background image

 

nv 

Niko

 sa    Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: [email protected] — www.niko.be 

PM005-00002R10111

05-000-02

Read the complete manual before attempting installation and activating the system.

1. DESCRIPTION

The switching module switches and controls wall outlets and other electrical devices by means of contactors. In 
push button mode together with the Niko range of push button dimmers, the module can also be used as a dim 
controller for light circuits. The switching modules operates both in centralized and decentralized installations 
(fig. 1 & 2) and fits into any DIN-rail distribution board (14U wide). The module has its own galvanically isolated 
power supply, a special output for the bus cable, a detection circuit, diagnosis functions, an EEPROM memory, 
programming keys, a micro processor, a LED interface, relays and indicators for all functions. The switching 
module is provided with 2 prewired, separated circuits with 1-pole relay output contacts (1x3 and 1x6 contacts). 
The module is provided with 3 separate output circuits 1 of which has a changeover contact (in total: 12 outputs). 
The module has a non-volatile memory. In case of a power cut, no battery is required. The memory can always 
be reprogrammed and exchanged without opening the module (EEPROM).

Attention:

 The changeover contact (output 6) is not suitable for control of fluorescent lamps with parallel 

compensation.

2. OPERATION AND USE

If more than 12 outputs are required, several modules can be connected in parallel. Take into account the bus 
polarity. Output B1 of the first module must be connected to output B1 of the second module. One of these 
modules takes over the power supply for the bus; the power supply of the other modules is automatically 
switched off. The different functions of the bus push buttons are programmed by means of the ‘mode’-key. On 
the output terminals, both the neutral conductor and the switched phase are available. After a power cut, the 
outputs that were activated before, are turned back on (with some time delay) in order to avoid current peaks. 
Every module can realize a LED feedback (for the LEDs of the bus push buttons) on three outputs (10, 11 and 
12). These LEDs are supplied via an external transformer. The feedback is not transmitted through the bus and 
requires two additional wires in the bus cable. The module is provided with 2 binary 230V~ inputs. These can 
be used both as ‘switch input’ and as ‘enable function input’.
In a three-phase connection, a separate phase may be used per circuit, but only with the same phase in one 
group.
The separate circuits/contacts L4, L5, L6 may not be used for the wiring of SELV circuits.

2.1. Start-up function

Briefly press the ‘select’ key in order to select the outputs manually. Press longer (>1s.) in order to temporarily 
switch on the output:

• if the bus is not yet installed;
• to control the outputs in case of a failure on the bus (short circuit or open circuit)
• to test or locate output circuits.

2.2. Diagnosis reporting

During normal operation (not during programming) there is continuous reporting on the ‘mode’-LEDs:
M1  lights when receiving a correct Nikobus telegram (blinks in case of wrong data)
M2  blinks in case of short circuit or bus polarization errors (e.g. exchange of bus polarity between 2 modules)
M3  blinks in case of errors of the bus power supply (bus supply circuit error)
M4  blinks in case of a memory communication error (e.g. EEPROM error) or when using a wrong type of module 

(e.g. memory of a shutter unit in a switching unit). 

2.3. External 230V~ inputs with ‘logical’ functions

The 230V~ inputs ‘A’ and ‘B’ can be used both as switch inputs and as ‘enable function inputs’.

2.3.1. Use as switch input

- The outputs react to the input changes, depending on the mode.
- The action is always carried out, independent of what is happening on the bus.
- These inputs signals take priority over the Nikobus telegram.
- After a power cut, the functions are carried out according to the input status.
These inputs can also be programmed by means of the logical ‘AND’ function. This way, outdoor lighting can 
e.g. be switched on when both the time switch and the twilight switch are ‘ON’.

2.3.2. Use as enable function

During programming, an additional condition can be given via an external 230V~ input. The action will either or 
not be carried out, depending on the status of the input. This way, a shutter can e.g. be controlled by means of 
a bus push button if a twighlight switch reports that it is dark.

