Commander S100 User Guide
67
P2.03
Frequency Reference Configuration
Range:
0 to 9
Default:
1 (Local/Remote)
Used to automatically set a group of parameters for common configurations as outlined below:
The table above shows the options to quickly set up the reference system for a specific application. The assignments are made on exit of the
parameter (Press settings button or back in Marshal).
The table below indicates the parameters that are set up and the values written.
“-” indicates that the configuration will not change the setting of the parameter from the current value.
For more detailed information and wiring diagrams refer to
section 6.3 Running, stopping and controlling motor direction.
Value Configuration
Description
0
Custom
The parameters in the table below have been changed from a standard reference configuration.
1
Local/Remote
A current input on analog input 1 and a voltage input on analog input 2. digital input 5 is used to select
between them.
2
Voltage/Preset Input
A voltage input on analog input 1. Digital input 5 and digital input 1 are used as binary switches to choose
between it and preset frequency references 2, 3, and 4.
3
Current/Preset Input
A current input on analog input 1. Digital input 5 and digital input 1 are used as binary switches to choose
between it and preset frequency references 2, 3, and 4.
4
Presets
Digital input 5 and digital input 1 are used as the binary switches to choose between the four preset
frequency references.
5
Keypad
The keypad buttons are used to control the frequency
Up/Down Percentage
(P1.18).
6
Terminal Up/Down
Digital input 5 and digital input 1 are used to control the
Up/Down Percentage
(P1.18).
7
Frequency Input
A frequency input on digital input 5.
8
PID Voltage Ref.
A Voltage input on analog input 1 as the reference, and a current input on analog input 2 as the feedback.
The PID output is used as the drive reference.
9
PID + Feed Forward
A Voltage input on T2 analog input 1 as the Feed Forward, and a current input on T4 analog input 2 as the
feedback, the PID reference is set by PID Fixed Reference Setpoint 1. The PID output is used as the
drive reference.
Parameter
Frequency Reference Configuration (P2.03)
0
1
2
3
4
5
6
7
8
9
Up/Down Percent Configuration
(P2.14)
-
-
-
-
-
3
0
-
-
-
Frequency Reference 1 to 4 Switch
(P2.20)
-
0
0
0
0
1
1
1
1
1
Frequency Reference 1 Selector
(P2.21)
-
5
5
5
1
8
8
7
9
9
Frequency Reference 2 Selector
(P2.22)
-
6
2
2
2
-
-
-
-
-
Frequency Reference 3 Selector
(P2.23)
-
-
3
3
3
-
-
-
-
-
Frequency Reference 4 Selector
(P2.24)
-
-
4
4
4
-
-
-
-
-
PID Reference Selector
(P5.03)
-
-
-
-
-
-
-
-
1
5
PID Feedback Selector
(P5.04)
-
-
-
-
-
-
-
-
2
2
PID Feed Forward Selector
(P5.05)
-
-
-
-
-
-
-
-
0
1
PID Enable Selector
(P5.11)
-
-
-
-
-
-
-
-
1
1
T2 Analog Input 1 Type
(P6.01)
-
3
0
3
-
-
-
-
0
0
T4 Analog Input 2 Type
(P6.02)
-
0
-
-
-
-
-
-
6
6
T11 Digital IO 1 Type
(P6.04)
-
-
0
0
0
-
0
-
-
-
T15 Digital Input 5 Type
(P6.05)
-
0
0
0
0
-
0
1
-
-
T11 Digital Input 1 Function Select
(P6.16)
-
-
11
11
11
-
8
-
-
-
T15 Digital Input 5 Function Select
(P6.20)
-
10
10
10
10
-
7
-
-
-
Содержание COMMANDER S100