Nice D-Pro Action Series Скачать руководство пользователя страница 14

14

 – English

EN

TABLE 3

DIP1 DIP2 DIP3 DIP4 Function

OFF

OFF

OFF

OFF

Hold-to-run movement

ON

x

OFF

OFF

Acquisition of positions and status of the ALT 
input

OFF

ON

OFF

OFF

Rotation direction of the encoder reversed

OFF

x

OFF

ON

Industrial mode (semi-automatic opening – 
hold-to-run closing), if positions recognised

OFF

x

ON

OFF

Semi-automatic mode, if positions recog-
nised

OFF

x

ON

ON

Automatic mode with adjustable pause time, 

if positions recognised (see para. 5.1.2 “Other 
functions” for info on saving the pause time)

3.11 -

 

Oview programming unit

Using  the  Oview  programming  unit  allows  you  to  manage  the  installation, 

maintenance and diagnosis of the entire automated system in a thorough and 

rapid manner.

You can connect Oview to the control unit via the IBT4N interface using a bus 

cable with 4 wires inside.

To access the BusT4 connector, you need to open the control unit box, plug 

the  IBT4N  connector  into  the  appropriate  slot  and  then  connect  the  Oview 

programmer (

Fig. 17

).

V

W

U

L1

L2

L3

d

b

c

ON

a

OFF

17

Oview  can  be  used  at  a  maximum  cable  distance  of  100  metres  from  the 

control unit; it can be connected simultaneously to multiple control units (up to 

16) and can remain connected even during normal operation of the automated 

system. When working with Oview, it is very important to observe the instruc-

tions in the Oview instruction manual.

If there is an OXI radio receiver in the control unit, when you use Oview you can 

have access to the parameters of the transmitters memorised in the receiver. 

For further information, refer to the Oview instruction manual or the control unit 

function sheet available from the website www.niceforyou.com

CAUTION! - If the functions of Table 3 are programmed with the Oview 

programming unit, it is necessary to set the dip switches to OFF.

4

TESTING AND COMMISSIONING

The testing and commissioning phases are the most important when creating 

an automated system in order to ensure maximum safety. The testing proce

-

dure can also be performed as a periodic check of the automation devices.

These phases must be performed by qualified and experienced personnel who 

must take charge of establishing the tests necessary to verify the solutions adopt-

ed in respect of risks and verify the compliance of the system with applicable 

standards, legislation and regulations, in particular all requirements of the standard 

EN 12445 which establishes the test methods for checking automated systems 

for doors and gates. The additional devices must undergo specific testing, both 

in terms of their functions and in terms of their interaction with the control unit; 

therefore, you need to refer to the instruction manuals for the individual devices.

4.1 - Testing

The sequence of steps to be performed when running the testing phase, as 

described below, refers to a typical system (

Fig. 2

):

1

 Check  that  all  the  instructions  in  the  “Installation  warnings”  chapter  have 

been rigorously complied with.

2

 Release the motor. Check that the door can be manually manoeuvred with a 

force no greater than 225N.

3

 Lock the motor.

4

 Using the control devices (transmitter, push button, key switch, etc.), test the 

Opening, Closing and Stopping of the door, ensuring that the movement of 

the door leaves corresponds to specifications. Test several times to assess 

the movement of the door and check for any defects in assembly or adjust-

ment and for any particular points of friction.

5

 Check, one by one, that all the safety devices featured in the system (photo-

cells, sensitive edges, etc.) work properly.

6

 If the dangerous situations caused by the movement of the door leaves have 

been safeguarded against by limiting the impact force, the impact force must 

be measured according to the EN 12445 standard.

4.2 - Commissioning

Commissioning can only be performed after obtaining positive results in all the 

test phases run on the control unit and the other devices (paragraph 4.1). 

It is 

not permissible to execute partial commissioning or to enable use of 

the system in “makeshift” conditions.
1

 Prepare and store the technical documentation for the automated system 

for at least 10 years. This must include at least: an assembly drawing of the 

automated system, a wiring diagram, an analysis of hazards and solutions 

adopted, a manufacturer’s declaration of conformity of all the devices installed 

(for the control unit, use the annexed CE declaration of conformity); a copy of 

the automation system instruction manual and maintenance schedule.

2

 Post a label on the door providing at least the following data: type of auto

-

mated system, name and address of manufacturer (person responsible for 

the “commissioning”), serial number, year of manufacture and “CE” marking.

3

 Post a permanent label or sign near the door detailing the operations for 

releasing the system and its manual operation

4

 Post a permanent label or sign on the door containing this picture (min. 

height 60 mm). 

5

 Prepare the declaration of conformity for the automation system and hand it 

to the owner.

6

 Prepare the “Instructions and warnings for the use of the automation system” 

and hand it to the owner.

7

 Prepare the maintenance schedule for the automation system and hand it to 

the owner; it must include all the instructions regarding maintenance of the 

individual devices.