2.4. Central functions with operating time (1 to 3s., for mode M2 and M3)

The operating time can be set between 1 and 3s. For security reasons an application can be e.g.: press 2s. on 
the bus push button in order to turn off all lights. Another application can be: assign several actions to one push 
button in function of the operating time.

2.5. Sequencer (mode M13)

Especially suitable for applications for which the load needs to be distributed due to capacity restrictions. E.g. lawn 
sprinkler system, nursery or greengrocery installation, controlled ventilation system. Also suitable for switching in 
sequences in nursery gardens for light sensitive plants in order to not turn on the full brightness at once.

2.6. Light atmospheres (mode M14 and M15)

You can set a number of outputs (e.g. lamps) ‘on’ or ‘off’ according to your personal choice. Press the ‘light 
atmosphere’ key long in order to save this light scene. Press the ‘light atmosphere’ key briefly in order to recall 
this light atmosphere. You can always modify the light atmosphere by programming a new setting and saving 
it in the memory by means of a long press on the ‘light atmosphere’ key. This way, the old light atmopshere is 
overwritten. Every bus push button as well as the external 230V~ inputs can be used as light atmosphere keys. 
By means of M14, a light atmosphere can only be switched on. Afterwards, every output is individually switched. 
By means of M15, a light atmosphere can be completely switched on or off.

3. TECHNICAL DATA

- Ambient operating temperature: 0° to 50°C
- Power supply switch module: 230V/5W
    2 terminals: 4 x 1,5mm

2

 or 2 x 2,5mm

2

 max. per terminal

- Mains supply: 230V/10A
    5 x 2 terminals: 4 x 1,5mm

2

 or 2 x 2,5mm

2

 max. per terminal

- Outputs: 230V/10A, 1 x 6 N.O. + 1 x 3 N.O. + 2 x N.O. + 1 x changeover = 12 outputs
    2 x 8 terminals: 4 x 1,5mm

2

 or 2 x 2,5mm

2

 max. per terminal

- Bus connection: 9V DC (SELV, safety extra low voltage)
    2 terminals: 2 x 1,5mm

2

 max. per terminal

- Output for lighting of the bus push buttons: via a separate power supply (bell transformer, 8 to 12V AC), the 

LED bus push buttons can be constantly lit or show the status of the outputs 10, 11 and 12. The switching 
unit is provided with 4 terminals for these LEDs (max. 2 x 1,5mm

2

 per terminal).

- 2 x 230V~ external inputs:
    3 terminals: max. 2 x 1,5mm

2

 or 1 x 2,5mm

2

 per terminal, 230V, 5mA, 2 inputs with common N

- Non-volatile EEPROM memory (2Kb)
- Dimensions: DIN-rail enclosure, 14U, H88 mm x W251 mm x D60mm

4. LEGAL WARNINGS

- The installation has to be carried out by a qualified person and in compliance with the statutory regulations.
- This user manual has to be handed over to the user. It has to be included in the electrical installation file and 

has to be passed on to any new owners. Additional copies are available on the Niko website or via the support 
service.

- During installation, the following has to be taken into account (not limited to list below):
  - The statutory laws, standards and regulations;
  - The state of the art technique at the moment of installation;
  - This user manual, which must be read within the scope of each specific installation, only states general 

regulations;

  - The rules of proper workmanship
- In case of questions, you can consult Niko’s support service or contact a registered control organisation.
  Support Belgium: 

Support UK:

  +32 3 778 90 80 

+44 1525877707

  website : http://www.niko.be 

http://www.nikouk.com

  e-mail: [email protected] 

[email protected]

In case of a defect, you can return your product to a registered Niko wholesaler, together with a clear description 
of your complaint (Conditions of use, stated defect…).

5. GUARANTEE PROVISIONS 

- Period of guarantee: 2 years from date of delivery. The delivery date is the invoice date of purchase of the 

product by the consumer. If there is no invoice, the date of production applies.

- The consumer is obliged to inform Niko in writing about the defect, within two months after stating the 

defect.

- In case of a failure to conform, the consumer has the right to a repair or replacement (decided by Niko) free 

of charge.

- Niko cannot be held liable for a defect or damage as a result of an incorrect installation, improper or careless 

use or wrong usage or transformation of the goods.

- The compulsory regulations of the national legislation concerning the sales of consumer goods and the protection 

of the consumers in the countries where Niko sells, directly or via sister or daughter companies, chain stores, 
distributors, agents or permanent sales representatives, take priority over the rules and regulations mentioned 
above.

Modes  Function 

Description 

Necessary control keys

Press the ‘mode’-key <1,6s. during programming in order to retrieve modes M1 to M8. The ‘mode’-LEDs light continuously.

M1: ........on/off ............................................................................................................................... top: on, bottom:off ....................................................................................................................................................2

M2: ........on (if necessary with operating time) ................................................................................. always on (centralized functions) ...............................................................................................................................1

M3: ........off (if necessary with operating time) ................................................................................. always off (centralized functions) ..............................................................................................................................1

M4: ........push button ...................................................................................................................... on for as long as the rocker is pressed (e.g. bell push button, dim control) max. 8s. ...................................................1

M5: ........toggle ............................................................................................................................... pulse ON / pulse OFF (e.g. toggle switch or teleruptor)...............................................................................................1

M6:........delayed off (longer times, up to 2h.)................................................................................... press: after certain time: off (e.g. staircase timer) .....................................................................................................1

M7: ........delayed on (longer times, up to 2h.) ................................................................................... press: after certain time: on (e.g. operating delay) .....................................................................................................1

M8:........blinking............................................................................................................................. press: on/off/on/…, turn off with M3 ........................................................................................................................1

Press the ‘mode’-key >1,6s. during programming in order to recall modes M11 to M15. The ‘mode’-LEDs blink.

M11: ......delayed off (shorter times, till 50s.) ................................................................................... as M6, but shorter times ..........................................................................................................................................1

M12: ......delayed on (shorter times, till 50s.) .................................................................................... as M7, but shorter times ...........................................................................................................................................1

M13: ......sequencer on/off...............................................................................................................  switching of several outputs subsequently via a time cycle  ......................................................................................2

 

 

The final switching order is determined during programming.

M14: ......light scene on ................................................................................................................... press short: recalling a certain light scene ................................................................................................................1

 

 

press long: stores the modified light scene in the memory (> 3s.)

M15: ......light scene on/off .............................................................................................................. press top rocker briefly: recall a certain light scene ...................................................................................................2

 

 

press top rocker long: save the modified light scene in the memory (> 3s.)

 

 

bottom key:  —> off

M16, 17, 18 have no function yet.

Modes M6, M7 and M13 

Modes M11 and M12 (short times): 

M2 and M3 (operating mode):

0  =   10s. 

 

 

 

 

 

 

0  =  0,5s. 

 

 

 

 

 

 

0  =  0s. 

1  =   1min. 

6  = 

6min. 

B  = 

30min. 

1  = 

1s. 

6  =  6s. 

B  =  20s. 

1  =  1s. 

2  =   2min. 

7  = 

7min. 

C  = 

45min. 

2  = 

2s. 

7  = 

7s. 

C  =  25s. 

2  =  2s. 

3  =   3min. 

8  = 

8min. 

D  = 

60min. 

3  = 

3s. 

8  =  8s. 

D  =  30s. 

3  =  3s. 

4  =   4min. 

9  = 

9min. 

E  = 

90min. 

4  = 

4s. 

9  =  9s. 

E  =  40s. 

4,...,F   =   0s. 

5  =   5min. 

A  =  15min. 

F  =  120min. 

5  = 

5s. 

A  =  15s. 

F  =  50s. 

Содержание 05-000-02

Страница 1: ...sfeertoets legt u deze sfeer vast Met een korte druk op de sfeertoets roept u de sfeer terug op U kunt deze sfeer altijd wijzigen door een nieuwe situatie in te stellen en deze in het geheugen op te slaan met een lange druk op de sfeertoets Op die manier wordt de oude sfeer overschreven Elke busdrukknop en de externe 230V ingangen mogen als sfeertoets gebruikt worden Met M14 kunt u een sfeer enkel...

Страница 2: ...R VERBRUIKERS 16A 10A L N T 40A 30mA 10A 10A 20A 20A K1 K2 230V B A Alarm of Telefooninterface 01 2 3 4 5 6 78 9 A B C E F N N N L N 10A 230V 50Hz 10A 230V 50Hz N 12 11 10 9 8 12 11 10 B A N B2 B1 0V 7 5 3 6 4 select mode bus feedback led program m 6 m 5 15 m 4 14 m 3 13 m 2 12 m 1 11 L4 L L5 L6 2 1 230V 50Hz 05 000 02 T1 230V set 6 m 7 m 8 18 01 2 3 4 5 6 78 9 A B C E F 01 2 3 4 5 6 78 9 A B C E ...

Страница 3: ...ambiances lumineuses en autorisant la commande ON marche OFF arrêt d un certain nombre de sorties p ex lampes Par une pression prolongée sur la touche d ambiance l ambiance est mise en mémoire Par une courte pression sur cette même touche elle est appelée L utilisateur peut ainsi créer une autre ambiance lumineuse et la mémoriser en appuyant longuement sur cette touche d ambiance Chaque bouton pou...

Страница 4: ...ODULE 3 16A 230V T 40A 300mA APPAREILS SALLE DE BAINS 16A 10A L N T 40A 30mA 10A 10A 20A 20A K1 K2 230V B A alarme ou interface téléphone 01 2 3 4 5 6 78 9 A B C E F N N N L N 10A 230V 50Hz 10A 230V 50Hz N 12 11 10 9 8 12 11 10 B A N B2 B1 0V 7 5 3 6 4 select mode bus feedback led program m 6 m 5 15 m 4 14 m 3 13 m 2 12 m 1 11 L4 L L5 L6 2 1 230V 50Hz 05 000 02 T1 230V set 6 m 7 m 8 18 01 2 3 4 5 ...

Страница 5: ...urch langes Drücken auf den Szenetaster wird die Lichtszene abgespeichert Durch kurzes Drücken auf den Szenetaster wird die Lichtszene wieder aufgerufen Sie können diese Lichtszene auch immer ändern durch langes Drücken auf den Szenetaster So wird die neue Lichtszene abspeichert und die alte überschrieben Jeder Bustaster wie auch die externen 230V Eingänge können als Szenetaster verwendet werden M...

Страница 6: ...ASTER und INTERFACES MODUL 3 16A 230V T 40A 300mA BADEZIMMER VERBRAUCHER 16A 10A L N T 40A 30mA 10A 10A 20A 20A K1 K2 230V B A Alarm oder Telefoninterface 01 2 3 4 5 6 78 9 A B C E F N N N L N 10A 230V 50Hz 10A 230V 50Hz N 12 11 10 9 8 12 11 10 B A N B2 B1 0V 7 5 3 6 4 select mode bus feedback led program m 6 m 5 15 m 4 14 m 3 13 m 2 12 m 1 11 L4 L L5 L6 2 1 230V 50Hz 05 000 02 T1 230V set 6 m 7 m...

Страница 7: ...s e g lamps on or off according to your personal choice Press the light atmosphere key long in order to save this light scene Press the light atmosphere key briefly in order to recall this light atmosphere You can always modify the light atmosphere by programming a new setting and saving it in the memory by means of a long press on the light atmosphere key This way the old light atmopshere is over...

Страница 8: ... 10A 10A 20A 20A K1 K2 230V B A Alarm or telephone interface 01 2 3 4 5 6 78 9 A B C E F N N N L N 10A 230V 50Hz 10A 230V 50Hz N 12 11 10 9 8 12 11 10 B A N B2 B1 0V 7 5 3 6 4 select mode bus feedback led program m 6 m 5 15 m 4 14 m 3 13 m 2 12 m 1 11 L4 L L5 L6 2 1 230V 50Hz 05 000 02 T1 230V set 6 m 7 m 8 18 01 2 3 4 5 6 78 9 A B C E F 01 2 3 4 5 6 78 9 A B C E F N N N L N 10A 230V 50Hz 10A 230V...

Отзывы: