6.3.6 Extended information
Bytes 10~73 report information from the soft starter’s internal registers.
Table 6-7 Internal register data
Byte
Description
Bits
Details
10-11
Version
0 to 5
Reserved
6 to 8
Product parameter list version
9 to 15 Product type code
1
12-13
Device details
14-15
Changed parameter
number
2
0 to 7
0 = no parameters have changed
1 to 255 = index number of the last parameter changed
8 to 15 Total number of parameters available in the starter
16-17
Changed parameter
value
2
0 to 13 Value of the last parameter that was changed, as indicated
in register 2
14 to 15
Reserved
18-19
Starter state
0 to 4
0 =
Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay, restart temperature check, run
simulation, input A (DI4, +24V) not shorted)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Unintialised
1 = Initialised
7
0 = Local control
1 = Remote control
8
0 = Parameter(s) have changed since last parameter read
1 = no parameters have changed
2
9
0 = Negative phase sequence
1 = Positive phase sequence
10 to 15 See Trip Codes on page 13
3
20-21
Current
0 to 13 Average rms current across all three phases
4
14 to 15
Reserved
22-23
Current
0 to 9
Current (% motor FLC)
10 to 15
Reserved
24-25
Motor temperature
0 to 7
Motor 1 thermal model (%)
8 to 15 Motor 2 thermal model (%)
26-27
Power
5
0 to 11 Power
12 to 13 Power scale
14 to 15
Reserved
28-29
% Power factor
0 to 7
100% = power factor of 1
8 to 15
Reserved
30-31
Reserved
0 to 15
32-33
Current
4
0 to 13 Phase 1 current (rms)
14 to 15
Reserved
34-35
Current
4
0 to 13 Phase 2 current (rms)
14 to 15
Reserved