Parameter:

4. Sound notifications status

Description:

This parameter allows to activate sound signals but does not apply to major alarms, such as Fire, Trouble and 

Low battery alarm.

Available settings:

0 - all notifications disabled
1 - casing opening notification enabled
2 - exceeding temperature threshold notification enabled 
4 - lack of Z-Wave range notification
Parameter values may be combined, e.g. 1+2+4=7, means that all notifications are enabled.

Default setting: 

0 (notifications disabled) 

Parameter size:

1 [byte]

Parameter:

10. Configuration of control frames in BASIC command class

Description:

This parameter defines which frames will be sent in the 2-nd Association Group (SMOKE ALARM). The values of 

BASIC ON and BASIC OFF frames may be defined as described in further parameters.

Available settings:

0 - BASIC ON & BASIC OFF enabled
1 - BASIC ON enabled
2 - BASIC OFF enabled

Default setting: 

0 (both frames enabled) 

Parameter size:

1 [byte]

Parameter:

11. BASIC ON frame value

Description:

BASIC ON frame is sent in case of smoke presence detection and Fire Alarm triggering. Its value is defined by the 

parameter.

Available settings:

0 - turn off the device
1-99 - set the device to 1-99% 
255 - set the last status

Default setting: 

255

Parameter size:

2 [bytes]

Parameter:

12. BASIC OFF frame value

Description:

BASIC OFF frame is sent in case of Fire Alarm cancellation. Its value is defined by the parameter.

Available settings:

0 - turn off the device
1-99 - set the device to 1-99% 
255 - set the last status

Default setting: 

0 (turn off the device) 

Parameter size:

2 [bytes]

Parameter:

13. Alarm broadcast

Description:

A value other than 0 means that alarms are being sent in broadcast mode, i.e. to all devices within Smoke-Con-

trol’s range.

Available settings:

0 – broadcast inactive
1 – SMOKE ALARM command broadcast (2-nd & 4-th Association Group) active; casing opening notification 

broadcast (3-rd & 5-th Association Group) inactive
2 – SMOKE ALARM command broadcast (2-nd & 4-th Association Group) inactive; casing opening notification 

broadcast (3-rd & 5-th Association Group) active
3 – SMOKE ALARM command broadcast (2-nd & 4-th Association Group) active; casing opening notification 

broadcast (3-rd & 5-th Association Group) active.

Default setting: 

0 (broadcast inactive) 

Parameter size:

1 [byte]

Parameter:

14. Associations in Z-Wave network security mode

Description:

This parameter defines how commands are sent in specified association groups: as secure or non-secure. Pa-

rameter is active only in Z-Wave network security mode. It doesn’t apply to 1st Lifeline group.

Available settings:

0 - all groups sent as non-secure
1 - 2nd group sent as secure
2 - 3rd group sent as secure 
4 - 4th group sent as secure 
8 - 5th group sent as secure
Parameter values may be combined, e.g. 1+2=3 means that 2nd & 3rd group are sent as secure.

Default setting: 

15 (all groups sent as secure) 

Parameter size:

1 [byte]

Содержание FGSD-002

Страница 1: ...EN Instructions and warnings for installation and use Smoke and temperature sensor Smoke Control Nice...

Страница 2: ...d ambient conditions fire alarms are not always effective in all situations Smoke Sensors must be tested regularly according to this operating manual and local code Ventilation sys tems chimneys and p...

Страница 3: ...lace of installation It s recommended to install the sensor on the ceiling or upper portion of the wall at least 40cm 2 feet from corners and other objects Particu lar attention should be paid to any...

Страница 4: ...ompletely discharged 6 2 Battery replacement Once a Smoke Control has reported low battery level or battery is discharged it should be replaced observing the following procedure 1 Detach the sensor fr...

Страница 5: ...B button After 3 sec onds from the first beep smoke chamber operation will be checked Triggering fire alarm and beep mean positive result and should occur within 10 seconds No fire alarm means that th...

Страница 6: ...update procedure GREEN sending device state to associated devices VIOLET Z Wave range test YELLOW device reset 10 ALARMS AND NOTIFICATIONS Smoke Control indicates particular states as follows Fire al...

Страница 7: ...ve groups 1st group Lifeline Reporting device state Only one device Z Wave network controller may be set in this group It s not recommended to modify this association group 2nd group Smoke Alarm Sendi...

Страница 8: ...ate with the main controller After each failed communication attempt the sensor will retry to establish a connection with the main controller after 60 seconds After 3 failed attempts the lack of the Z...

Страница 9: ...n case of Fire Alarm cancellation Its value is defined by the parameter Available settings 0 turn off the device 1 99 set the device to 1 99 255 set the last status Default setting 0 turn off the devi...

Страница 10: ...measured by the built in temperature sensor above which the excess temperature notification is sent visual indication sound Z Wave report Available settings 1 100 1 C 100 C Default setting 55 55 C Par...

Страница 11: ...ms and radio headphones which interfere with the control unit transceiver 12 PRODUCT DISPOSAL This product is an integral part of the automation and therefore must be disposed together with the latter...

Страница 12: ...www niceforyou com Nice SpA Oderzo TV Italia info niceforyou com IS0859A00EN_05 03 2022...

Отзывы: