Страница 2: ...g In the interests of commitment to a policy of continuous development and improvement the manufacturer reserves the right to change the specification of the product or its performance or the content...

Страница 3: ...Configuration 8 4 1 Ethernet Device Configuration Tool 8 5 Operation 10 5 1 Device Classification 10 5 2 Master Configuration 10 5 3 LEDs 10 6 Packet Structures 11 6 1 Ensuring Safe and Successful Con...

Страница 4: ...lable for Profinet Modbus TCP and Ethernet IP networks The Profinet Module operates at the application layer Lower levels are transparent to the user Familiarity with Ethernet protocols and networks i...

Страница 5: ...e top and bottom retaining clips to secure the module to the starter 5 Insert the network connector 6 Apply control power to the soft starter Figure 2 1 Attach the module to the starter 1 2 3 10178 B...

Страница 6: ...ote See the soft starter user manual for parameter details Figure 3 1 Profinet Module connections Digistart D2 Digistart D3 15633 A 1 3 2 15634 A 1 3 2 Digistart D2 Digistart D3 Remote mode CSL DI2 St...

Страница 7: ...st communication relation RTA Real time acyclic protocol Flexible RT_CLASS_2 Real time cyclic protocol Class 2 synchronised RT_CLASS_UDP Unsynchronised cross subnet communication between different sub...

Страница 8: ...ice Configuration Tool can be downloaded from www nidec com To configure the device using the Ethernet Device Configuration Tool 1 Attach the module to a soft starter 2 Connect one Ethernet port on th...

Страница 9: ...7 To set a static IP address click Configure then select Set IP address 8 To configure a device name click Configure then select Device Name Profinet Module User Guide 9 Issue B www nidec com...

Страница 10: ...on screen icons two graphic bitmap files are available from the website SSPM_N bmp indicates normal mode SSPM_D bmp indicates diagnostic mode 5 3 LEDs Figure 5 1 Feedback LEDs 1 2 T X R X 2 T X R X 1...

Страница 11: ...send a control command to the soft starter Table 6 1 Control I O data structure Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Reserved Reserved Reserved Quick stop coast to stop Motor set Res...

Страница 12: ...is value will be 10 times greater than the value displayed on the keypad Ready is set when the soft starter is ready to start the motor On is set when the soft starter is starting running or soft stop...

Страница 13: ...s the fault code detailed in the table below 201 Ground fault 23 Parameter out of range 24 Input B trip 26 L1 phase loss 27 L2 phase loss 28 L3 phase loss 29 L1 T1 shorted 30 L2 T2 shorted 31 L3 T3 sh...

Страница 14: ...VZC Fail Px 83 Low Control Volts 84 to 98 Internal fault X Contact your local supplier with the fault code X 6 3 4 Motor current Bytes 6 and 7 report motor current in amperes For models D3 1x 0053 B a...

Страница 15: ...heck run simulation input A DI4 24V not shorted 6 Tripped 7 Programming mode 8 Jog forward 9 Jog reverse 5 1 Warning 6 0 Unintialised 1 Initialised 7 0 Local control 1 Remote control 8 0 Parameter s h...

Страница 16: ...r 3 Changed parameter value will reset registers 2 Changed parameter number and 4 Parameters have changed Always read registers 2 and 4 before reading register 3 3 Bits 10 to 15 of register 4 report t...

Страница 17: ...ut byte structure Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte 2 Parameter number to read write Byte 3 Reserved Reserved Reserved Reserved Reserved Write parameter Read parameter Reserved Byte...

Страница 18: ...7 0 1 Read starter status Running Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 3 0 Read starter status Tripped trip code 4 Current imbalance Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte...

Страница 19: ...ntil all devices are connected Figure 7 2 Line network topology 14695 A NOTE The Profinet Module has an integrated switch to allow data to pass through in line topology The Profinet Module must be rec...

Страница 20: ...n turn connects to another module until all devices are connected The final module connects back to the switch Figure 7 3 Ring network topology 14696 A NOTE The network switch must support loss of lin...

Страница 21: ...Network RJ45 Settings IP address Automatically assigned configurable Device name Automatically assigned configurable Network Link speed 10 Mbps 100 Mbps auto detect Full duplex Auto crossover Power Co...