DW1401995  Rev.K2 

Feb 28, 2020 

Instruction  Manual

           

   

                   

 

EVA-SCM-SCI    Sounder Control Module

                                         

Before Installation 

Please read these instructions carefully and keep for future reference.   

The  information  in  this  document  is  subject  to change  without notice. 

For updates please refer to our website. 

 

 

 
 
 
 
 
 

Note

: 

Follow  the  requirements  for  the  installation  of  the  product  in 

accordance with the Specifications. Otherwise it may cause malfunction.

 

Note

: 

Do  not  install  the  product  in  any  location  where  oil,  dust,  iron 

powder, chemicals, or hydrogen sulphide may occur or affect the product. 

It may cause malfunction.

   

 

This package contains the following items: 

Main  unit 

…………………………………………………………………

Outer  cover  EVA 

…………………………………………………………

Instruction  Manual

  ……………………………………………………

Tapping  screw 

……………………………………………………………

Pan  head  screw   

…………………………………………………………

EOL  Resister  (RE-10k) 

…………………………………………………

 

General Description 

EVA-SCM-SCI  Sounder  Control  Module  with  Short  Circuit  Isolator  is 

an  output  module  intended  for  use  in  addressable  two  wire  systems, 

which  provides  the  control  of  NAC  (Notification  Appliance  Circuit) 

devices. The Notification Appliance Circuit can be wired on Class A and 

Class B.   

 

General Operation 

Normal  standby condition:  The module  receives  polling  from  a control 

panel at the regular interval. Polling LED (green) flashes. 

Active condition: When receiving a control signal from the control panel, 

the module operates NAC devices, and Output LED (red) illuminates. 

Trouble condition: If an overcurrent occurs because SLC (Signaling Line 

Circuit)  is  shorted,  SCI  LED  (yellow)  illuminates,  and  the  module 

communicates  to  the  control  panel  the  short  status.  The  module  also 

communicates to the control panel the open/short status of NAC. 

 

SCI (short circuit isolator) Function 

The  module  has  a  built-in  short  circuit  isolator.  SCI  circuit  prevents 

entire loop failure in the event of a short between L+ and L- on the loop. 

If  a  short  is  detected  between  L+  and  L-,  the  yellow LED  indicator  is 

illuminated.  The  line  between  Lin-  and  Lout-  is  disconnected 

automatically  to  isolate  the  short  circuit,  and  short  circuit  status  is 

communicated to the control panel. Upon removal of the short condition, 

the module will automatically connect between Lin- and Lout- to restore 

the entire loop to the normal operating status. 

 

Polling LED (GREEN)

Output LED (RED)

SCI LED (YELLOW)

Address Setting Port

 

Figure 1 

 

 

 

 

 

 

 

 

 

 

Figure 2 

 

 

 

NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN

 

http://www.nittan.com

 

Make  sure  to  turn  the  power  off  before  commencing  any  wiring  work. 

Otherwise it may cause electric shock or damage to equipment.

CAUTION

!

Do not use the products outside the rated power supply voltage range 
specified in the Specifications. It may cause a fire or damage to 
equipment.

CAUTION

!

Do not disassemble, repair, or modify the products. It may cause a fire or 
electric shock.

CAUTION

!