Restart
FIRE ALARM acknowledgement
Fire alarm (code 3) can be acknowledged automatically via
SERVICE
-
RESTART FIRE ALARM
menu:
[OFF, FIRE].
Fire alarms can be acknowledged automatically during fire drills and tests. This requires that the fire
thermostat input has returned to normal (closed contact).
Service / Restart
↳
Restart
Settings:
Standard setting:
Description:
Off / HP/LP / Continuous / Fire
Off
HP/LP: High pressure alarm/ Low pressure alarm.
Restarts automatically.
Continuous: Continuous operation after the second
Critical Alarm.
Fire: Automatic acknowledgement when fire input is
back to normal.
Restore settings
It is possible to restore factory and Back-up settings.
Service / Restore settings
↳
Restore settings
Settings:
Standard setting:
Description:
Off / Factory / Back-up / Restore
Off
Factory: Restores factory settings.
Back-up: Here you can Back-up. When you have
Backed-up, the Restore menu appears allowing you to
restore the Back-up of the selected settings.