Read the complete manual before carrying out the installation and activating the system. Keep the 
manual for future reference.

1. DESCRIPTION 

The 

presence or absence detector 360° (slave) for surface mounting on high ceilings

 consists of an 

integral unit with on-off control of one channel and a motion sensor (PIR or passive infrared technology).

You will use this device in combination with a master (350-20080) to increase the detection area (see section 
4.2.).

The slave will control the lighting according to the parameters set on the master. For more information, please 
refer to the manual supplied with the master.

2. INSTALLATION

2.1. Connection
Danger

Disconnect all power before installing the detector. Do not connect the device to the mains voltage 

until installation has been completed.

Refer to the wiring diagram (fig. 1).

2.2. Mounting
Tip

:

 Do not install the detector in the vicinity of heat sources such as stoves or electric heaters, air currents 

(ventilation systems) or any moving objects (fig. 2). This can activate the device unnecessarily as it reacts to 
motion and heat in its surroundings. If the detector is installed in warehouses where closed trucks are used,  
its operation may be less than optimal due to temperature differences that are too small.

Tip

:

 The recommended mounting height is 4 to 8 m. At this height, the detector has a range with a diameter 

of 16 to 32 m on the ground (fig. 3).

The detector is suited for direct mounting on high ceilings (fig. 4).

At delivery, the cover mask is mounted on the detector (see also section 4.2.).

3. SETTINGS

3.1. DIP switches

Using the two DIP switches you set the 

sensitivity of the motion sensor

. You can choose from the following 

options: minimum, low, high or maximum. Refer to figure 5 for the position of the DIP switches depending on 
the desired sensitivity.

At delivery the motion sensor of this detector is set at the high sensitivity mode.

3.2. Potentiometer

Contrary to the master, the housing of the slave includes only one potentiometer with one single function, i.e. 
activating the walking test (fig. 6).

The detection area is tested by activating the integrated motion sensor for 

the walking test

:

1. Set the potentiometer to the minimum value.
 

The blue indication LED lights up when you activate the test mode.

 

The lighting is switched on for five seconds and the red indication LED lights up each time the sensor 
detects activity. If no activity is detected and the sensor is still in test mode, the blue indication LED lights 
up.

2. Set the potentiometer back to the middle value as soon as the walking test is completed.  
 

If you forget to close the test mode, the detector will return to the selected settings after five minutes.

4. OPERATION AND USE

4.1. Activation

The detector should not be powered until all cables are connected. After powering the device, the detector will 
be ready for use after approximately 40 seconds (warm-up time).

The red indication LED flashes during warm-up time. After the device has warmed up, the green indication 
LED will flash briefly twice.

4.2. Detection range

The detection area can be increased by adding an extra detector (slave) (350-20081). A maximum of ten 
slaves can be connected to one master (350-20080). The lighting is operated in accordance with the settings 
on the master. Both the master and the slave have the same detection range (a circle with a diameter of 16 
to 32 m). When covering a complete area using several detectors, it is recommended to take into account an 
overlap of approximately 30% (fig. 7).

If you would like to exclude motion detection in a portion of the detection area or if the detection area is too 
large, you cover the sensor lens using the cover mask supplied. This allows you to reduce the maximum range 
to 32 m. The 360° detection angle can be reduced in steps of 30°.

5.

 

MAINTENANCE

Dirt may prevent the detector from functioning properly. Therefore, always keep the lens clean and dry. Use a 
damp cloth and water with some detergent to clean the lens. Never exert pressure to wipe the lens clean. If 
the lens or other parts of the detector are defective, please contact an authorised installer.

6. TECHNICAL DATA

dimensions

45.9 x 117.3 mm (HxW)
64.1 x 117.3 mm (HxW) (including non-visible part)

power supply voltage

230 Vac ± 10%, 50 Hz

power consumption

0,2 W

mounting height (fig. 3)

4 – 8 m

detection angle (fig. 3)

360°

detection range (fig. 3)

circular, 16 – 32 m

wire input

3 x 2,5 mm²

cable inlet

on the side: 3 x Ø 14 mm
on the top: 2 x Ø 14 mm

protection degree

IP54

protection class

class I devices

ambient temperature

-5 – +50°C

quality mark

CE marked in compliance with EN 60669-2-1

accessories

presence or absence detector 360° (master) (350-20080)

7. WARNINGS REGARDING INSTALLATION

 -The installation should be carried out by a registered installer and in compliance with the statutory regulations.
 -This user manual should be presented to the user. It should be included in the electrical installation file, and 

it should be passed on to any new owners. Additional copies are available on the Niko website or via the Niko 
support service.

