6. Operation

6. Operation

.33.

.32.

Maintenance or replacement could clear or cause a different value of total energy. Use this 

function could allow user to revise the value of total energy to the same value as before. If 

the monitoring website is used the data will be synchronous with this setting automatically. 

(see Figure 6.20).

Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the 

ENTER key to execute the setting. Press the ESC key to return to the previous menu. 

6.5.6 Calibrate Energy

Figure 6.20 Calibrate energy

YES=<ENT> NO=<ESC>

Energy:0000000kWh

6.5.7 Special Settings

This

 

functions is applicable by maintenance personnel only, wrong 

operation will prevent the inverter from working properly.

6.5.8 STD. Mode Settings

This sub menu is enabled when the grid standard is set to AS4777. To comply with New AUS/

NZ 4777.2, Solis 4G inverter could set different work mode to work with different

grid requirement. 

There are 6 work mode in working mode submenu.

1.NULL     2.Volt-watt     3.Volt-var     4.Fixed-PF     5.Reac-power     6.Power-PF

There are 5 setting under STD. Mode settings.

1. Working mode     2. Power Rate limit    3. Freq. Derate set    4. 10mins OV-G-V set.

5.Initial Settings

The parameter in each model could be set as below:

This

 

functions is applicable by maintenance personnel only, wrong 

operation will prevent the inverter from working properly.

1. NULL(default)

Inverter not under any of below working mode.

The default setting of working mode is NULL.

2. Volt-Watt

Set Voltage1: 207-220V, Default 207V

Set P_Limit1: 20%-100%, Default 100%

Set Voltage2: 216-230V, Default 220V

Set P_Limit2: 20%-100%, Default 100%

Set Voltage3: 235-255V, Default 250V

Set P_Limit3: 20%-100%, Default 100%

Set Voltage4: 244-265V, Default 255V

Set P_Limit4: 20%-100%, Default 100%

3. Volt-Var

Set Voltage1: 207-220V, Default 207V

Set Voltage2: 216-230V, Default 220V

Set Voltage3: 235-255V, Default 250V

Set Voltage4: 244-265V, Default 255V

Set Leading: 0~+60%, D30%

Set Lagging: 0~-60%, Default -30%

6. Power-PF

Set Pb_Limit: 0-100%, Default 25%

Pc_Limit: 0-100%, Default 50%

Pc_Factor:  (-0.8, +0.8), Default -0.95

4. Fixed PF

Set PF (-0.8, +0.8), Default 1, Resolution 0.01.

 

5. Reac. Power

Set reacive power (0, 60%), Default 0, Resolution 1%.

Содержание Solis 4G Mini

Страница 1: ...Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we...

Страница 2: ...6 Operation 24 5 Start Stop 5 1 Start the Inverter 5 2 Stop the Inverter 23 23 23 1 1 Product Description 3 1 2 Packaging 4 4 3 1 Connect PV side of inverter 13 4 3 2 Connect grid side of inverter 16...

Страница 3: ...6 4 2 Running Message 28 32 6 5 3 Clear Energy 6 5 4 Reset Password 31 31 6 4 6 Daily Record 6 4 7 Communication Data 29 29 6 5 5 Power Control 6 5 6 Calibrate Energy 31 32 6 5 7 Special Settings 6 5...

Страница 4: ...ety Symbols Safety symbols used in this manual which highlight potential safety risks and important safety information are listed as follows WARNING WARNING symbol indicates important safety instructi...

Страница 5: ...Main Switch AC must be switched off before the solar panel s DC isolator shall be switched off 6 CAUTION The PV array Solar panels supplies a DC voltage when they are exposed to sunlight CAUTION Risk...

Страница 6: ...t indications 8 Figure 4 1 Recommended Installation locations To select a location for the inverter the following criteria should be considered To avoid over heating ambient air temperature must be co...

Страница 7: ...nverters are installed in one location a minimum 12inchs clearance should be kept between each inverter or other object The bottom of the inverter should be 20inchs clearance to the ground Visibility...

