Manual: EV-PYS Manual 000028 (Changes are subject to DCRN)
7
• Ref No: NISM/EV-PYS/02 • 19.02.19 • Issue: 2
• Evolution • EV-PYS • analogue addressable photoelectric sensor with integral sounder
Section 7 - ENVIRONMENTAL
PARAMETERS
Temperature Considerations:
Over the range from -10 ºC to +55 ºC
Humidity:
Relative Humidity of up to 95%, measured at 50 ºC,
non condensing.
Section 8 - EMC
Installation
The installation shall be in accordance with the regulations either
of the approval body for an approved system, or otherwise, to the
national code of practice/ regulations for the installation of the fire
alarm system, e.g. BS 5839 part 1.
Electromagnetic Compatibility (EMC)
On a site where there is an unusually high level of potential
electrical interference, e.g. where heavy currents are being
switched or where high levels of R.F. are prevalent, care then must
be taken in the type and routing of cables. Particular care should
be given to the separation of zone wiring from the cable carrying
the interference.
Section 6 - SPECIFICATIONS
Model Reference:
- EV-PYS
EV-PYS-DSCI
Computer Reference:
- F20-82510
F20-82511
Sensor Type:
- Photoelectric smoke sensor
Sensitivity:
- Nominal 4.5%/m
Operating Current:
- 200 microamps
fire alarm (LED on) 5.2mA
Sounder on 3.5 mA
RIL 2mA
Standard:
- EN54 Part 7:2001 A2
EN54 Part 3:2001
EN54 Part 17:2005
Mass:
- 145g (excluding base)
Charging Time:
- 1 minute
Ambient Temperature
Range:
- -10 ºC to +55 ºC
IP Rating:
- 42C
Sounder Type
- Type A Indoor
Sounder Device
- Piezo
Power Consumption
- 150mW Max (Sounder)
Sounder Output
- 77 - 88db (A-weighted)
Directional Dependent
Sounder Tones
- Standard two tone 750Hz/1000Hz
0.5/0.5sec Only
Other tone models available
on request
CPR Certificate
- 0359-CPR-00640
Declaration of
- 00640
Performance