber and the optic s bridge and check for any dust or dirt which may give cause for false alarm If the sensor is very dirty damaged or corroded please return the complete detector to Nittan for service v If the parts of the sensor are still serviceable proceed to clean the out...

Страница 5: ... C to 50 Deg C Section 8 ENVIRONMENTAL PARAMETERS TemperatureConsiderations Over the range from 10 deg C to 50 deg C Humidity Relative Humidity of up to 90 measured at 50 deg C non condensing Section 9 EMC Installation The installation shall be in accordance with the regulations either of the approval body for an approved system or otherwise to the national code of practice regulations for the ins...

Страница 6: ...correctly read Set each digit on the appropriate eight switches according to the address required 64 8 16 32 4 1 On 2 On 128 Rear of ST P AS Sensor and Address Switch Setting DIL Switch Above switch setting set to address 12 decimal Off Off 64 8 16 32 4 1 On 2 On 128 Above switch setting set to address 26 decimal Off Off 64 8 16 32 4 1 On 2 On 128 Above switch setting set to address 95 decimal Off...

Страница 7: ...UCTION MANUAL MARCH 2001 15mm 35mm 104mm NOTE Clear LED denotes Photoelectric sensor Section 11 CONNECTIONS Also suitable for ST I AS and ST H AS sensors Section 12 DIMENSIONS STB 4 base _ 6 5 3 3 6 5 6 3 5 1 1 STB 4 base LED 1 STB 4 base SIG S Low current LED 3mA max STA R1 loop return to control panel ...

Страница 8: ...D HipleyStreet Old Woking Surrey England GU22 9LQ United Kingdom Tel 44 0 1483 769555 Fax 44 0 1483 756686 WebSite www nittan co uk e mail sales nittan co uk Quality System Certificate No 041 Assessed to BS EN ISO 9002 ST P AS ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE SENSOR INSTRUCTION MANUAL LPCB REF 041c 09 ...

Отзывы: