DOMESTIC
WATER
Geothermal heat pump JVP is designed for HEATING
For SHW it should only be used as back-up or as preheating
HEATING
OFF
Heat source selection for domestic water production
[OFF, HP, AUX, HP+AUX]
MINIMUM
35
°C
Temperature setting for auxiliary heating (if released and selected)
[5..80]
SETTING
45
°C
Temperature setting for heat pump compressor
[5..60]
NEUTRAL
ZONE
4
°C
Dead time for connecting. Heating starts at setting minus this value
[1..9]
CP CAP
60
%
Compressor capacity during domestic hot water production. (Factory setting 60 %)
LEGIO
DAYS
OFF
Legionella function frequency (auxiliary heating must be released for operation)
[OFF, 7..30] days
CENTRAL
HEAT
CTR HEAT
HP+AUX
Heat source selection for room heating
[OFF, HP, AUX, HP+AUX]
T HEAT
MIN
35
°C
Setpoint of the housing central heating temperature and setpoint-heating [5 0.60].
Recommended central heating temperature is 30 ° C to 45 ° C. By TEMP CTR, AMB
COMP will restrict the central heating temperature, downwards, and must therefore
be adjusted the curve.
T HEAT
MAX
45
°C
The maximum permitted setpoint for the building central heating temperature
[5 0.60] By TEMP CTR, AMB COMP will restrict the central heating temperature up
to MAX
NEUTRAL
ZONE
3
°C
Dead time for connecting. Heating starts at setting minus this value
[1..9]
TEMPCTRL
MIN
Central heating temperature control function
[MIN, OUT COMP]
CURVE
SELECT
5
Outside temperature compensation curve (Curve Menus displayed if selected under
CONTROL)
[DEF, 1..10]
CURVE
+/-
0
°C
Raises or lowers the calculated curve setting a fixed value (°C)
[-9..9]
CURVE -
20
DEF
50
°C
Manually-selected five-interval out/in curve (at -20, -10, 0, 10 and 20 °C) for central
heating temperature [5..60]
CURVE -
10
DEF
45
°C
CURVE 0
DEF
40
°C
CURVE+10
DEF
35
°C
CURVE+20
DEF
30
°C
Parameters menu, DOMESTIC WATER and CENTRAL HEAT needs to be set by authorized ser-
vice personnel
Parameters in gray boxes changed as required, while the other parameters should not be changed
* Version 1.09 displayed T HEAT as T RETUR