9. INSTALLATION
The fan installation must be carried out only by competent and qualified staff.
9.1 Commissioning
Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe
personal injury or serious damage to material.
Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the
product should carry out work on the device/system.
The RDP fan must be grounded through the PE connector on the driver.
The following terminals can carry dangerous voltages even if the driver is inoperative:
the power supply terminals L, N or R, S, T
the motor terminals U, V, W
WARNING
WARNING
In the final installation, the device shall be directly connected to the supply terminals and shall have a con-
tact separation in all poles, providing full disconnection under overvoltage category III conditions.
WARNING
WARNING
9.2 Operation
The driver must NOT be removed from the related RDP fan type and size.
The driver cannot be used separate from the related fan.
WARNING
WARNING
Ensure correct grounding connections. The ground cable must be enough to carry the maximum supply fault
current which normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in
the main supply to the driver, according to any local legislation or codes.
WARNING
WARNING
The driver operates at high voltages.
Certain parameter settings may cause the driver to restart automatically after an input power failure.
CAUTION
CAUTION
9.3 Ambient operating conditions
The installation place must be in accordance with the IP protection degree of the fan. In this respect, refer
to the ID plate described in chapter 3.
Humidity Range: 90% non-condensing
Altitude: if the fan is to be installed at an altitude > 1000m, derating is required.
Shocks: do not drop the fan or expose it to sudden shock.
Vibration: do not install the fan in an area where it is likely to be exposed to constant vibrations.
CAUTION
CAUTION