Страница 8: ...0 4G Solis mini 3600 4G Solis mini 1000 4G LV Please don t connect PV array positive or negative pole to the ground it could cause serious damages to the inverter Figure 4 6 DC Connector Figure 4 7 DC...

Страница 9: ...nnector cap nut and contact pin Figure 4 8 Disassemble the Connector Cap nut Figure 4 9 Insert the Wire into the Connector Cap nut and contact pin iii Crimp the contact pin to the wire using a proper...

Страница 10: ...semble the AC grid terminal connectors are listed as follows a Disassemble the AC connector Strip the AC wires about 6mm Figure 4 15 Stripped AC Wires c Tighten up the cap on the terminal see Figure 4...

Страница 11: ...l connector to the inverter Small click will confirm connection Figure 4 18 Connect the AC Connector to the Inverter The inverter can be monitored via Wi Fi or GPRS All Solis communication devices are...

Страница 12: ...lease set the corresponding configuration as sections 6 5 11 1 2 and 6 5 11 1 3 1 5 6 7 8 MENU 1600 imp kWh 220V 10 60 A T1 T2 T3 DDSD1352 L N L N Communication Figure 4 22 Meter in Load Grid Load A B...

Страница 13: ...Inverter the following steps must be strictly followed 1 Switch the Supply Main Switch AC OFF 2 Wait 30 seconds Switch the DC Switch OFF All the LEDs of the inverter will be off in one minute 5 Start...

Страница 14: ...ormation list Inverter SN 00000000000000 Export_P 0000W Export_I 00 0A 10 sec 10 sec Display series number of the inverter Power of ERM Current of EPM 10 sec Work Mode The work mode of inverter DRM Nu...

Страница 15: ...word the Main Menu will display a screen and be able to access to the following information 1 Alarm Message 2 Running Message 3 Version 4 Daily Energy 5 Monthly Energy 6 Yearly Energy 7 Daily Record 8...

Страница 16: ...reen shows the internal data of the Inverter see Figure 6 14 which is for service technicians only 01 05 01 25 E4 9D AA 06 10 C2 B5 E4 9D 55 Figure 6 14 Communication Data Press DOWN key to move the c...

Страница 17: ...OTE This function is for technicians use only Press the UP DOWN keys to select the standard AS4777 02 AS4777 15 VDE4105 VDE0126 UL 240V A UL 208V A UL 240V UL 208V MEX CFE G83 2 for 1 3 6kW models G59...

Страница 18: ...u 1 NULL 2 Volt watt 3 Volt var 4 Fixed PF 5 Reac power 6 Power PF There are 5 setting under STD Mode settings 1 Working mode 2 Power Rate limit 3 Freq Derate set 4 10mins OV G V set 5 Initial Setting...

Страница 19: ...o default 6 5 10 HMI Update This function is used for update the LCD program This function is applicable by maintenance personnel only wrong operation will prevent the inverter from reaching maximum p...

Страница 20: ...ore than 500W Correct means CT has been connected correctly Before pressing the CT Link Test menu please check as follow 1 Load power 500W 2 Inverter should be set Grid Off 3 CT should be connected 4...

Страница 21: ...igned in accordance with the most important international grid tied standards and safety and electromagnetic compatibility requirements Before delivering to the customer the inverter has been subjecte...

Страница 22: ...staller UN G V01 02 DC INTF DC input overcurrent 1 Restart inverter 2 Identify and remove the string to the fault MPPT 2 Change power board IGFOL F Grid current tracking fail OV G I Over grid current...

Страница 23: ...t rated output power 1 5 42 43 50 550 Start up voltage Volts 60 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT numb...

Страница 24: ...voltage Volts 60 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage...

Страница 25: ...voltage Volts 90 Max short circuit input current Amps 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage...

Страница 26: ...Volts 90 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number M...

Страница 27: ......

Отзывы: