background image

DW1401995  Rev.K2 

Feb 28, 2020 

Class A 

Connect  Listed  synchronization  module  EVCA-AP-SMD10  for  the 

synchronization of NAC devices. 

Lin+
Lin-
Lout+
Lout-

Loop

-          +

TO NEXT

DEVICE

R-

R+

S+
S-

I+
I-

+O

U

T

P

U

T

1

EVCA-AP-SMD10

+I

N

P

U

T

1

-G

N

D

1

+O

U

T

P

U

T

2

+I

N

P

U

T

2

-G

N

D

2

S

Y

N

C

+

S

Y

N

C

-

H

+IN

H

-IN

+

-

NAC

device

UL LISTED 1481 24 VDC POWER SUPPLY 
ISOLATED, REGULATED,
POWER LIMITED PER N FPA 70, LISTED  
FOR FIRE PROTECTION WITH BATTERY 
BACKUP.

Note: For Class A wiring, power supply 
connections shall be made within 20 ft(6.1m) 
and enclosed within conduit or equivalently 
protected against mechanical injury.

+

-

NAC

device

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Use for horn only

 

Figure 4 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class B 

EOL (10k ohm) is connected between S+ and S- in EVA-SCM-SCI. 

Refer to Figure 5 for wiring. 

Connect  Listed  synchronization  module  EVCA-AP-SMD10  for  the 

synchronization of NAC devices.   

Lin+
Lin-
Lout+
Lout-

Loop

-          +

TO NEXT

DEVICE

R-

R+

S+
S-

I+
I-

+

O

U

T

P

U

T

1

EVCA-AP-SMD10

+

IN

P

U

T

1

-

G

N

D

1

+

O

U

T

P

U

T

2

+

IN

P

U

T

2

-

G

N

D

2

S

Y

N

C

+

S

Y

N

C

-

H

+

IN

H

-

IN

+

-

NAC

device

UL LISTED 1481 24 VDC POWER SUPPLY 
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70, LISTED 
FOR FIRE PROTECTION WITH BATTERY 

BACKUP.

+

-

NAC

device

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Use for horn only

EOL 

10kΩ

(RE-10k)

Figure 5 

Maintenance 

Routine inspection: Ensure the module is secure and undamaged. 

 

Operation Test 

The purpose of the Operational Test is to confirm the product’s correct 

operation. 

1)

 

When  carrying  out  site  testing  of  the  product,  the  control  panel 

shall be set to “one-man-walk test mode” prior to the test. 

2)

 

Take any necessary precautions to limit the sounding of the alarm 

sounders/bells and any fire service summoning device. 

3)

 

Operate  a  control  signal  from  the  control  panel  to  activate  NAC 

devices, and confirm that the Output LED (red) illuminates. 

Note: If the test cannot be carried out as terminal wiring is connected, 

remove the wire connected to NAC, and test between terminal S+ and   

S-

or  R+  and  R-

to  check  the  module.  (In  the  active  status,  24V  is 

output between S+ and S- (or between R+ and R-). 

 

Отзывы: