Technical Manual: EV-UV - 000023 (Changes are subject to DCRN)
12
FIG. 7.
Section 15 - FLAMEPROOF
HOUSING
The EV-UV detector may also be used with the NITTAN NFD-FPH
Flameproof housing. The NFD-FPH is for use in areas made
potentially hazardous by the presence of flammable liquids or
vapours (zone 1 or zone 2).
The housing has a threaded cover to enable ease of access for
installation and includes internal and external earth terminals
suitable for up to 4mm sq. cable. The EV-UV, when installed in the
NFD-FPH, requires a special bracket and base inside the housing to
enable correct mounting of the flame detector - this is included in
the housing.
Fig. 7.
(below) is a diagram of the housing.
Flameproof Housing Specifications:
Model Reference:
- NFD-FPH
Computer Reference:
- F07N*63542
Body & Cover
- Copper free aluminium (Chromate primed
polyester powder coated)
Locking Screw
- Steel zinc plated
Window
- Heat resistant quartz glass
IP Rating
- I.P.66
Cable Entries
- 2 x M20 (1.5mm pitch)
Weight
- 2.3 Kgs
Standards:
CENELEC
EN 50014/50018 & NBM C23.001/103
INIEX
ATEX Approved to II 2 G D, EExd IIC T6 (85 ºC)
• Ref No: NISM/EV-UV/01 • Date: 16.04.09 • Issue: 1
• evolution advanced • EV-UV • analogue addressable ultraviolet flame sensor
instruction manual