DW1401995 Rev.K2
Feb 28, 2020
3
Class A
Connect Listed synchronization module EVCA-AP-SMD10 for the
synchronization of NAC devices.
Lin+
Lin-
Lout+
Lout-
Loop
- +
TO NEXT
DEVICE
R-
R+
S+
S-
I+
I-
+O
U
T
P
U
T
1
EVCA-AP-SMD10
+I
N
P
U
T
1
-G
N
D
1
+O
U
T
P
U
T
2
+I
N
P
U
T
2
-G
N
D
2
S
Y
N
C
+
S
Y
N
C
-
H
+IN
H
-IN
+
-
NAC
device
UL LISTED 1481 24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER N FPA 70, LISTED
FOR FIRE PROTECTION WITH BATTERY
BACKUP.
Note: For Class A wiring, power supply
connections shall be made within 20 ft(6.1m)
and enclosed within conduit or equivalently
protected against mechanical injury.
+
-
NAC
device
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Use for horn only
Figure 4
Class B
EOL (10k ohm) is connected between S+ and S- in EVA-SCM-SCI.
Refer to Figure 5 for wiring.
Connect Listed synchronization module EVCA-AP-SMD10 for the
synchronization of NAC devices.
Lin+
Lin-
Lout+
Lout-
Loop
- +
TO NEXT
DEVICE
R-
R+
S+
S-
I+
I-
+
O
U
T
P
U
T
1
EVCA-AP-SMD10
+
IN
P
U
T
1
-
G
N
D
1
+
O
U
T
P
U
T
2
+
IN
P
U
T
2
-
G
N
D
2
S
Y
N
C
+
S
Y
N
C
-
H
+
IN
H
-
IN
+
-
NAC
device
UL LISTED 1481 24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70, LISTED
FOR FIRE PROTECTION WITH BATTERY
BACKUP.
+
-
NAC
device
- +
Loop
FROM PANEL OR
PREVIOUS DEVICE
Use for horn only
EOL
10kΩ
(RE-10k)
Figure 5
Maintenance
Routine inspection: Ensure the module is secure and undamaged.
Operation Test
The purpose of the Operational Test is to confirm the product’s correct
operation.
1)
When carrying out site testing of the product, the control panel
shall be set to “one-man-walk test mode” prior to the test.
2)
Take any necessary precautions to limit the sounding of the alarm
sounders/bells and any fire service summoning device.
3)
Operate a control signal from the control panel to activate NAC
devices, and confirm that the Output LED (red) illuminates.
Note: If the test cannot be carried out as terminal wiring is connected,
remove the wire connected to NAC, and test between terminal S+ and
S-
(
or R+ and R-
)
to check the module. (In the active status, 24V is
output between S+ and S- (or between R+ and R-).