5

FURTHER DETAILS AND DIAGNOSTICS

5.1 - Further details

5.1.1 - Signals when switching ON

When the D-Pro Action control unit is switched ON, the reaction of the green 

OK L2 LED and the red WARNING L1 LED is important, as shown in Table 4. 

In particular, it indicates whether:

- The recognition of the Opening and Closing positions is correct;

- The recognition of the (sensitive edge) safety device is correct and what kind 

of safety device has been recognised.

TABLE 4

Signals when 

switched on

Signal

GREEN OK 

L2 LED

RED WARNING 

L1 LED

Blank memory (no acquired 
position or safety device)

Rapid flashing for 5 

seconds

Rapid flashing for 5 

seconds

Positions acquired correctly 

and “8k2” safety recognised

Rapid flashing for 2 

seconds

Just one slow flash

Positions acquired correctly 

and “OSE” safety device 

recognised

Rapid flashing for 2 

seconds

Two slow flashes

After providing the signals shown in Table 4, the D-Pro Action control unit shows 

any errors through Diagnostics using the OK L2 LED and the WARNING L1 LED.

5.1.2 - Other functions
Status and diagnostics indicator (terminal on the keyboard)

The  control  unit  allows  you  to  connect  a  24V-5W  max.  indicator  light  to  the 

Содержание D-Pro Action Series

Страница 1: ...nstallazione e l uso FR Instructions et avertissements pour l installation et l utilisation ES Instrucciones y advertencias para la instalaci n y el uso DE Installierungs und Gebrauchsanleitungen und...

Страница 2: ......

Страница 3: ...product as described in this instruction manual and for certain types of use e g excluding use solely for vehicles may cause the product to fall within the scope of Regulation No 305 2011 and its har...

Страница 4: ...it is accessible to the public the command button must not be available to them e g use only with a key switch 2 For Semi automatic operation through the use of an active sensitive edge for limiting t...

Страница 5: ...und the product allows safe and easy access Check that all electrical cables to be used belong to the type listed in Table 1 Check that the automation has mechanical stops in both the opening and clos...

Страница 6: ...eed as follows when installing the control unit 01 Open the control unit box unscrew the screws as shown in Fig 3 A Fig 3 B 02 Prepare the holes for routing the electrical cables for the accessories p...

Страница 7: ...Cable for FLASHING LIGHT with aerial 2 x 1 mm2 for 230 V AC flashing light RG58 type shielded cable aerial 10 m D PHOTOCELL cable 4 x 0 5 mm2 10 m E KEY SWITCH cable 2 cables 2 x 0 25 mm2 10 m note 2...

Страница 8: ...inputs 8 com 24 V DC common 9 open 10 close 11 photo ing1 ALT ALT terminal SAFE only for motors with mechani cal limit switches leave uncon nected with motors which have electronic limit switches LIMI...

Страница 9: ...ing movement It is possible to connect contacts of the Normally Open type to this input ING1 photo 11 Normally Closed NC input for devices that control the movement of the automation If this input is...

Страница 10: ...echanical limit switch Fig 11A Three phase motor with electronic limit switch Fig 12A Three phase motor with mechanical limit switch and brake Fig 11B Three phase motor with electronic limit switch an...

Страница 11: ...E 2 SMXI SMXIS Receiver in Mode 1 or 2 output description Output No 1 Step by Step Output No 2 Partial open factory setting it opens to halfway this may be changed during the position acquisition phas...

Страница 12: ...ent procedures according to the different types of motor Motor with electronic limit switch encoder see paragraph 3 9 1 Motor with mechanical limit switch see paragraph 3 9 2 3 9 1 Recognition of the...

Страница 13: ...n 03 a Set the limit switch cam 1 E green Fig 16 to operate the limit switch b Tighten the locking screw A Fig 16 c For precision adjustment use screw B Fig 16 04 Press the Close button to move the do...

Страница 14: ...switch etc test the Opening Closing and Stopping of the door ensuring that the movement of the door leaves corresponds to specifications Test several times to assess the movement of the door and chec...

Страница 15: ...s for a few seconds then try sending a command again if the problem persists there may be a serious fault on the circuit board or on the connections of the motor Carry out checks and replace parts if...

Страница 16: ...no manoeuvre takes place and the flashing light is OFF check that the command is actually received if the command reaches the SS input the OK LED flashes twice to indicate that the command has been r...

Страница 17: ...erminal and gnd STOP 8K2 OSE terminal see Fig 7 STOP SAFETY EDGE Input For contacts that are normally closed normally open or of the 8 2k constant resistance type or the OSE optical type in auto recog...

Страница 18: ...harmonised standards EN 61000 6 2 2005 EN 61000 6 4 2007 A1 2011 In addition the product conforms to the following directive in accordance with the provisions applicable to partly completed machinery...

Отзывы: