Parameter:

13. Commands sent to 4th association group (CO Level)

Description:

This parameter defines commands sent to devices associated in 4th association group (CO Level). Values of 

specified commands may be set in parameters 16 and 19. 

Available settings:

1 - BASIC ON
2 - BASIC OFF
3 - BASIC ON & BASIC OFF

Default setting: 

3 (ON & OFF)

Parameter size:

1 [byte]

Parameter:

14. CO level required for sending BASIC ON command to 4th association group

Description:

This parameter defines the minimum level of CO concentration which exceeding will result in starting the timer set 

in parameter 15. 

Available settings:

25-400 - CO concentration level in ppm

Default setting: 

40 (40 ppm)

Parameter size:

2 [bytes]

Parameter:

15. Time required for sending BASIC ON command to 4th association group

Description:

This parameter defines the time during which the level of CO concentration should remain above the value set in 

parameter 14 to send the BASIC ON command to 4th association group. 

Available settings:

0 - immediate sending of BASIC ON command
1-2880 (30s - 24h, in 30s steps)

Default setting: 

0

Parameter size:

2 [bytes]

Parameter:

16. Value of BASIC ON command sent to 4th association group

Description:

This parameter defines the value of BASIC ON command sent to devices in 4th association group after exceeding 

the CO level set in parameter 14 through the time set in parameter 15.

Available settings:

0-99 or 255

Default setting: 

255 (turn on)

Parameter size:

2 [bytes]

Parameter:

17. CO Level required for sending BASIC OFF command to 4th association group

Description:

This parameter defines the level of CO concentration below which falling will result in sending the BASIC OFF 

command to 4th association group. 

Available settings:

10-400 - CO concentration level in ppm

Default setting: 

25 (25 ppm)

Parameter size:

2 [bytes]

Parameter:

19. Value of BASIC OFF command sent to 4th association group

Description:

This parameter defines the value of BASIC OFF command sent to devices in 4th association group after falling 

below the CO level set in parameter 17.

Available settings:

0-99 or 255

Default setting: 

0 (turn off)

Parameter size:

2 [bytes]

Parameter:

20. Temperature reporting time interval

Description:

Time interval (in seconds) between consecutive reports of temperature (done by built-in temperature sensor). 

Short time interval means more frequent communication, which results in shortened battery life.

Available settings:

0 - no periodical reports
10-1440 (5min - 12h, in 30s steps)

Default setting: 

0

Parameter size:

2 [bytes]

Parameter:

21. Temperature reporting hysteresis

Description:

This parameter defines a minimum change in temperature resulting in a report being sent to the main Z-Wave 

controller.

Available settings:

1-20 (0.5°C - 10°C, each 0.5°C)

Default setting: 

2 (1°C)

Parameter size:

1 [byte]

Parameter:

22. Threshold of exceeding the temperature

Description:

This parameter defines the temperature level, which exceeding will result in sending actions set in parameters 2, 3 

and 4.

Available settings:

1-85 (1°C - 85°C, each 1°C)

Default setting: 

55 (55°C)

Parameter size:

1 [byte]

Содержание CO Alarm-Control

Страница 1: ...EN Instructions and warnings for installation and use CO and temperature sensor CO Alarm Control Nice...

Страница 2: ...these symptoms even in healthy people It can also cause sleepiness vision problems including blurred vision ringing in the ears aching arms and legs irregular breathing fatigue and confusion At very...

Страница 3: ...ting Z Wave network To add the device to the Z Wave network manually 1 Place the device within direct range of the Z Wave controller 2 Set the main Z Wave controller in security non security adding mo...

Страница 4: ...e ceiling level The device should be installed on the wall at least 30 cm 1 ft away from the corners The device should not be installed in a bathroom next to heat sources within range of kids obstruct...

Страница 5: ...e self test procedure does not result in emitting sound and red light signal replace the device 1 Press and hold the button 2 The LED indicator will glow white and you will hear a short beep 3 Release...

Страница 6: ...than specified may result in explosion Dispose of properly observing environmental protection rules Use only type of battery specified in this manual and keep proper polarity CO Alarm Control can be...

Страница 7: ...me cases system response may be delayed Notification report The device uses Notification Command Class to report different events to 1st association group Lifeline Table A2 Notification reporting Noti...

Страница 8: ...0 Parameter size 1 byte Parameter 7 Associations in Z Wave network security mode Description Parameter defines how commands are sent in specified association groups as secure or non secure Parameter...

Страница 9: ...Parameter size 2 bytes Parameter 17 CO Level required for sending BASIC OFF command to 4th association group Description This parameter defines the level of CO concentration below which falling will...

Страница 10: ...vel which exceeding will result in sending a new value to the main Z Wave controller according to parameter 25 settings Adjusting the value allows to get the accurate data in case of danger and helps...

Страница 11: ...el 85 dBA at 3 meters 10 feet Operating temperature 0 50 C Operating humidity 10 95 RH without condensation Dimensions d x h 65 x 28 mm Radio frequency of individual device must be same as your Z Wave...

Страница 12: ...ces which if disposed of into the environment may cause serious damage to the environment or physical health As indicated by the symbol alongside disposal of this product in domestic waste is strictly...

Страница 13: ...www niceforyou com Nice SpA Oderzo TV Italia info niceforyou com IS0860A00EN_15 03 2022...

Отзывы: