Compatibility Requirement 

To ensure proper operation, the module shall be connected to UL listed 

control panel NFU-7000 series. 

 

Before Installing 

Disconnect power to the control panel before installing the module. 

If the module is installed in an existing operational system, inform the 

operators and local authorities that the system will be temporarily out 

of service. 

 

Mounting 

Mount the module directly to 4’’ square electrical box (UL Listed). 

Secure the module to the electrical box, as shown in Figure 3. 

Main unit

Outer cover EVA

Electrical box

Tapping screw

Pan head screw

Figure 3 

Address Setting 

Use EVA-AD2 Programmer for setting the address of the module prior 

to  installation.  EVA-SCM-SCI  has  an  address  given  at  random  from 

factory.  Connect  the  Programmer  with  the  address  setting  port  to 

change  the  address  to  any  of  1-254  (dec),  with  reference  to  the 

instruction  manual  of  EVA-AD2  Programmer.  The  address  can  be  set 

regardless of whether power supply from the control panel is turned on 

or  off.  During  setting  address,  the  module  does  not  respond  to  the 

control panel.   

Set the address of module according to Job data. 

 

Wiring 

All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 

regulations.   

Install  module  wiring  in  accordance  with  the  appropriate  wiring 

diagrams.   

 
 
 
 
 
 

Note: All wiring is power-limited and supervised. 

 

Refer to the following table for listed NAC devices to be connected. 

The number of NAC devices that can be connected varies depending on 

settings,  but  shall  not  exceed  14  devices.  Please  refer  to  the 

specifications  of  NAC  devices  for  the  consumption  current  and  DIP 

switch  setting.  Select  the  “temporal”  tone  in  each  NAC  device  for  a 

standard evacuation pattern.   

Do not exceed the maximum current rating 2A and 14 maximum number 
of NAC devices

.

CAUTION

!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Name

 

Manufacturer

 

Description

 

EVCA-AP-H

 

NITTAN

 

Horn

 

EVCA-AP-S

 

NITTAN

 

Strobe

 

EVCA-AP-SH

 

NITTAN

 

Horn & strobe

 

EVCA-AP-SWP

 

NITTAN

 

Waterproof Horn

 

EVCA-AP-SHWP

 

NITTAN

 

Waterproof Horn & strobe

 

Use cable AWG12-22 for wiring. Do not connect different gauge cables 
at one terminal in order to prevent loosening. Use a fork terminal for 
crimping two cables. 

CAUTION

!

Do not connect cables in reverse polarity. Failure to connect the polarity 
correctly could result in damage to the module and/or other equipment.

CAUTION

!