 -During installation, the following should be taken into account (non-exhaustive list):

 

- the statutory laws, standards and regulations.

 

- the technology currently available at the time of installation.

 

- this user manual, which only states general regulations and should therefore be read within the scope of 

each specific installation.

 

- the rules of proper workmanship.

  

This product complies with all of the relevant European guidelines and regulations. If applicable, you can find 

the EC declaration of conformity regarding this product at www.niko.eu.

8. NIKO SUPPORT

In case of doubt or for the specific exchange procedure in case of a possible defect, contact the Niko support 

service in Belgium at +32 3 778 90 80 or your wholesaler/installer. Contact details and more information can 

be found at www.niko.eu under the “Help and advice” section.

9. GUARANTEE PROVISIONS

 -The period of guarantee is four years from the date of delivery. The delivery date is the invoice date of purchase 

of the product by the consumer. If there is no invoice, the date of production applies.

 -The consumer is obliged to inform Niko in writing about the non-conformity, within two months after stating 

the defect.

 -In case of a non-conformity, the consumer only has the right to a product repair or replacement free of charge, 

which shall be decided by Niko.

 -Niko shall not be held liable for a defect or damage resulting from incorrect installation, improper or careless 

use, incorrect operation, transformation of the product, maintenance that does not adhere to the maintenance 
instructions or an external cause, such as damage due to moisture or overvoltage.

 -The compulsory regulations of the national legislation concerning the sale of consumer goods and the 

protection of the consumer in the countries where Niko sells, directly or via sister companies, subsidiaries, 
chain stores, distributors, agents or permanent sales representatives, take priority over the above-mentioned 
rules and regulations.

Содержание 350-20081

Страница 1: ...vlak te beslaan met meerdere melders wordt het aanbevolen rekening te houden met een overlap van ongeveer 30 fig 7 Als je in een deel van het detectiegebied geen bewegingsdetectie wilt of als het dete...

Страница 2: ...ve poss dent la m me port e de d tection cercle de 16 32 m de diam tre Pour couvrir une surface compl te au moyen de plusieurs d tecteurs il est conseill de tenir compte d un chevauchement d environ 3...

Страница 3: ...ereich Kreis eines Durchmessers von 16 bis 32 m Um eine Fl che vollst ndig mit mehreren Meldern zu erfassen wird eine berlappung des Erfassungsbereichs von circa 30 empfohlen Abb 7 Wenn Sie in einem b...

Страница 4: ...ection range a circle with a diameter of 16 to 32 m When covering a complete area using several detectors it is recommended to take into account an overlap of approximately 30 fig 7 If you would like...

Страница 5: ...ktorov typu slave Osvetlenie bude ovl dan v z vislosti od nastavenia na detektore typu master Detektory typu master a slave maj rovnak oblas sn mania kruh s priemerom 16 a 32 m Pre dosiahnutie pln ho...

Страница 6: ...1 N N N 1 1 350 20081 slave L1 L1 L1 L1 N N N T1 S T1 S T1 S H A B C D E F 4 m 0 20 0 03 m 2 00 3 1 m 3 70 10 8 m 6 50 33 2 m 11 00 95 m 16 00 201 m 8 m 0 50 0 20 m 4 00 12 6 m 7 50 44 2 m 14 00 154 m...

Страница 7: ...E 9100 Sint Niklaas Belgium tel 32 3 778 90 00 fax 32 3 777 71 20 e mail support niko be www niko eu 71 51 Fig Abb Obr 4 DIP switch Sensitivity On 1 Off 0 DIP 1 2 0 0 Min 0 1 Low 1 0 High Factory sett...

Страница 8: ...350 20081 8 nv Niko sa Industriepark West 40 BE 9100 Sint Niklaas Belgium tel 32 3 778 90 00 fax 32 3 777 71 20 e mail support niko be www niko eu PM350 20081R14135...

Отзывы: